TIA Portal: PUT Command / PLC-PLC Communication

Поділитися
Вставка
  • Опубліковано 5 жов 2019
  • One way of PLC-PLC Communication.
    PUT memory areas to a partnered PLC
    If this video helped you, please consider helping me by joining my "GoFundMe" and donating a small amount to my cause. Link here:
    www.gofundme.com/f/let039s-fi...
  • Наука та технологія

КОМЕНТАРІ • 95

  • @sashkindg
    @sashkindg 4 роки тому +1

    Hello! With PUT, Data Blocks can be optimized ?

    • @hegamurl7434
      @hegamurl7434  4 роки тому +7

      Generally said: Yes!
      But the topic is a bit more complicated... when using "optimized block access" you can not used on an "address based" way anymore, so you have to use the symbolic names or drag and drop (like I did in the video with the data that the first PLC sends). You can PUT a whole DB, simply by dragging it and dropping it at the "SD_1" input.
      ...but as said... the topic of optimized block access is quite complex, maybe I'll make a video on it in the future.

    • @sashkindg
      @sashkindg 4 роки тому +2

      @@hegamurl7434 I think the topic of optimized block access will be very useful.

    • @MAli-zh6cr
      @MAli-zh6cr 4 роки тому

      @@hegamurl7434 In case of whole db with different data types needs to be sent, should I make another db on the other side (plc) with same data types/lengths as well?

    • @bacem_ch
      @bacem_ch 3 роки тому

      @@MAli-zh6cr yes

  • @austins.275
    @austins.275 Рік тому +2

    Man I ran out of inputs on a big project and thought "PLC to PLC communication should be easy" 72 hours of pulling my hair and you saved me. Had EVERYTHING right but couldn't get the REQ parameter to work and your video explained it perfects. Thank you!

  • @NikitaBelousovIE
    @NikitaBelousovIE 11 місяців тому

    Thank you very much for so easy explanation of the complicated things!

  • @shushimhuntinwabbits
    @shushimhuntinwabbits Рік тому

    Once again, a logical clear explanation for anything Siemens based... Thanks so much 🙂

  • @zedjag7701
    @zedjag7701 3 роки тому

    Another great TIA Portal video, thanks a lot.

  • @framos9991
    @framos9991 Рік тому

    My favorite teacher /Thank you!

  • @76POK
    @76POK 2 роки тому

    Thanks again. I have got so much help from this site!

  • @pksharma9329
    @pksharma9329 4 роки тому

    Sir your video always helpful for me....greetings from INDIA as well

  • @hichemchawi4498
    @hichemchawi4498 4 роки тому

    thanks for your videos, those are very useful to learn about automation

  • @sagarparmar8904
    @sagarparmar8904 3 роки тому

    Sir , your videos are very helpful thanks 🙏

  • @crja4114
    @crja4114 Рік тому

    My good friend you have a new subscriber. Thanks.

  • @rhysdavies8947
    @rhysdavies8947 4 роки тому

    Awesome video. Thanks!

  • @braincrackz
    @braincrackz 4 роки тому +3

    hello there greetings from saudi arabia. god bless you

  • @armchairfreedomfighter
    @armchairfreedomfighter 4 роки тому

    Keep'em coming!!

  • @alexchiosso221
    @alexchiosso221 4 роки тому

    Thank you so much!!!

  • @simonmax3901
    @simonmax3901 4 роки тому

    That was so informative

  • @naifsahin
    @naifsahin 2 роки тому

    Very useful, thanks.

  • @IK-qu9hw
    @IK-qu9hw 4 роки тому

    Thank you sir.

  • @danielesauhs5083
    @danielesauhs5083 3 роки тому +1

    Hey man! I really like your videos, your explanations are excepcional, thanks for this knowlegment.
    Just a quick question, I have 2 PLC 1500, both have diferent subred, but one of them have two ethernet ports available, is it possible to link each other trought this free port?

  • @HectorRodriguez-si3yr
    @HectorRodriguez-si3yr 3 роки тому

    i love u man, thanks a lot.

  • @GeneralKiller1337
    @GeneralKiller1337 3 роки тому

    Nice job, Hega! I have one question: can I use this protocol with SINAMICS devices or the S7 protocol is only for the comunication between 2 S7 PLCs?

