Underfloor heating regulation, manifold balancing.

Поділитися
Вставка
  • Опубліковано 29 січ 2025

КОМЕНТАРІ • 44

  • @karstennevepetersen
    @karstennevepetersen 2 роки тому +6

    Thank You. This was just the explanation I have been looking for 😊

  • @HelmeElrawas
    @HelmeElrawas 2 роки тому +4

    Always useful, great explanation !!

  • @grandenauto3214
    @grandenauto3214 Рік тому +1

    Very useful…. I was wondering how to get equal flow for each circuit, especially for my system where I don’t want stagnant water in a loop

  • @kristofp3350
    @kristofp3350 2 місяці тому +1

    Hello thansk very very much. Small question: Is it wrong if my mark is not exactly in front from my perspective like in yours case. In my case is almost on side. From upper view yours is straight on 6 hour in my on 8/9 on left side.

    • @heatingsolutions123
      @heatingsolutions123  2 місяці тому

      Hi! It might happen mark is not exactly in front. There is no problem if so.

    • @kristofp3350
      @kristofp3350 2 місяці тому

      @heatingsolutions123 Ok. Thanks a lot. Just for my understanding: Mark position dosnt matter at all? For example can be on back, some on side? All idea is to find it and line up it with number (1-7) or N we want?

    • @heatingsolutions123
      @heatingsolutions123  2 місяці тому

      @@kristofp3350 Mark position should be visible from front or side. Main idea is a you say, to line it up with number 1-7 or N. N is factory setting, so marking will be lined to N

  • @robertnagy2456
    @robertnagy2456 Місяць тому

    Which temperatures would be the optimal on both water side? I don't have any specification for my system, but I think, if I measure the temperatures, I can find the optimal settings so.

    • @heatingsolutions123
      @heatingsolutions123  Місяць тому +1

      Max allowed temperature for underfloor heating should not exceed 50°C. Common supply/return temperature difference is 5-10°C. Supply temperature depends on house insulation, pipe distance in concrete, covering ...but mostly depends on outside temperature (location). Supply should be higher if outside gets colder. So the is no one common supply/return. We can only talk at design conditions. Let's say outside -20°C, supply 38°C, return 32°C and house is well insulated according to local norms.

    • @robertnagy2456
      @robertnagy2456 Місяць тому +1

      @@heatingsolutions123 Thanks

    • @robertnagy2456
      @robertnagy2456 27 днів тому

      An other question: on which side should I change the flow rate? On both sides possible this step.

    • @heatingsolutions123
      @heatingsolutions123  27 днів тому +1

      @ with presetting using setting knob 1,2,3,4,5,6,7,N N-is max. According pipe length and chart or if you have project with flow meters according flow rate from project. It is important ti use one ar another method, but not both at the same time :)

  • @GatoIB
    @GatoIB Рік тому

    In what position debitometers should be ? Fully open ?

    • @heatingsolutions123
      @heatingsolutions123  Рік тому

      To open flow meter. Turn flow meter counter clockwise. Flow meter thread should be visible.

  • @davideyres955
    @davideyres955 2 роки тому +1

    Do the actuators just open and close or do they regulate the flow? Just wondering how this works in the real world.

    • @heatingsolutions123
      @heatingsolutions123  2 роки тому +1

      It depends on room controller. Usually simple ON/OFF thermostats just open/close actuator +/- 0.5C from set point. More advanced are Danfoss Link, Icon 24V, Ally controllers... They can regulate flow to each circuit with pulse wide modulating signal the same ON/OFF actuator. In this case actuator may "modulate" and have more precise room control.

  • @logicalmind3230
    @logicalmind3230 Рік тому

    first of all, this is great video. i have a question. mine makes an extremely loud banging sound that lasts around 5 min when heating zones come on flow meter which keeps moving up and down.
    This does not happhen often like 3 times in 3 month. do you have any sugestions.

    • @heatingsolutions123
      @heatingsolutions123  Рік тому +1

      Probably wrong flow direction. Manifold with flow meters should be on supply, manifold with actuators on return. Here is a video on this topic: ua-cam.com/video/5hurO6e1xlc/v-deo.htmlsi=j7ddpy74ctndCtc5

    • @logicalmind3230
      @logicalmind3230 Рік тому

      @@heatingsolutions123 the sound is like video at 14 seconds to 18 seconds, and it will eventually stop with sound like pressure got released. any suggestions?

  • @HuseyinD44
    @HuseyinD44 10 місяців тому

    Hello, shouldn't the liter adjustment be made on the glass tube? Also, should they all be on when making adjustments via the tube?

    • @heatingsolutions123
      @heatingsolutions123  10 місяців тому

      If you know exactly how much litres/min you need for each cirquit you can adjust with flow meter. Another way is using presetting as on video.

