I have a total of 20 Shelly products installed in my house. I am super happy that there are such good and affordable devices. Who is looking for Smarhome devices should definitely have Shelly in mind.
I recently bought a whole lot of Sonoff Mini switches connecting to my Zigbee network. I'm running out of IP addresses on my router, so Zigbees are my preferred devices now.
I think, that there is a further bug: AC Loads does not show correctly. The Venus OS does not add the PV Inverter production to the loads. If PV is 500W and the inverter is adding further 50W, it should show 550W on the AC Loads...but it only shows 50W. Thank you for this Video and thanks you all Developers of those integrations!
Yes, if the AC-In is set to Generator, it won't be added. I've set the option to Grid now and it works. Martin thinks, the script may only work with ESS and grid connected systems. He hasn't got to time to further look into it, so I'm looking for another solution...😐
You could work with a ET112 and RS485 to USB-converter, that nativly integrates into Venus OS (EM24 DIN or EM540 or EM530 [current clamps] for more than 1 Phase). @@OffGridGarageAustralia
Great video, it showed me a lot of very useful info, thank you! I have a different, but similar problem, trying to add a second inverter to the Cerbo GX: The background: My Victron system is in a small travel trailer. I full time in the travel trailer and try to stay off the grid as much as possible. While I LOVE the dual MultiPlus II 3000 because I can run anything and everything I need, for 95% of my needs the overhead is too high for running the light day-in/day-out A/C loads I need all day long: computers, monitors, Starlink, CPAP machines, and other small devices. I already own one of the smaller 800VA Victron inverters and plan to wire that up to run the loads. The problem: I have heard the Cerbo GX can only show one inverter group (the dual MultiPlus II). So I was going to install the SmartShunt on the DC side of the 800VA inverter and the Shelly EM + 50A Clamp on the AC side. Is there any way to configure the Cerbo-GX so I can track the usage of this inverter? I am also thinking of adding a Shelly Plus 1 to turn the 800VA inverter on and off. I would love to get that on the Cerbo GX, too. I am guessing this is outside your knowledge base, but can you point me to those that might be able to help?
Hey Andy - I recognise the background music you used. Is music by Australian composer Sven Libaek (well, born in Norway, but lives & works in Oz). Nice choice. He's written so much music for Australian movies & TV series.
Note that ssh should be native in modern Windows OS (so no need for Putty). Also, vim is the editor of Linux 😅 Finally, you may want to set a static DHCP address for your Shelly as it could change otherwise making your script look for the wrong address.
@pau1phi11ips, I assume this is you: github.com/pau1phi11ips/dbus-venus-mqqt-pvinverter I've tried your script as well on my Cerbo but with the same result: generator shows negative figures and Total Solar is not combined. If I set Grid as AC-In, it still shows negative numbers for AC-In but at least the Total Solar is correct now (MPPTs plus PV Inverter) Are you able to help and troubleshoot? Happy to colab and get something done. My email is under the About tab on YT. Martin is not keen to investigate further as the script works for him and his ESS 🤷♂️
@@OffGridGarageAustralia In the Cerbo remote console, what do you have the recently added Shelly device set to within Setup > Position? Likewise for other devices?
Hey Andy. These micro inverter series was really intresting, how to set up the victrons and so forth. Im thinking these would come in handy for spare panels and for example for vertical fits on the walls of the garage or something like that. Thanks for videos, cheers.
Very nice, congrats. I understand the reason for the shelly but to know the production of the micro inverter you should use Solarman integration it will give much more information that the one you get from shelly. Since you are using Hassio you can install one more shelly in the pump and only have it running when the microinverter can fully power it.
Andy solarman integration updates de data every minute, it will talk direct with the microinverter, has long you can connect to the microinverter thru wifi I'm sure it will work. Hassio - HACS - Integrations - search Solarman Integration - restart - settings - integrations - open solarman - put the data of your microinverter, mine gave me 55 parameters. Let me know if you need help.@@OffGridGarageAustralia
I'm running a Plus1PM in a similiar configuration for testing purposes and just recently found the reporting into the vrm not working anymore after turning the Shelly off and on again. Had to ssh into venusOS and restart the dbus-service for the given Shelly (no need to reboot!). This is with static IP set both in the shelly and directly in the switch that manages the whole network. In case you encounter a similiar problem...
