I know it’s no longer done in kitchens because of GFI protection, could you have run a 12/3 and done a shared neutral circuit? save wire box fill and time.
Yes, many times a 12-3 is pulled here for a disposal and dishwasher sharing the neutral. You have to make sure each breaker is on opposite phases otherwise you could overload the neutral. Yes, definitely can’t be a GFI .
I know it’s no longer done in kitchens because of GFI protection, could you have run a 12/3 and done a shared neutral circuit? save wire box fill and time.
Yes, many times a 12-3 is pulled here for a disposal and dishwasher sharing the neutral. You have to make sure each breaker is on opposite phases otherwise you could overload the neutral.
Yes, definitely can’t be a GFI .