    • @HuseyinD44
      @HuseyinD44 10 місяців тому

      @@heatingsolutions123 If they are all on, is the setting correct? Or should I move on to the next after setting one zone? Is there a video about this?

  • @gibbodive140
    @gibbodive140 2 роки тому

    Thank you for your presentation.
    How would this be achieved if you did not know the length of the circuits ? E.g On a system that has been previously fitted, no drawing are available, unknown pipe spacing etc ?
    Thank you

    • @heatingsolutions123
      @heatingsolutions123  2 роки тому +5

      In this case an option could be to open all circuits. Wait at least half a day. Measure return flow temperature from each circuit and try to make it the same. Temperature can be measured with infra red thermometer directly from return pipe. It takes time and patience.
      Using Danfoss Icon 24V, Danfoss Icon 2 commissioning is not so important. Systems has automatic balancing functionality. It can balance circuits using thermal actuators mounted on manifold. No drawing, no pipe length, no pipe spacing is needed. In case you got some very very short circuits Icon controller may ask to reduce flow on it.

  • @rsmaster5637
    @rsmaster5637 2 роки тому

    Thanks .. can you set a valve to have a minimum opening all the time ? I want to have a minimum flow in the heating system even when the heating actuator is off..

    • @TheZippyMark
      @TheZippyMark 2 роки тому

      Doubt it, I'd think the actuators are on/off. Why would you want that?

    • @heatingsolutions123
      @heatingsolutions123  2 роки тому

      With presetting it is not possible. Valve works separately from presetting. Only way is to something hand made:) Like washer on needle....

  • @flaviusvirlan3406
    @flaviusvirlan3406 11 місяців тому

    Some folks do this balancing on the flow meters, by taking the red caps off and setting the flow on the setting wheel. Is it a mistake ?

    • @heatingsolutions123
      @heatingsolutions123  11 місяців тому

      Setting on flow meters is another way of circiut balancing. Where do they get needed flow to set? Setting all flow meters at same flow would be a mistake if circuits are not same length.

  • @joaosidonio7562
    @joaosidonio7562 Рік тому

    Don't the actuators control the flow rate according to the heat required by the system?
    Or they just open/close?
    I am looking at the Emmeti control T and it doesn't have any flow rate regulation, hence it probably needs some flow valves anyway
    Apparently the flow rate is length of pipe/40 - so it depends what is the length of the pipe. I have a schematic of mine so I know what is there.
    The example you show 100m to be 2.5 is 100/40 which is 2.5l/min

    • @heatingsolutions123
      @heatingsolutions123  Рік тому

      In case you got manifold without presetting you can use Danfoss Icon or new Icon2 automatics. It has automatic circuit balancing with actuators. Icon controller has PWM control signal. It allows to "hang" actuator on middle position, not only ON/OFF. One thing you should check is it allowed to use PWM signal with your actuators using Icon control: ua-cam.com/video/52wKnb-YC9A/v-deo.htmlsi=tGYU5j58JU1X-97k

    • @joaosidonio7562
      @joaosidonio7562 Рік тому

      @@heatingsolutions123 why are the flowmeters installed at the top and not bottom?
      I had an issue where the actuator's plastic broke, exposing it and the bleeding valve went and when I went to check the system, it was live since water dripped on the actuator because it was at the on the bottom section of the manifold

  • @izmirfication
    @izmirfication 2 роки тому

    If heated water first enters the return manifold which the actuators are mounted , and water after completing the circuit gets into the manifold with flowmeters(glass tubes)
    Does this kind of application have any drawbacks or risks while the heating system operates ??

    • @heatingsolutions123
      @heatingsolutions123  2 роки тому

      No good. Flow meters will not work on reversed flow. Integrated valves on return manifold if mounted with actuators will be making "knocking" noise while closing. You should dismount manifolds on a right way. Supply manifold with flow meters, return manifold with actuators.

  • @vanmore5124
    @vanmore5124 2 роки тому +1

    Mine don't have the n and the numbers.

  • @Mk-fb4ns
    @Mk-fb4ns 2 роки тому

    The maximum for circuit its 100m and i have 7 circuits. Circuit 1. 75m, circuit2 75m ,circuit3- 126m(to long i think) circuit4 -72m,circuit5-55m,circuit6-98m,circuit7-100m. How I can to echilibrait the system?? Thank you

    • @heatingsolutions123
      @heatingsolutions123  2 роки тому

      Chart for d20 pipe is up to 120 meters. You can use that one, link to pdf file is here: assets.danfoss.com/documents/latest/202878/AN17038645953600-000301.pdf

  • @EliteHydronics.
    @EliteHydronics. Рік тому

    Giacomini manifold that