thank you idol sa mga videos mo. hope magdagdag ka pa ng maraming troubleshooting video para may idea kami kung sakaling dumating na need namin ito. thank you sir and ingats palagi
Hello there. Respect for what you doing over there and also taking time to explain as much and as detailed as possible. I`m working also as an ETO onboard Cotainer Vessels. Can we do a detailed video about Boiler, functions, alarms testing, troubleshootings if have any or advices for good maintanance. All the best !
Thank you sir for yr video. some emergency switchboard arrangments have a key which can be put to test or simulation mode. does it cause the main switchboard bus tie to open.therby causing the emergency generator to start.like u did in the video .thanks in advance.
I want to ask how supply signal is given to emergency generator when main generator trip or black out . As normally we have beaker for emergency generator in ECR if main generator running .
no voltage relay senses the voltage and sends signal to start the emg gen in event of blackout..In this video he opened the tie breaker and start sequence initiated.
I can only imagine that there must be interlocks ensuring that both bus ties cannot ever be closed at the same time. Otherwise it seems entirely too easy to do!
In my last ship, the emergency generator was not coming on load, the bustie isolation breaker was burned out, it was 2004 built ship, the technician came in dubai and replaced breaker but it took 50secs to automatically come on load, as per solas it should be 45secs maximum, is it related to wrong setting of timer,?
Sir gud day ask lng for ds video, after restore ng power to MSB, need din ba ntin ibalik sa AUTO, kc nkita q d2 sa video mo after load test, din bfore u start restore nag MANUAL ka mna din bgo mo enopen ung ESB din close ung MSB,din u til back to normal na, so di mna pnakita ung pagbalik ng AUTO?
Master ano problema sa generator na ayaw mg start bago Yung battery niya, gc 10 ang control niya para NG on and automatic, wala na ilaw ang light indicator sa gc 10, sira na Kaya ito master salamat sir
Sir elect may tanong ako tungkol sa emergency generator ,. Ang battery ng emergency generator ay automatic ba yan nagchacharge.. Kahit dmo pah iniinistart at nka stanby nagchcharge ba yan. Kasi ayw umistart dito sakto naman yung voltage. Bigla nalng ayaw umistart, tenistesting ko to weekly. Ngayun pag pinipress ko yung start button may lagutok lng sia doon sa solenoid na 24volt, may tutunog lng. Hnd sia tutuloy magstart.. Sna may free tym ka sir elect at mkarespond. Thanks and more power to ur channel.
Ang pag check ng battery is dapat pinapatay mo ang charger pala malaman ang mismong voltage ng battery. Kapag di mo pinapatay ang charger ang nasusukat mo is yung voltage ng charger mismo. Regarding sa condition ng battery mo, ang life span ng batteries nag last lang ng 2 years. Kailangan every 2 years pinapalitan ang battery. Second, if hindi mag start ang Generator mo using battery, try mo start sa hydraulic system, kapag nag start sa hydraulic then malamang sa malamang need mo na palitan ang baterya mo.
@@leckyjake salamat sa tips sir lecky, may point ka na dapat i off muna ang charger kung mag reading ng voltage.NOTED. So automatic pla talaga, Akala ko kasi nung ona hindi sia atumatic magcharge, akala ko tuwing mag start lng sia mgacharge. Godbless!
Testing of emergency gen kung papasok ng auto in case of black out. The idea is tinaggal lang ang ESB sa MSB by opening the ACB. Hindi siya yung full black out na patay lahat.
rodel durban pag onload mo unang mag open ka ng MSB bus tie at auto mag close ang emcy acb. Pag put back naman need mo open ang acb the manual din close mo bus tie ng msb
Ask lng po ako mga sir kng anong mga latest requirements para maging certified ETO this year 2020. RECE po ako landbase and 10 years experienced as E&I Engineer sa Shipbuilding Industry in UAE. Gusto ko lng po magshift sa seabase na work as an ETO. Any informative reply will be much be appreciated.
