BREAKER AND CABLE SIZES FOR ELECTRICAL CIRCUITS.

Поділитися
Вставка
  • Опубліковано 30 лис 2024

КОМЕНТАРІ •

  • @learnelectrics4402
    @learnelectrics4402  3 роки тому +8

    SEE ALL - To view a list of all our LearnElectrics videos, click on the link below.
    There are many videos on many electrical topics including Installation, Part P, 18th Edition, Testing, Certification, Lighting, Sockets, Ring Circuits and much more.
    ua-cam.com/channels/YaJQnpO4XAp0yCgqzMkmfA.html

    • @alejandrolian7101
      @alejandrolian7101 3 роки тому

      you probably dont give a damn but does anyone know a method to get back into an instagram account??
      I somehow forgot my login password. I appreciate any tips you can give me

    • @danteameer4536
      @danteameer4536 3 роки тому

      @Alejandro Lian Instablaster =)

    • @alejandrolian7101
      @alejandrolian7101 3 роки тому

      @Dante Ameer thanks so much for your reply. I found the site on google and I'm in the hacking process now.
      Takes a while so I will get back to you later with my results.

    • @alejandrolian7101
      @alejandrolian7101 3 роки тому

      @Dante Ameer It worked and I now got access to my account again. Im so happy!
      Thank you so much you saved my ass :D

    • @danteameer4536
      @danteameer4536 3 роки тому

      @Alejandro Lian glad I could help =)

  • @jeremykemp3782
    @jeremykemp3782 8 місяців тому +3

    9 times out of 10, yt influencers give out incorrect information. This guy does NOT.. Excellent stuff sir . Sub from me

  • @chrissmith7259
    @chrissmith7259 3 роки тому +30

    When you fully understand something it is easy to explain said Isacc Newton. Your explanation was simple and complete. Thanks

    • @learnelectrics4402
      @learnelectrics4402  3 роки тому +3

      Thank you Chris. We really appreciate this feedback.
      Dave

  • @souljimmy1
    @souljimmy1 2 роки тому +2

    Finally someone has explained the actual calculation of what we were trying to learn 👏

    • @learnelectrics4402
      @learnelectrics4402  2 роки тому

      Thanks for the great comment. Lots more videos to come, including more calculations. Dave.

    • @souljimmy1
      @souljimmy1 2 роки тому

      @@learnelectrics4402 hi dave 👋today is Christmas day "so I'll bid you merry Christmas 🎅 "and a big thanks for your teaching videos " I've been in the building trade for nearly 40 years now? As a bricklayer ☠👻spent most of my time on sites 'but went self employed in 2000 ' I've learnt a little bit about electrics 'wired up a few sockets now and again? And normally had to get electrician to check it over ' 🤪but recently I came across your videos " and got interested in expanding my knowledge of electrics 'I've watched other videos of similar advice "but found yours the one that struck me the most ' its not elaborate or highly glifick "but some how it works for me?? Think it comes down to how someone can get a difficult scenario across ! I find your instruction easy to understand 😃I'm going to follow you deeper into this "and get more equated with this "wish you could of taught me years ago "🙈all the best my friend "have a good New-year 👍

  • @markandrews8437
    @markandrews8437 3 роки тому +13

    I can't begin to tell you how grateful I am for these videos although I retrained 7 years ago as a older student know 53 they give me a much better understanding I am now confident enough to help some of the younger apprentices with issues or just show them your videos keep them coming matey 👍

    • @learnelectrics4402
      @learnelectrics4402  3 роки тому

      Thanks Mark, brilliant feedback, makes our day. 53? Still got loads of life in you yet and yes, it is good to pass on knowledge to the younger electricians. Thanks again. Dave

    • @angelofranklin1
      @angelofranklin1 3 роки тому +1

      Mark, Your just a young man, Im 66 and still going strong so dont worry about age mate.

    • @markandrews8437
      @markandrews8437 3 роки тому +1

      @@angelofranklin1 66 that's excellent I just noticed I put 53 don't know why because I'm 55 🤣 tell me I'm going be OK 🤣

  • @mohammadtahir5357
    @mohammadtahir5357 2 роки тому

    If i am not wrong, there is not even a channel like yours...
    It is helping me...
    Thank you for everything and may ALLAH(GOD) bless you...
    From Mozambique

    • @learnelectrics4402
      @learnelectrics4402  2 роки тому

      Thanks Mohammed. Thanks for watching and I'm so glad the channel is helping. I have some very fond memories of my time in Africa. Beautiful country, amazing skies. Dave.

