  • @georgebrabec1749
    @georgebrabec1749 3 роки тому +3

    Well most of the time, depending on the degree of ground/burn it will take out the other compressor. It the same thing as replacing a single compressor without cleaning up the system. You may get lucky, at least I hope so !

    • @hvacworld7421
      @hvacworld7421  3 роки тому

      Totally agree. It's always recommended that you replace a trio or tandem when one compressor is a burnout. However most customers will not want to pay for that. Luckily I did an acid test and it came out negative, however you never know if there was a mechanical failure and shavings such as from the bearings got in the oil.

  • @georgebrabec1749
    @georgebrabec1749 3 роки тому +1

    Great troubleshooting, but did you leave that circuit active or off on the options program ?

    • @hvacworld7421
      @hvacworld7421  3 роки тому

      Thanks. Left it active. The building needed that additional circuit active. Chiller was calling for compressor 1 and 3 to engage. However only compressor 3 was running.