Nice idol...now....I have have knowledge more about...keep blogging
thank you idol sa mga videos mo. hope magdagdag ka pa ng maraming troubleshooting video para may idea kami kung sakaling dumating na need namin ito. thank you sir and ingats palagi
Sir idol. Salamat sa pag share👍. More power and god blessed. 🙏
Hello there. Respect for what you doing over there and also taking time to explain as much and as detailed as possible. I`m working also as an ETO onboard Cotainer Vessels. Can we do a detailed video about Boiler, functions, alarms testing, troubleshootings if have any or advices for good maintanance.
All the best !
Hii brother
Thank you for sharing this leckyjake
This is a very informative video sir. Waiting for your next video😋. Thanks sir. Safe sailing
Thanks for sharing your knowledge sir, sharing kwowledge is like sharing your blessings.
Thank you for your support
Hey! Good video. Keep it up))
Hi sir pa shoutout naman jan sir galing mo
Good sharing👍👍👍
Good work sir🤘
GAURAV RAWAT thank you
Thank you for sharing sir new supporters here
Thank you sir. Very educational. New Subscriber here ♥️
Thanks for sharing, Sir 👍
Very informative video
Kudos Sir!
Mark Estreller thank you
Nice sir
Thanks for sharing sir
Good 👍
Very good sir please upload more videos
may i know what is the standard you are using when inspecting generators.. thanks for a beautiful video..
Very helpful talaga mga vlog mo idol rest in peace
Well done you the best
That's a good job. However, Starting Em Generator on manual & keeping ACB close while Bus-tie is closed seems doubtful. Kindly clarify
Sir can you make video regarding basic electrical line diagram tracing
Thanks you sir..
From Bangladesh 🇧🇩👌
Thank you sir for yr video.
some emergency switchboard arrangments have a key which can be put to test or simulation mode. does it cause the main switchboard bus tie to open.therby causing the emergency generator to start.like u did in the video .thanks in advance.
I want to ask how supply signal is given to emergency generator when main generator trip or black out . As normally we have beaker for emergency generator in ECR if main generator running .
no voltage relay senses the voltage and sends signal to start the emg gen in event of blackout..In this video he opened the tie breaker and start sequence initiated.
Thankyou so much❤️ make more videos 🙏❤️❤️❤️
Thanks sir idol kita
Thank you
I can only imagine that there must be interlocks ensuring that both bus ties cannot ever be closed at the same time. Otherwise it seems entirely too easy to do!
Secondly how supply is given from emergency switch to equipment that are run from ESB.
Tnx for this
Engine room tour vlog sirr
In my last ship, the emergency generator was not coming on load, the bustie isolation breaker was burned out, it was 2004 built ship, the technician came in dubai and replaced breaker but it took 50secs to automatically come on load, as per solas it should be 45secs maximum, is it related to wrong setting of timer,?
Yup, there is a timer after the no voltage sense
Sir gud day ask lng for ds video, after restore ng power to MSB, need din ba ntin ibalik sa AUTO, kc nkita q d2 sa video mo after load test, din bfore u start restore nag MANUAL ka mna din bgo mo enopen ung ESB din close ung MSB,din u til back to normal na, so di mna pnakita ung pagbalik ng AUTO?
After the load test do we have to switch the EG back to Auto..?
yes
Very nice 👍🏼 you man 👨🏻, love 💕 u
Happy morning
Its very important to share unifilaire diagram to understand well your work
Thanks
Do you think living on a ship is good or bad?
Thank you sir
Is Cruise line requires ETO officers ?
That is a very old cummins nt855.. that's 70s style governor
Thanks 🤗💐
Master ano problema sa generator na ayaw mg start bago Yung battery niya, gc 10 ang control niya para NG on and automatic, wala na ilaw ang light indicator sa gc 10, sira na Kaya ito master salamat sir
my question is, when you disconecy from the shore power what is the sequence?