Hmm, strange. I have turned off my Shelly a few times so far but it always came back in the VRM after turning it back on. I also have a static IP for the Shelly. Do you use the same script?
@@OffGridGarageAustralia same GitHub repo, yes, but maybe not the same version as my installation is already some months old, I'll check if I can update. Also i'm pretty sure that everything worked fine some months ago, maybe it was just a hickup
Andy, 1. You can use the "Victron GX modbusTCP" to get all VRM data to the Home Assistant, control Multiplus, dynamically control EV charging, based on available PV production / battery SoC, etc. 2. Multiplus losses are 30%, when charging from AC and then inverting from the battery. Huge loss of the tilting benefits 😞 (3). Shelly 1pm is not robust for such wattage. Shelly EM, with the 2x A clamps is much better with no inline connections to the inverter/consumption.
Thanks you. I think I have used that as an HACS integration already. It works well. The power of the tilt system will mainly go directly into the pool pump, the house pressure pump and the SPAT fridge. Some small excess will go back to the garage. I have seen a video where someone calculated all the losses of the MP and charging efficiency was actually surprisingly good with around 80-85% The Shelly runs a treat since installation, no problems so far. It's only 7A which is going through it, less than half of what it is rated for.
@@OffGridGarageAustralia Trivial losses for direct use and 4x MPPTs, good job. You can add the "vebus acin1toinverter" and "vebus invertertoacout" entities at the Energy Dashboard and check the MP losses when using AC charging + inverter. For DC charging + inverter the 80-85% seems correct. 7A for 1pm is ok for just measuring energy. Using the internal relay for 7A loads on-off can be too high, depending on loads. Actually its not measuring energy, like grid meters / inverters, just gets a power measurement every second, so some % inaccuracy, depending on variations, not so important.
Super! Thank you and Martin! Very useful! And please please publish Igor’s solution when it’s ready. I am pretty sure you already have MQTT servers, might be even couple of them :) But that’s another topic (currently my system is down as we moved to our new home so can’t check it and write instructions how to use it), maybe will do it when system will be back and running. I do not have Shelly but a lot of Sonoff’s as well as bit hacked circuit breakers with power metering options (as Shelly one isn’t dirty cheap). Any way, thanks once again from sunny NZ and keep your amazing work! Hope one day will be able to bring you some beer in person ;) Thanks Andy!
it seems that Martin has changed his integration scrips and they work only with the shelly 1pm - not with the plus version anymore. any idea, how i get my plus 1pm functioning? thanks!
Is it possible to use another instance of shelly 1PM attached to Old Good Xijia 3kW Inverter to show them as AC LOAD on VRM? It would be a super option for ppl like me, which doesn't have Victron Multiplus Inverters (yet ;)) Great video Andy
Well, you don't need the Multiplus to show the Shelly in VRM. It also works in my SPAT Calibration Centre for testing purposes. But yes, there is a thread on the Victron Community forum where people have modified the script so it shows a load instead of a PV Inverter. Search for the word 'load': community.victronenergy.com/questions/127339/shelly-1pm-as-pv-inverter-in-venusos.html
My friend had micro inverters at his house with panels. Problem: they produce a lot of RF interference, being a Amateur Radio operator, the interference disappears with no sun, he got rid of them and went with a single MPPT charger. He can now communicate during the daytime. Some manufactures are not following RF radiation compliance rules.
I cannot use MPPTs in this location as it is too far away from the battery. AC-coupled solar is the only solution. I don't know anything about RF interference. Should the manufacturer take care of such a problem?
Hi Andy, doesn't the Shelly have the Outbound Websocket support? In that case you don't need anything, just point it to Venus OS and it will popup as a meter you can configure for PV Inverter. No MQTT , no root, and no other difficulties required
I have no idea how this would work. Quick Google search, it seems to be the Gen2 of the Shelly switch which has that. But still needs some sort of script in Venus OS? Happy to test a simpler solution if there is one.