  • @mobros1298
    @mobros1298 Рік тому

    so clear thank you

  • @kadadjamel4545
    @kadadjamel4545 Рік тому

    MERCI beaucoup

  • @mirrorcopy4681
    @mirrorcopy4681 9 місяців тому

    மிகவும் நன்றி நண்பா

  • @Raul-jl1nd
    @Raul-jl1nd Рік тому

    thanks, grate job

  • @vishalpatil6740
    @vishalpatil6740 4 роки тому

    Thanks bro.... 👍

  • @beautyofislam323
    @beautyofislam323 4 роки тому

    Thanks sir

  • @petervranks2723
    @petervranks2723 2 місяці тому

    Hello , video is well explained as ever, but still a question : do'n I need to define the S7-connections in the network view are they generated automatically ? What is the SIMATI-ACC option ? Best allways on for easy configuration with unspecified partner ( in my case S7_1500 GET from S7-1200 ?

  • @santoshkumarpatro2772
    @santoshkumarpatro2772 4 роки тому +1

    Thanks for this video..its helped me

  • @kathirangamuthu3574
    @kathirangamuthu3574 3 роки тому

    Thanks

  • @hansbrannstrom620
    @hansbrannstrom620 2 роки тому

    Hi Thanks a lot for all nice videos you share with us :-)
    Is it even possible to test this PUT & GET function with PLC SIM? I does not get it to work....

  • @Gumballation
    @Gumballation 7 місяців тому

    Hi sir! Your tutorial is amazing ❤. I have a question: is it possible to take text input from a human-machine interface and then process it using if/else statements like in programming? For example, the user types "password" and if the password is wrong, you know, like an if/else statement in programming.

  • @ouluberlu7373
    @ouluberlu7373 Рік тому

    Hi, I'have got a 1214CPU and using TIA V15. Unfortunatley, S7-communication library is missing. Do you know if I can import it in TIA? If yes, where can I get this library?
    Or is it a default library?
    Thanks for your videos !

  • @khaledtebai3920
    @khaledtebai3920 4 роки тому +1

    This video came just in time! thank you so much!
    I have a school project, in wich I have to communicate three S7-1200. for now, connecting two PLC's is quit clear, with three , do I just need to add PUT and GET functions in the three of the PLC's if i want to send and read data from all three of them?

    • @hegamurl7434
      @hegamurl7434  4 роки тому

      Yes exactly! Junse repeat for the third PLC

    • @genantamtam9364
      @genantamtam9364 3 роки тому +1

      @@hegamurl7434 so putGet is only for siemens s7 communication? What if i want ro connect to other systems with my siemens plc? You have a video on that?

  • @ansonkiek6471
    @ansonkiek6471 4 роки тому

    If we set unspecified is this must delete the s7 connection ?
    My partner plc is s400 , I tried use this function communicate but always failed.

  • @alvaropalenciano6147
    @alvaropalenciano6147 3 роки тому +1

    Master!

    • @hegamurl7434
      @hegamurl7434  3 роки тому

      Give yourself some years and experience and you will be the master!

  • @seanyushi9096
    @seanyushi9096 2 роки тому

    The connection id is actually not taken care by TIA. I've tried to have more than 1 PUT instructions and all of the block will always have the identical configuration following the latest changes i made, e.g. ip address of partner, memory address, etc. And this might be my issue, i need to change the connection name.

  • @akshayjadhav6145
    @akshayjadhav6145 3 роки тому

    Hello, thanks for such great videos.
    Could you have a video on Ethernet diagnostics to find communication error in your network and display on HMI.
    That would be very helpful
    And thank once again

  • @NotMarkKnopfler
    @NotMarkKnopfler 3 роки тому

    Is this command also available over Profibus (rather than Profinet)? Thanks :-)

  • @stuatkins5
    @stuatkins5 2 роки тому

    hi great video , if i wanted to send a qr code value (say PAC123) from one plc to another is a put instruction the best way?

  • @dee-hl2tp
    @dee-hl2tp 3 роки тому

    Hi, another great video thank you. Just one question, In the PU_DB ADDR_1 parameter, (P#M0.0 INT 1) is M0.0 not just 1 BIT? If so how can you store an INT value in it?

  • @legendary686
    @legendary686 3 роки тому

    Thanks for the video. I have a question. Can you do this with PLCs from different brands? i.e Sending data from my siemens PLC to an omron in a different project for example?

