DIST.TRANSFORMER MEGGER/INSULATION RESISTANCE TEST PROCEDURE OF A DISTRIBUTION TRANSFORMER

Поділитися
Вставка
  • Опубліковано 24 лис 2024

КОМЕНТАРІ • 7

  • @sachinkunkalienkar8088
    @sachinkunkalienkar8088 5 місяців тому

    It is not clear what should be the test voltage while testing IR value between hv to Lv.
    Is it as per LV voltage or as per hv voltage.
    Is there any significance for line terminal & power terminal while carrying out the test.
    What I mean is where to connect line terminal & earth terminal of megger

    • @electricalpassionate
      @electricalpassionate  5 місяців тому

      You are welcome. As the tests are performed on 11/0.4KV Transformer,so LV side rated voltage is 400 Volt. We must use 500 Volt Megger or test voltage while testing IR between LV and Earth/body as well as testing IR between HV and LV. Test Voltage should be

  • @hymavathi9948
    @hymavathi9948 7 місяців тому

    How much voltage to be applied while doing IR LV to Body?

    • @electricalpassionate
      @electricalpassionate  7 місяців тому

      You are welcome. Requested to re-watch the video.As such during testing IR between LV to Body 500 Volt to be applied either by using Digital Megger or by using 500 volt. hand-driven Megger ( like Waco make). Thank you.

  • @dodiyasanjay7777
    @dodiyasanjay7777 7 місяців тому

    33KV cable end termination video

    • @electricalpassionate
      @electricalpassionate  7 місяців тому

      Power cable end termination video is not available right now. It is not possible to make animated video on it by me. So my dear, I will try to collect the same. Thank you❤.

    • @dodiyasanjay7777
      @dodiyasanjay7777 7 місяців тому

      @@electricalpassionate ok sir,33Kv cable Construction video