Sir mere pass same vfd hai dumb elevator me lagi hai. J se hi elevator ko run command dete hai. Vfd band ho jati hai. Please suggest about this problem rectify
I faced one issue with this vfd..from local it working but I can't able to run it through PLC.. At DI 4 to 20ma a got while increase or decreasing the frequency from control room. Can u help me on this..??
I'm using atv320 I can't see UFT *sensors essentially vector control* in drc menu. I have set motor control type ctt to expert . What might be the reason?
Dear please do as below: Cause: NLP means no line power or no line voltage. The drive thinks that there is no input voltage coming into the drive. Resolution: Check and verify the line voltage on L1, L2 and L3 of the drive. Go to the MON menu and check the ULn Mains voltage to see what the drive thinks the main voltage is. Verify DC bus voltage on PA+ and PC-.
@@j.s.electricalinstrumentat2146 I have checked L1, L2 & L3 and it's showing 415V, ULn is 242V, DC Bus voltage is 345.5V. Now please let me know if it's ok or not, where is the problem.
hello sir my Bangladesh se bol raha hoo,, Altivar ATV 320 lekar main bahut problem mein hun sar, mujhe aap ki madad ka bahut jarurat hai sar,, please help me 🙏🙏🙏
Very nicely explained sir ji ...thank you sir😊
Thank you 🙏 ek bar me chal gai motor 😊
Sir aapne bahut hee achhe samjhta ❤❤
Aap ka trika bhut hi achcha h batane ka🙏🙏
Thanks
Very nice sir
Your teaching method very simple
Thank you very much sir , you are great 👍👍👍👍❤❤❤❤❤
Sir mere pass same vfd hai dumb elevator me lagi hai.
J se hi elevator ko run command dete hai.
Vfd band ho jati hai.
Please suggest about this problem rectify
Bigger potassium ke RPM kam jyada ho sakte hain kya
Schneider me trip free threshold ka function available hai kia? Jis tarha invt me pb.04 hota hai
Nice superb idea 🎉
Bahut badhiya video, Sir 👍
Okay
Very nice vedio sir, sir aur video banaye
Thanks
I faced one issue with this vfd..from local it working but I can't able to run it through PLC.. At DI 4 to 20ma a got while increase or decreasing the frequency from control room. Can u help me on this..??
I thing it's for 10v reference type
How many ohms potentio meter you suggest for 1.5 hp atv320
Dear
5 Killo-ohm potentiometer
Good job Sir 👍
Sir motor ko jog mode mein kaise chlayein
Thank you sir !!
Can you please send me an image of paper you explaining on ?
I'm using atv320
I can't see UFT *sensors essentially vector control* in drc menu.
I have set motor control type ctt to expert . What might be the reason?
Merci ❤
What's 2/3 wire Control?
Thanks
Brother mujhe es company ki Lt, CT, aux and MH sabhi panal ki jankari chahiye.
Very nice sir
Thanks
Thanks and great support
Thanks
Thanks sir
Iss drive per fault showing nST kese thik kare
Thankyou sir
Ok
Schneider ATV320055N4B sar vfd per video bnao
Nice sir ji
Thanks
I m using ATV320 VFD and my problem is that my VFD is showing nLP and its not getting power up. help me please
Dear please do as below:
Cause:
NLP means no line power or no line voltage. The drive thinks that there is no input voltage coming into the drive.
Resolution:
Check and verify the line voltage on L1, L2 and L3 of the drive. Go to the MON menu and check the ULn Mains voltage to see what the drive thinks the main voltage is.
Verify DC bus voltage on PA+ and PC-.
@@j.s.electricalinstrumentat2146 I have checked L1, L2 & L3 and it's showing 415V, ULn is 242V, DC Bus voltage is 345.5V.
Now please let me know if it's ok or not, where is the problem.
Thank you sir
Thanks for watching videos
Nice video
Thanks
Good Sir.
Thank you so much sir 🙏🏻
Thanks
Vfd 420 ki bajay 110 nikal raha hai to kya karna sahiye
Forward & reverse jog parametr pls
Thank
Nice
To sir nice video
Thanks
In this vfd I want to know how I can set fix RPM without the potentiometer?
Dear
put requried rpm value in minimum rpu
Good sir
Thanks
Sir with out potential meter remove connection .only using vfd pls send me sir
How to increase its torque
I need your help
.18 kw moter ka parameter kya Hota hai
Thanks 🙏
Como aumentar el par en el altivar 320
Pl send blc settings for crane application
I watched yr all video related to this model drive.. But can't get solution.. 🙄
What is OPFi
1 Output phase loss
Motor 1-phase loss
Sir what is the meaning of OHF ?
OHF Meaning: Over Heating Fault. Drive temprature to high.
Rpm meter ka pemameter kya hai sir
Manual ko sar discretion mein dal dena
hello sir my Bangladesh se bol raha hoo,, Altivar ATV 320 lekar main bahut problem mein hun sar, mujhe aap ki madad ka bahut jarurat hai sar,, please help me 🙏🙏🙏
Apni problem likho
@@j.s.electricalinstrumentat2146 aapke reply ka intezar korta korta hum ne use program Ko hi change kiya
रिले के बारे में बताओ पैरामीटर R A R c
Watch this video
ua-cam.com/video/WpTc7zx5yx0/v-deo.html
Hello sir
Potencial meter ka parameter bataye hi nahi
Sir , do you provide me manual in pdf form?
Yes share me your mail ID
@@j.s.electricalinstrumentat2146 me too required Manual for it please
especially for troubleshooting