    • @RemixProf
      @RemixProf 2 роки тому

      NOPE. Siemens S7 only.

  • @vijayakanthm705
    @vijayakanthm705 4 роки тому +1

    Thanks to your good work.I have a question That i didn’t have a physical plc ,so shall configure two plc’s in a single project and test them with each other by single PLCSIM.Don’t bother if it is a genuine question

    • @tuleanhvt
      @tuleanhvt 3 роки тому

      you can simulate two PLC by PLC SIM

  • @Der_Geraet1
    @Der_Geraet1 3 роки тому

    Kann man damit auch bspw. M0.0 der einen sps setzt M0.0 der zweiten sps? Sprich kann man einfach nur merker 1 und 0 setzten damit?

  • @santiagomoore374
    @santiagomoore374 3 роки тому

    Sir, I have confusion over profibus, profinet, ethernet?? Please make a video on this topic.
    At 0:32 we found two ip address
    1) is 192.168.1.1
    2) 192.168.0.101
    What is those two ip?? Please explain or suggest any video

  • @deshabandhunayak320
    @deshabandhunayak320 4 роки тому

    What is the maximum size of data we can send in PUT command?

  • @Reaper0931
    @Reaper0931 5 місяців тому

    Hey, How can I send more information ? Im a beginner and you say in the end of the video that it is possible, how ?

  • @ikkusoft
    @ikkusoft 3 роки тому

    Can this be simulated in PLC SIM,
    I tried, I'm not getting value in other PLC.

  • @user-ch1ep4hi7q
    @user-ch1ep4hi7q Рік тому

    I need to get encoder value from another cpu can I use the GET bock
    and how???

  • @jamesedrielleaurellana
    @jamesedrielleaurellana 8 місяців тому

    😍😍😍

  • @kreditslavkov8115
    @kreditslavkov8115 2 роки тому

    Hello, pleace can i have a guestion.... i used a condition as you did at the end of the video for the REQ input. i also put a negativ contact "PUT_DB".DONE instead of freguency. but when i did it for the first time nothing has came into the my next plc. when i deleted it and did it again and upload the plc program again, it works. But when i was working on that again today also same problem and i have to do the same solution. deleted that condition and do it again the same. unfortunetly i cannot used the frueqvency condition, do you know why this negativ contact "PUT_DB".DONE doesnt work for the first time(the datablock put_db is green, but nothing has came into the database on the next plc...)? and is there any solution idea for condition like do it with every cycle of the cpu?

  • @mohdshahzad9427
    @mohdshahzad9427 Рік тому

    How to convert 1 Word into bits via siemens S7 1200 PLC?

  • @zhengkunyan8001
    @zhengkunyan8001 4 роки тому

    Good

  • @whatacode
    @whatacode 2 роки тому

    How Can we send use put for more than 5 plc and send data to one Common plc.....
    Please respond sir

  • @melvingomez426
    @melvingomez426 3 роки тому +1

    How do you send multiple data..🙏🏽

  • @EshmesVid
    @EshmesVid 4 місяці тому

    Uhh it also works on Logo not only S7

  • @mat77111
    @mat77111 Рік тому

    I take it this method doesn’t work with S7-1200 PLCs?

  • @dennisrubio2375
    @dennisrubio2375 Рік тому

    why does not PLC 102 isnt on profinet red plz help sr

  • @vinothparker7425
    @vinothparker7425 4 роки тому +1

    Kindly make a video on various communication protocols and what is the difference between each of them sir..

    • @hegamurl7434
      @hegamurl7434  4 роки тому +1

      Will do at some point!

    • @genantamtam9364
      @genantamtam9364 3 роки тому

      @@hegamurl7434 hi there.
      You mentioned 14:46 that put/get is not your recommended type of communication but you mentioned "ip protocol"? Which one is that? Isit i-device/control? IO communication by pnpn coupler? Is that the most common?

  • @ericanderson560
    @ericanderson560 Рік тому

    DO you have to set up a TCON to do a put? If not what's the purpose of setting up the TCON in the prior video?