One question.I appreciate much this video but I have a question. I have a installation of 4,4KW or 6KW with a Multiplus II solar inverter. I am not interested now (probably in medium term) in integrating a shelly switch to get more data. So, without applying what you recomend is it possible to get data from that inverter to home assistant? Just to get data, even if they are not the right ones. Note: the ip of the inverter pannel is a fixed ip.
Grüße nach Australien aus Germany ;D eine Frage habe an meiner Batterie einen PV inverter (Lumentree600) den ich auch wie Du per Shelly im VRM nur anzeigen lassen will ohne dass er als weiterer PV Ertrag mit eingerechnet wird. Kann man das deaktivieren? Habe 3 Victron Laderegler die ja im VRM dokumentiert werden und den Inverter will ich da ja nicht mit drin haben. *grübel* kann man den separat dokumentieren lassen?
I have tried the same with my grid connected Fronius inverter from the house solar. It shows in Victron but will be added to the Total Solar even it is a standalone system and not feeding into the battery. I just wanted it to show the actual power production, same like you. The only 'solution' I found is setting the AC-Input to Generator (Settings - System Setup). Then, it shows the inverter in VRM without adding it to the Total Solar. BUT, it also shows this power then as a Generator power in the statistic. So, no, this is not possible, at least not with this script.
@@OffGridGarageAustralia ok so the generator is displayed and the PV inverter at the same time? You can not set that the generator is only displayed? I wouldn't care about the name if you knew it was my Lumentree. I have a 1PM Plus here, but I'm afraid of destroying my statistics for the last few months, I think I'd better leave it alone ;D Thanks again and many sunny spring days.
Just to add that the shelly plus 1pm works with grid tied PV inverters too. I simply had to reverse the Live and output "O" wires, with the switch always "ON". The Shelly then operates in reverse, but still provides a positive (solar generation) reading.
@@OffGridGarageAustralia Thanks for the reply. Just to confirm that I have connected the Shelly Plus 1PM to the Shelly Cloud only so far. It indicates positive power when generating - in my case up to 3.5 KW - and positive power when idle,
@@georgebajan5691I have tested the script on my Cerbo and downgraded and upgraded the system again and both ways the integrations seems to keep working. I think there was some info on the github page which explained the mechanic they implemented in their script to ensure that. That does not mean it wont break with a future update though. And thanks for the kind words and feedback in your last comment.
hello, for me this somehow didn't work, I did all the steps, and all seemed to be working fine, just that the files are not seen in the Cerbo directories, neither the shelly connects in the VMR. Any hints what could be the issue??
HELP. Please. My cheap epever charge controler burned out . I'm looking for a victron replacement 100 / 50. Would be perfect . Looking for a used one . I can't afford new
does this require the shelly to have a static ip-address? in most cases, the ip-address is given by the dhcp server (or in most cases your internet router) - so the ip of the shelly might change after the next reboot ...
If the router restarts, it may hand out a different IP address to the Shelly and the script would stop working. So, yes, highly recommended to setup a static IP for the Shelly or do a IP address reservation in your router.
@@herwigg3327 I think the static IP is a must for such devices or something may stop working at some stage and it's hard to troubleshoot. I personally keep a list of all devices and MAC addresses on my network and if the IP is either static, router reserved or dynamic. It helps a lot to identify and resolve issues quickly.
I needed to change the position of the integration. It is in the file dbus-shelly-1pm-pvinverter.py in line 52. A zero means it is on the AC Input side and position 1 is for connected to output 1 of the multi. I think this will fix the problem with the AC Input Box.
You have to try and see if it works. I could not alter the ini file without losing all the data being transmitted. So, mine shows L1, L2 and L3 even I'm using only L1.
Hi Andy. Any ideea why i'm not getting that icon in the vrm portal ? Also no icon in the remote console. I can see just the consuption graphic. Thanks. Have a great day. Maybe because i'm using a non victron inverter ?
