hello, I installed a sun-8K-SG01LP1-US/EU hybrid Deye inverter, on which I mounted a 10kw battery with bms jk, during the day when I disconnect the electrical network it is ok, but at night when the panels no longer I produce and disconnect the network, the battery enters the load after 3 minutes, can it be set to enter the load immediately??? (I mention that in the manual it is written that it can also work with agm, gel battery, i.e. not with a dedicated battery) the inverter detects the battery but on application is not visible, what settings can be made or can be made ???? anticipated thanks for the answer.
Je naweza kuto kutiki Grid charge ili kuondoa gharama ya umeme wa Grid kuchaji battery zangu?. Ninachotaka nikuona panakuwa na Grid passthroug to the load.
hi thanks for the detailed video , just got Deye hybrid, its an amazing inverter. I have 200 amp c20 batteries can i do time schedule with these batteries in the system work mode?
Amazing video! One question: I have a small battery bank. Is there a way of setting it up to use just as a no-break? Not draining from battery unless PV is insufficient and grid is out? I assume it would be Zero export to Load, Load First, grid charge. Am I right? Thanks for the work
nice! 1. is there anyway to completely disable charging of batteries from grid? 2. can we set the amount of voltage or amps if we need to charge batteries from grid?
1, yes, please don't tick "grid charge" on the battery setting, then the grid won't charge the battery. 2, yes, can . you need to choose battery V or battery % mode, then you can change the battery charge voltage. for the current, you just need to setup the grid charge current on the battery setting.
Hello. Certainly! I am experiencing a problem with my Deye 50 kW inverter. When the inverter is taking all its load from solar power and my batteries are at 100% charge, the grid consumption is displayed as 0.014 kW. However, when I measure the current on the grid cable with an ammeter, it shows a consumption of 14 amps on each line. Despite this, the inverter's screen indicates no power consumption from the grid. Can you please help me resolve this issue?⸻Let me know if you need any further adjustments or additional details included!
hello, I installed a sun-8K-SG01LP1-US/EU hybrid Deye inverter, on which I mounted a 10kw battery with bms jk, during the day when I disconnect the electrical network it is ok, but at night when the panels no longer I produce and disconnect the network, the battery enters the load after 3 minutes, can it be set to enter the load immediately??? (I mention that in the manual it is written that it can also work with agm, gel battery, i.e. not with a dedicated battery) the inverter detects the battery but on application is not visible, what settings can be made or can be made ???? anticipated thanks for the answer.
Je naweza kuto kutiki Grid charge ili kuondoa gharama ya umeme wa Grid kuchaji battery zangu?.
Ninachotaka nikuona panakuwa na Grid passthroug to the load.
hi thanks for the detailed video , just got Deye hybrid, its an amazing inverter. I have 200 amp c20 batteries can i do time schedule with these batteries in the system work mode?
HI yes can
Amazing video! One question: I have a small battery bank. Is there a way of setting it up to use just as a no-break? Not draining from battery unless PV is insufficient and grid is out? I assume it would be Zero export to Load, Load First, grid charge. Am I right? Thanks for the work
if using very small size battery, it may damage the battery.
nice!
1. is there anyway to completely disable charging of batteries from grid?
2. can we set the amount of voltage or amps if we need to charge batteries from grid?
1, yes, please don't tick "grid charge" on the battery setting, then the grid won't charge the battery.
2, yes, can . you need to choose battery V or battery % mode, then you can change the battery charge voltage. for the current, you just need to setup the grid charge current on the battery setting.
Is their any option to prevent power going to Grid if Net metering is not option on our country.
Good question sir.
don't tick “solar sell and selling first” then PV energy won't flow to the grid
@@kylezhang8343 What is the different between Zero export to load and zero export to CT ?
What does CT stand for?
Current transformer
What happen if the grid failed during daytime?
the battery and PV will power the load when grid failed
what is the setting for CT Ration
the default setting is 2000:1
Hello.
Certainly! I am experiencing a problem with my Deye 50 kW inverter. When the inverter is taking all its load from solar power and my batteries are at 100% charge, the grid consumption is displayed as 0.014 kW. However, when I measure the current on the grid cable with an ammeter, it shows a consumption of 14 amps on each line. Despite this, the inverter's screen indicates no power consumption from the grid. Can you please help me resolve this issue?⸻Let me know if you need any further adjustments or additional details included!
it could be FW issue, please contact the deye service to udpatet the FW.
hello, is there any way of locking my screen using a password? so that no one can change my settings ?
there's password to lock the parameters setting. four 9
Just a lot of music and no explanations. Can you not speak?👎