Start one of the auxiliary engine generator and close the main circuit breaker to energize the main busbar
Emergency generator should come on load automatically within 45seconds after the failure of main power supply.
sir paki explain po
Sayang yong content sir we wish detail for your next video.keep safe
Sir elect may tanong ako tungkol sa emergency generator ,. Ang battery ng emergency generator ay automatic ba yan nagchacharge.. Kahit dmo pah iniinistart at nka stanby nagchcharge ba yan. Kasi ayw umistart dito sakto naman yung voltage. Bigla nalng ayaw umistart, tenistesting ko to weekly. Ngayun pag pinipress ko yung start button may lagutok lng sia doon sa solenoid na 24volt, may tutunog lng. Hnd sia tutuloy magstart.. Sna may free tym ka sir elect at mkarespond. Thanks and more power to ur channel.
Ang pag check ng battery is dapat pinapatay mo ang charger pala malaman ang mismong voltage ng battery. Kapag di mo pinapatay ang charger ang nasusukat mo is yung voltage ng charger mismo.
Regarding sa condition ng battery mo, ang life span ng batteries nag last lang ng 2 years. Kailangan every 2 years pinapalitan ang battery. Second, if hindi mag start ang Generator mo using battery, try mo start sa hydraulic system, kapag nag start sa hydraulic then malamang sa malamang need mo na palitan ang baterya mo.
@@leckyjake salamat sa tips sir lecky, may point ka na dapat i off muna ang charger kung mag reading ng voltage.NOTED.
So automatic pla talaga,
Akala ko kasi nung ona hindi sia atumatic magcharge, akala ko tuwing mag start lng sia mgacharge.
Godbless!
Sir good day tanong lang sir.
Anong test yan sir for emergency light lang or blackout?
Once off mo bus tie mag blackout sir?
Testing of emergency gen kung papasok ng auto in case of black out. The idea is tinaggal lang ang ESB sa MSB by opening the ACB. Hindi siya yung full black out na patay lahat.
@@leckyjake ok po sir. Maraming salamat po sa oag share. Bale parang blackout simulation test lang pala. Emgcy lights lang gagana.
Marc Aguihap hindi sir, emergency lights ang mawawala at lahat ng connected sa ESB
@@leckyjake baliktad pala. hehehe
Emgcy pala mawawala. Ok po sir. Maraming salamat sa pag share po sir. Godbless.
Sir kapag ngclose po yung emcy ACB automatic na po b mgopen yung MSB bus tie? Salamat
rodel durban pag onload mo unang mag open ka ng MSB bus tie at auto mag close ang emcy acb. Pag put back naman need mo open ang acb the manual din close mo bus tie ng msb
@@leckyjake ok sir pro pagminanual mu sir yung emcy d/g open parin muna msb bus tie before closing the ACB control knob? Thanks
rodel durban yes. Open mo muna bus tie ng msb tsaka mo close ang sa emcy.
@@leckyjake thank you very much sir..
Ask lng po ako mga sir kng anong mga latest requirements para maging certified ETO this year 2020. RECE po ako landbase and 10 years experienced as E&I Engineer sa Shipbuilding Industry in UAE. Gusto ko lng po magshift sa seabase na work as an ETO. Any informative reply will be much be appreciated.
I will visit marina pag uwi ko to verify the latest rules and regulations nila
Niz video
How can i contact you?
how to become an ETO sir?
blackout my genrator Emergency anyhere Night sir.
Việt Nam! ???
Gamecrook looks like the only working web app from which you can get free gems, coins, gold or whatever.
Thanks for sharing ur knowledge sir.. It ll benefit for me lot... Can i talk with you sir regarding wiring diagram? Please can i get your number?
Anyone else used Gamecrook. It worked for me.
Looks like L class Vessel😅
Tarun Jagatha this is an S class singapore. L class they have the knob switch that once flip everything will be automatic
@@leckyjake you really remember a lot! L class was my first vessel..this video made me reminisce! Nice video btw very informative one