I'm using a none Victron inverter as well. The script works with the Shelly not the inverter so should just work. 1. Do you see the Shelly in the Device List in VRM? 2. what Venus OS version and device are you using? 3. rebooted the device after installing the script? 4. have you used the exact same script I have shown in the video?
1. Yes 2. I'm using 3.10 venus os on raspi 2. 3. Yes 4. Yes. I am able to see al the information in remote console in device list but no icon. If you agree i can sent some print screens via email to you. Just for an opinion. I don't want to bother you.
@@OffGridGarageAustralia Nice but for DC 48V system i would need up to 100A current.. If there was that option then for sure that would be perfect for most systems that don't come with option to connect to Victron systems.
@@OffGridGarageAustralia now Andy question is ..Can it be set as Power Generator instead of only smart shunt ? Will it show as lets say new extra unit ..and if you will put two shunts will it say Power Generator 1 and 2 for example ? That might be worth to test it.
Yes, I have the ET 112 as well but the installation location of the micro inverter is too far away from the garage where my Victron is. I know they have a Zigbee adapter...
Moin, For some reason I installed the wrong code. It was for the Shelly 1. But I have the Shelly 1 Plus installed. Now I have 2 programs running and it does not work. So my question is... How can I remove it all so I can start over with the right one? Anyone? Thankx
Since it is a single phase script I would not dbus init the phases not in use. Then they won't show up as L2 and L3 with 0 value. It takes unnecessary space in the console.
Super vidéo 😀😀.
J'attends avec impatience l'intégration de victron VRM dans home assistant 😁😁😁
Nice to see others who have the skills and time to contribute to better educate the community. Cheers from Michigan, USA
Thanks 👍
I have a total of 20 Shelly products installed in my house. I am super happy that there are such good and affordable devices. Who is looking for Smarhome devices should definitely have Shelly in mind.
I recently bought a whole lot of Sonoff Mini switches connecting to my Zigbee network. I'm running out of IP addresses on my router, so Zigbees are my preferred devices now.
Thanks Andy, nice integration 👍Looking forward to the home assistant integration
Yay, another video! As always, thanks Andy 👍👍
Thanks, Dave!
Very interesting stuff. Thanks to all the OGG community. 👍
Yes, great people making great things work.
That sky is pretty much what I've had all of July and August in northern Ireland
Oh, wow... 😑
I think, that there is a further bug: AC Loads does not show correctly.
The Venus OS does not add the PV Inverter production to the loads.
If PV is 500W and the inverter is adding further 50W, it should show 550W on the AC Loads...but it only shows 50W.
Thank you for this Video and thanks you all Developers of those integrations!
Yes, if the AC-In is set to Generator, it won't be added. I've set the option to Grid now and it works.
Martin thinks, the script may only work with ESS and grid connected systems. He hasn't got to time to further look into it, so I'm looking for another solution...😐
You could work with a ET112 and RS485 to USB-converter, that nativly integrates into Venus OS (EM24 DIN or EM540 or EM530 [current clamps] for more than 1 Phase).
@@OffGridGarageAustralia
Is there a solution already?
Thanks Andy and the work that you do. 😊
Thank you.
Great video, it showed me a lot of very useful info, thank you!
I have a different, but similar problem, trying to add a second inverter to the Cerbo GX:
The background:
My Victron system is in a small travel trailer. I full time in the travel trailer and try to stay off the grid as much as possible. While I LOVE the dual MultiPlus II 3000 because I can run anything and everything I need, for 95% of my needs the overhead is too high for running the light day-in/day-out A/C loads I need all day long: computers, monitors, Starlink, CPAP machines, and other small devices. I already own one of the smaller 800VA Victron inverters and plan to wire that up to run the loads.
The problem:
I have heard the Cerbo GX can only show one inverter group (the dual MultiPlus II). So I was going to install the SmartShunt on the DC side of the 800VA inverter and the Shelly EM + 50A Clamp on the AC side. Is there any way to configure the Cerbo-GX so I can track the usage of this inverter? I am also thinking of adding a Shelly Plus 1 to turn the 800VA inverter on and off. I would love to get that on the Cerbo GX, too.
I am guessing this is outside your knowledge base, but can you point me to those that might be able to help?