    • @hegamurl7434
      @hegamurl7434  Рік тому

      No you dont have to, they are different merhods of communication. The videos are unrelated

  • @umairshah9735
    @umairshah9735 3 роки тому

    Hi dear , Watching your vids . Best one can offer for the betterment of human beings . Thanks alot . Dear i want to send my Level signal from one PLC to other . I am no expert . Kindly, advice me videos in your playlist which can help me . Thanks

  • @ericanderson560
    @ericanderson560 Рік тому

    Do you have to be online for this to work? I can't get it to work at all. It tells me the data type is wrong when it is clearly correct, or it tells me the specified value is invalid

    • @ericanderson560
      @ericanderson560 Рік тому

      It says "The data type DInt of the actual parameter does not match the data type Remote of the formal parameter". In this case I dropped it in directly from the tag table of the receiving PLC, which is in my project. They are both Dints

  • @GeorgeMan_1981
    @GeorgeMan_1981 4 роки тому +1

    Just subscribe ..

  • @MrPushpalm
    @MrPushpalm 2 роки тому

    Will s71200 communicate with s71500

  • @mubarishussain3696
    @mubarishussain3696 4 роки тому

    So you only put instruction to communicate.What about get instruction on receiving PLC.Is not required?

    • @hegamurl7434
      @hegamurl7434  4 роки тому

      You only have the instruction on one PLC: If you want to read data from another PLC you use "GET" and if you want to push data into the other PLC you use "PUT". The other PLC does not need any function (although some prerequesites as described in the video)

  • @Olavotemrazaodenovo
    @Olavotemrazaodenovo 4 роки тому

    Where can I find the frame structure of a command between IHM and PLC by profinet? If I want to snif the protocol to discover how the adress of the word in PLC is coneccted with other adress word in IHM, how can I do it? Congratulations from Brazil. Thank you.

    • @hegamurl7434
      @hegamurl7434  4 роки тому +1

      Don't know what exactly you are looking for... but for analyzing network packages I recommend a free tool called "Wireshark" with which you can analyze network packages

    • @ziborgbe
      @ziborgbe 4 роки тому +1

      search for s7 protocol

    • @Olavotemrazaodenovo
      @Olavotemrazaodenovo 4 роки тому

      @@hegamurl7434 I want to analyze it. Thank you for wireshark!

  • @mehmettevfikcete3397
    @mehmettevfikcete3397 4 роки тому

    Hegamurl hi,
    Is there a limit on this process. I mean, can i send for example 200 byte datas with 300 ms rate ?
    And could you share a lesson about putting or getting data from different brand plc's to siemens plc please.(not s7 connection)
    Thank u so much again. God sent you to us. :)

    • @mehmettevfikcete3397
      @mehmettevfikcete3397 4 роки тому

      Note: our network bandwith is very nice. There is no bottleneck on this topic.

    • @hegamurl7434
      @hegamurl7434  4 роки тому +1

      Very good question! I have never tested the maximum, but also have never reached it. I'll simply test it out (and also read the documentation) on it, when I have the time.
      As far as I know the PUT/GET here is only between SIMATIC components. For other devices I always recommend a TCP connection (my next videos will be about that)

    • @lassejespersen9880
      @lassejespersen9880 3 роки тому

      With the 1500 system you Can PUT 400 bytes and GET 400 bytes

  • @saeed2tube
    @saeed2tube 4 роки тому

    Hi
    I have question maybe irrelative.
    How we can mirror hmi to monitor without pc and use finger touch of monitor?
    And if you can please make video about data logging server.
    thankful

    • @hegamurl7434
      @hegamurl7434  4 роки тому +2

      Hi! I am not sure if I fully understand your question, but if you want to use your PC as HMI you will need WinCC Professional Runtime on your PC, which will simply run a program that emulates an HMI on your PC.
      Added Data Logging to my list!

    • @saeed2tube
      @saeed2tube 4 роки тому

      Thank for your answer. But i want connect monitor directly to hmi.

    • @GeorgeMan_1981
      @GeorgeMan_1981 4 роки тому

      Use sm@rt client ..

  • @mrloh7197
    @mrloh7197 Рік тому

    Is it possible to use Put and Get instruction with the CPUs with different TIA Portal Version? One using V15.1 and another using V16.0.

  • @BG-gr1uu
    @BG-gr1uu Рік тому

    Please improve voice quality,

  • @Automation28
    @Automation28 2 роки тому +1

    thanks for your videos, those are very useful to learn about automation