Guide to completing the prospective short circuit current and prospective earth fault current test

Поділитися
Вставка
  • Опубліковано 26 гру 2024

КОМЕНТАРІ • 8

  • @ช่างไฟไทยแลนด์1985

    Which system is the electrical system grounded in?

  • @BULLEAD
    @BULLEAD 11 місяців тому +1

    Why did you use 2 Lo and not 2 hi, was this because you have an upstream RCD?

  • @ElectricalStudentsUK
    @ElectricalStudentsUK  11 місяців тому +1

    In short, yes. It is a test board, so there is actually fed from a board and RCD. I think the 2 cable, low test is a patent of Megger. Which prevents boards from tripping.

  • @IAmDefauLTz
    @IAmDefauLTz 7 місяців тому

    Where did you input the earth lead in the back of the tester for the test? also do you double this value if its 3 phase?

    • @ElectricalStudentsUK
      @ElectricalStudentsUK  7 місяців тому

      The Green earth lead goes in the green L2 port on the back of a Megger Multifunction tester. Other testers will he different. You do not double the value for 3 phase. The earth fault current will only travel down one of the phase cables in 3 phase, to activate the protective device. Therefore even in 3 phase, the calculated Ipf will always be 230/Zs

  • @mikethemask1525
    @mikethemask1525 5 місяців тому +1

    So im not sure why your testing pfc on the L-L L-N on the tester it should be L-PE for L to E pfc then for PSC should be L-L L-N setting both tests are 2 hi......

    • @kbagheri9026
      @kbagheri9026 Місяць тому +1

      Is exactly what I would say...

  • @kbagheri9026
    @kbagheri9026 Місяць тому

    You should change to L/N for pscc, and disconnect Rcds?