I like the part where you call yourself a lazy bastard. 😂 Thanks for the video. Interesting.
I am sometimes and have to call myself out! 😉
Hey Andy - I recognise the background music you used.
Is music by Australian composer Sven Libaek (well, born in Norway, but lives & works in Oz).
Nice choice. He's written so much music for Australian movies & TV series.
Note that ssh should be native in modern Windows OS (so no need for Putty).
Also, vim is the editor of Linux 😅
Finally, you may want to set a static DHCP address for your Shelly as it could change otherwise making your script look for the wrong address.
vim isn't installed in Venos OS
@@pau1phi11ips ok, good old vi then 😆
@pau1phi11ips, I assume this is you: github.com/pau1phi11ips/dbus-venus-mqqt-pvinverter
I've tried your script as well on my Cerbo but with the same result: generator shows negative figures and Total Solar is not combined. If I set Grid as AC-In, it still shows negative numbers for AC-In but at least the Total Solar is correct now (MPPTs plus PV Inverter)
Are you able to help and troubleshoot? Happy to colab and get something done. My email is under the About tab on YT.
Martin is not keen to investigate further as the script works for him and his ESS 🤷♂️
@@OffGridGarageAustralia In the Cerbo remote console, what do you have the recently added Shelly device set to within Setup > Position? Likewise for other devices?
Still no solution?😢
I love your channel. very good job.
A perfect BMS remains a bottle neck.
greetings from Belgium.
Hey Andy.
These micro inverter series was really intresting, how to set up the victrons and so forth. Im thinking these would come in handy for spare panels and for example for vertical fits on the walls of the garage or something like that. Thanks for videos, cheers.
Very nice, congrats. I understand the reason for the shelly but to know the production of the micro inverter you should use Solarman integration it will give much more information that the one you get from shelly. Since you are using Hassio you can install one more shelly in the pump and only have it running when the microinverter can fully power it.
The solarman integration gives me only data every 5 minutes, while the Shelly provides live data.
Andy solarman integration updates de data every minute, it will talk direct with the microinverter, has long you can connect to the microinverter thru wifi I'm sure it will work. Hassio - HACS - Integrations - search Solarman Integration - restart - settings - integrations - open solarman - put the data of your microinverter, mine gave me 55 parameters. Let me know if you need help.@@OffGridGarageAustralia
Hervorragend, diese Infos habe ich gesucht und wie immer sehr verständlich erklärt, thank you
I'm running a Plus1PM in a similiar configuration for testing purposes and just recently found the reporting into the vrm not working anymore after turning the Shelly off and on again.
Had to ssh into venusOS and restart the dbus-service for the given Shelly (no need to reboot!). This is with static IP set both in the shelly and directly in the switch that manages the whole network. In case you encounter a similiar problem...
Hmm, strange. I have turned off my Shelly a few times so far but it always came back in the VRM after turning it back on. I also have a static IP for the Shelly. Do you use the same script?
@@OffGridGarageAustralia same GitHub repo, yes, but maybe not the same version as my installation is already some months old, I'll check if I can update. Also i'm pretty sure that everything worked fine some months ago, maybe it was just a hickup
Heya, nice that you can see now all your pv in and all loads in 1 screan nice
Andy, 1. You can use the "Victron GX modbusTCP" to get all VRM data to the Home Assistant, control Multiplus, dynamically control EV charging, based on available PV production / battery SoC, etc. 2. Multiplus losses are 30%, when charging from AC and then inverting from the battery. Huge loss of the tilting benefits 😞 (3). Shelly 1pm is not robust for such wattage. Shelly EM, with the 2x A clamps is much better with no inline connections to the inverter/consumption.
Thanks you. I think I have used that as an HACS integration already. It works well.
The power of the tilt system will mainly go directly into the pool pump, the house pressure pump and the SPAT fridge. Some small excess will go back to the garage. I have seen a video where someone calculated all the losses of the MP and charging efficiency was actually surprisingly good with around 80-85%
The Shelly runs a treat since installation, no problems so far. It's only 7A which is going through it, less than half of what it is rated for.
@@OffGridGarageAustralia Trivial losses for direct use and 4x MPPTs, good job. You can add the "vebus acin1toinverter" and "vebus invertertoacout" entities at the Energy Dashboard and check the MP losses when using AC charging + inverter. For DC charging + inverter the 80-85% seems correct. 7A for 1pm is ok for just measuring energy. Using the internal relay for 7A loads on-off can be too high, depending on loads. Actually its not measuring energy, like grid meters / inverters, just gets a power measurement every second, so some % inaccuracy, depending on variations, not so important.
@1:34 ohhhh I GOT TO get me one of them!
My son got me this years ago 😂
My best guess of why there’s fronius logo, because script is emulating Fronius in AC coupling
It's gone now. I also had the Fronius inverter setup in Victron and it grabbed the logo. All fixed.
Super! Thank you and Martin! Very useful! And please please publish Igor’s solution when it’s ready. I am pretty sure you already have MQTT servers, might be even couple of them :) But that’s another topic (currently my system is down as we moved to our new home so can’t check it and write instructions how to use it), maybe will do it when system will be back and running. I do not have Shelly but a lot of Sonoff’s as well as bit hacked circuit breakers with power metering options (as Shelly one isn’t dirty cheap). Any way, thanks once again from sunny NZ and keep your amazing work! Hope one day will be able to bring you some beer in person ;) Thanks Andy!
Thank you and yes, I will post the other solution once it works.
I don't have any MQTT servers running. At least not that I'm aware of.
That sky is my typical English sky ...
Oh, wow...you need a lot of solar.
@@OffGridGarageAustralia and a battery to last a week ;) but I make it work.
@@KevIsOffGrid I can see your beard is getting longer and longer 🧔♂😉
I was thinking the same, that's "Cornish Sunshine"
Great video
Thanks!
it seems that Martin has changed his integration scrips and they work only with the shelly 1pm - not with the plus version anymore.
any idea, how i get my plus 1pm functioning?
thanks!
Same issue here ....
Is it possible to use another instance of shelly 1PM attached to Old Good Xijia 3kW Inverter to show them as AC LOAD on VRM? It would be a super option for ppl like me, which doesn't have Victron Multiplus Inverters (yet ;))
Great video Andy
Well, you don't need the Multiplus to show the Shelly in VRM. It also works in my SPAT Calibration Centre for testing purposes.
But yes, there is a thread on the Victron Community forum where people have modified the script so it shows a load instead of a PV Inverter. Search for the word 'load': community.victronenergy.com/questions/127339/shelly-1pm-as-pv-inverter-in-venusos.html
Du bist der Hammer Andreas ❤️🤩
Thank you, Klaus.
My friend had micro inverters at his house with panels. Problem: they produce a lot of RF interference, being a Amateur Radio operator, the interference disappears with no sun, he got rid of them and went with a single MPPT charger. He can now communicate during the daytime. Some manufactures are not following RF radiation compliance rules.
I cannot use MPPTs in this location as it is too far away from the battery. AC-coupled solar is the only solution. I don't know anything about RF interference. Should the manufacturer take care of such a problem?
Hi Andy, doesn't the Shelly have the Outbound Websocket support? In that case you don't need anything, just point it to Venus OS and it will popup as a meter you can configure for PV Inverter. No MQTT , no root, and no other difficulties required
I have no idea how this would work.
Quick Google search, it seems to be the Gen2 of the Shelly switch which has that. But still needs some sort of script in Venus OS?
Happy to test a simpler solution if there is one.
One question.I appreciate much this video but I have a question. I have a installation of 4,4KW or 6KW with a Multiplus II solar inverter. I am not interested now (probably in medium term) in integrating a shelly switch to get more data. So, without applying what you recomend is it possible to get data from that inverter to home assistant? Just to get data, even if they are not the right ones.
Note: the ip of the inverter pannel is a fixed ip.
I don't see a link to Martin's github web site.
Just added it. Of course I forgot...
github.com/vikt0rm/dbus-shelly-1pm-pvinverter
Greetings from Austria ;)
hi Andy, have you solved that negative reading bug with Martin? Thank you
Grüße nach Australien aus Germany ;D eine Frage habe an meiner Batterie einen PV inverter (Lumentree600) den ich auch wie Du per Shelly im VRM nur anzeigen lassen will ohne dass er als weiterer PV Ertrag mit eingerechnet wird. Kann man das deaktivieren? Habe 3 Victron Laderegler die ja im VRM dokumentiert werden und den Inverter will ich da ja nicht mit drin haben. *grübel* kann man den separat dokumentieren lassen?
I have tried the same with my grid connected Fronius inverter from the house solar. It shows in Victron but will be added to the Total Solar even it is a standalone system and not feeding into the battery. I just wanted it to show the actual power production, same like you.
The only 'solution' I found is setting the AC-Input to Generator (Settings - System Setup). Then, it shows the inverter in VRM without adding it to the Total Solar. BUT, it also shows this power then as a Generator power in the statistic.
So, no, this is not possible, at least not with this script.
@@OffGridGarageAustralia ok so the generator is displayed and the PV inverter at the same time? You can not set that the generator is only displayed? I wouldn't care about the name if you knew it was my Lumentree. I have a 1PM Plus here, but I'm afraid of destroying my statistics for the last few months, I think I'd better leave it alone ;D Thanks again and many sunny spring days.
Hi quick question can the multiplus be used as a gridtie inverter with a ct clamp
Yes, absolutely.
Don’t forget to make the Shelly IP address fixed in your network. Otherwise it’s IP address can/will change when the network restarts.
Yes, it has a static IP like most of my gear.
Andy how is it that your shelly pv shows up in the remote console and vrm? on my pi4b it doesn't (os 3.21/guimods)
Just to add that the shelly plus 1pm works with grid tied PV inverters too. I simply had to reverse the Live and output "O" wires, with the switch always "ON". The Shelly then operates in reverse, but still provides a positive (solar generation) reading.
And it does not show a negative AC-in or negative Generator figure any more?
With the Shelly still linked to the Shelly Cloud only , it shows positive (up to 3.5KW) when generating and positive (
@@OffGridGarageAustralia Thanks for the reply.
Just to confirm that I have connected the Shelly Plus 1PM to the Shelly Cloud only so far. It indicates positive power when generating - in my case up to 3.5 KW - and positive power when idle,
I've followed the "Martin" integration process and it works perfectly! PV generation readings show up as positive.
@@georgebajan5691I have tested the script on my Cerbo and downgraded and upgraded the system again and both ways the integrations seems to keep working. I think there was some info on the github page which explained the mechanic they implemented in their script to ensure that.
That does not mean it wont break with a future update though.
And thanks for the kind words and feedback in your last comment.
Can you tell me what version of Shelley firmware you are using ? version 1.0.8 does not work.
hello, for me this somehow didn't work, I did all the steps, and all seemed to be working fine, just that the files are not seen in the Cerbo directories, neither the shelly connects in the VMR. Any hints what could be the issue??
Victron have energy would you consider using one or not?
Dose Andy have an
eg4 powerpro 280ah heated battery to show us?
Nope, neither EG4 nor a battery with a heater 🤷♂️
HELP. Please. My cheap epever charge controler burned out . I'm looking for a victron replacement 100 / 50. Would be perfect . Looking for a used one . I can't afford new
does this require the shelly to have a static ip-address? in most cases, the ip-address is given by the dhcp server (or in most cases your internet router) - so the ip of the shelly might change after the next reboot ...
If the router restarts, it may hand out a different IP address to the Shelly and the script would stop working. So, yes, highly recommended to setup a static IP for the Shelly or do a IP address reservation in your router.
@@OffGridGarageAustralia so there is still room for improvememt ...
@@herwigg3327 I think the static IP is a must for such devices or something may stop working at some stage and it's hard to troubleshoot. I personally keep a list of all devices and MAC addresses on my network and if the IP is either static, router reserved or dynamic. It helps a lot to identify and resolve issues quickly.
I needed to change the position of the integration. It is in the file dbus-shelly-1pm-pvinverter.py in line 52. A zero means it is on the AC Input side and position 1 is for connected to output 1 of the multi. I think this will fix the problem with the AC Input Box.
Well, the position is correct though. Mine is at the output of the Multiplus.
Hey Andy,
I have a Shelly 3EM which means I have 3 phases. When configuring the .ini file, should I add a second and 3rd line to read L2 and L3???
You have to try and see if it works. I could not alter the ini file without losing all the data being transmitted. So, mine shows L1, L2 and L3 even I'm using only L1.
@@OffGridGarageAustralia aaaaahhhhhh okay... thanks for that prompt response... So without further "to do" I'll try this out...
There is a different solution for the 3EM. Follow this project here:
github.com/fabian-lauer/dbus-shelly-3em-smartmeter
Hi!
It is ok but much easy and natural with ET112!
Keep going!
Hi Andy. Any ideea why i'm not getting that icon in the vrm portal ? Also no icon in the remote console. I can see just the consuption graphic. Thanks. Have a great day. Maybe because i'm using a non victron inverter ?
I'm using a none Victron inverter as well. The script works with the Shelly not the inverter so should just work.
1. Do you see the Shelly in the Device List in VRM?
2. what Venus OS version and device are you using?
3. rebooted the device after installing the script?
4. have you used the exact same script I have shown in the video?
1. Yes 2. I'm using 3.10 venus os on raspi 2. 3. Yes 4. Yes. I am able to see al the information in remote console in device list but no icon. If you agree i can sent some print screens via email to you. Just for an opinion. I don't want to bother you.
@@dabo5068Sure send them. You're almost there. Maybe we can trouble shoot it this way.
While Naming it Pool-Solar, I just thought: Why not building a new roof for the Pool out of solar pannels? 😎
Yeah, why not just building a new roof over the pool. How????????????
This is indeed nice feature..too bad you can't use it for DC only..that would be awesome..
The Shelly 1 can be used for 48V applications up to 16A.
@@OffGridGarageAustralia Nice but for DC 48V system i would need up to 100A current.. If there was that option then for sure that would be perfect for most systems that don't come with option to connect to Victron systems.
@@SylwerDragon Yeah, that's a Victron Smart Shunt as the cheapest option then in this case.
@@OffGridGarageAustralia now Andy question is ..Can it be set as Power Generator instead of only smart shunt ? Will it show as lets say new extra unit ..and if you will put two shunts will it say Power Generator 1 and 2 for example ? That might be worth to test it.
Shelly introduced a 4PM after release of this package. Anyone got it to work?
😎
Hello Andy, I have microinverter sd3 appysistem, whit a et 112 meter I see production in gx.
Yes, I have the ET 112 as well but the installation location of the micro inverter is too far away from the garage where my Victron is. I know they have a Zigbee adapter...
does some one knows if for Shelly pro 3em is the same?
Moin,
For some reason I installed the wrong code. It was for the Shelly 1. But I have the Shelly 1 Plus installed. Now I have 2 programs running and it does not work. So my question is...
How can I remove it all so I can start over with the right one?
Anyone?
Thankx
Problem Solved
💙👊😎
I thought this is monitoring the tilt system? Why name it pool solar?
The inverter is at the pool and powering the AC pool pump system from what I understand.
Yes, correct. It is the tilt system. I should rename it. As we also have the Pool Fence Solar and it gets too confusing.
Like# 120
I just have solar man to see what my battery is doing you know what I mean
Need a wind turbine 😂
Dooooh!
🐸🐸🐸
Since it is a single phase script I would not dbus init the phases not in use. Then they won't show up as L2 and L3 with 0 value. It takes unnecessary space in the console.
How do I fix it?
Could you help me with my battery parameters please?
Sure, what's up?
@@OffGridGarageAustraliathank you, i cant set parameters right, where can i sent you my screenshoot of my parameters?
@@OffGridGarageAustraliai have 51,2v battery what ovp alarm, ovp protect, ovp release, full charge voltage and ovp cell release should i set?
@@sasoozvatic is that 16s battery Lifepo4 or Li-ion?
@@OffGridGarageAustralia16 cells lifepo4