  • @jamesbradley582
    @jamesbradley582 4 роки тому +2

    Thankyou described it in a easy to understand, in the past I have looked at books on electrics,and they made it sound so complicated, but with your explanation I got it straight away,once again thanks

  • @johnh6298
    @johnh6298 3 роки тому +10

    You have saved the day once again mate.
    I was sweating over this theory on a training course and its a relief to now understand it. Thanks to your excellent communication skills. 👏

    • @learnelectrics4402
      @learnelectrics4402  3 роки тому

      Glad we could help John, spread the word. Dave.

    • @adebayoagbaje
      @adebayoagbaje 2 роки тому

      Yes, I completly agree. Easy to follow through.

  • @nickknowledge298
    @nickknowledge298 Рік тому

    Thanks a lot dude. Just about to complete my engineering apprenticeship and now wish to base my career from an electrical bias. These theories aren't so intimidating when broken down and structured as well as you have demonstrated here 👍👍 will be sure to watch more. Thanks again

    • @learnelectrics4402
      @learnelectrics4402  Рік тому

      Thanks for the feedback. There is access to over 200 videos on the website LearnElectrics.com Dave.

  • @MegersaDuguma-hu2yg
    @MegersaDuguma-hu2yg Рік тому

    It's very important idea and concept about Electrical Engineering

  • @matthewdaniel1715
    @matthewdaniel1715 2 роки тому

    Master your videos are superb. I'm not yet an electrical engineering student but I'm about to be, watching your videos is pretty good for a lost sheep. After tons of research this piece just made my day.

    • @learnelectrics4402
      @learnelectrics4402  2 роки тому

      Thanks Matthew, good luck with your studies. Thanks for watching and keep learning. Dave.

  • @mossmm73
    @mossmm73 Рік тому

    Thanks once again for well presented technical material in the subject of electrical calculations
    Kindly keep them coming
    Thanks

    • @learnelectrics4402
      @learnelectrics4402  Рік тому

      Thank you, I will, lots more to come. Thanks for watching. Dave.

  • @shiamjad
    @shiamjad 2 роки тому

    i learnt more from you than from my 2 years at the college... keep the excellent work up

  • @CosiMonger
    @CosiMonger Рік тому

    Excellent video. I learned a lot about choosing the correct wire size and fuse to be used.

  • @ngqabuthongwenya3286
    @ngqabuthongwenya3286 3 роки тому +1

    Thank you so much, your explanation is perfect. In class they gave us handouts stating the steps of finding the cable size with these Ib, In, Iz symbols, never understood the meaning of these symbols, and now that i viewed this well explained video everything became clear

    • @learnelectrics4402
      @learnelectrics4402  3 роки тому

      So glad that it helped. Tell the rest of your class mates about us, it makes it all worthwhile to keep making more videos. Dave.

  • @abrananthamvelraj709
    @abrananthamvelraj709 3 роки тому

    Dear your explanation was so simple and it is delivering your experience. thanks ......

  • @jesswimbledon2118
    @jesswimbledon2118 2 роки тому

    Thank you for this video, something what i thought id never get my head around made it very easy by watching this. once again thank you

    • @learnelectrics4402
      @learnelectrics4402  2 роки тому

      Great to hear that Jess. If the video helped, its done its job. Dave.

  • @001Neal100
    @001Neal100 Рік тому

    Thank you for explaining this better than the big book! It's quite a simple theory, made incredibly confusing and baffling by the wording in BS7671. I don't know why they don't just print the formula in BS7671 instead of the 3 bullet points.

    • @learnelectrics4402
      @learnelectrics4402  Рік тому

      Unfortunately we have no control over how the boffins lay out the book. Glad it helped. Dave.

  • @robertpeters8531
    @robertpeters8531 2 роки тому

    Fantastic explanation really informative. Completed a domestic installers course with a well known training centre and this is great to keep my knowledge from rusting up. Great stuff and easier to understand.

  • @2scots
    @2scots Рік тому

    Very easy to understand. Great video. Cheers

  • @paulward143
    @paulward143 Рік тому

    Thankyou really clear and easy to understand

  • @marcjackson9943
    @marcjackson9943 2 роки тому

    Its great the way you simplify it by using that box method,really helpful.

  • @slapman7646
    @slapman7646 2 роки тому

    I've done 3 years of evening college, honestly wish I'd come across your videos first.

    • @learnelectrics4402
      @learnelectrics4402  2 роки тому

      Well, you've found them now. Stick with it, it really is a good trade to be in. It's taken me around the world several times, worked in some fantastic places. Dave.

  • @MS-Patriot2
    @MS-Patriot2 3 роки тому

    Hi Dave, I recently completed and passed an excellent domestic electrician course at EC4U in Ditchling. Your video series is a superb “old-school” reinforcement of these key principles and in some cases has offered an even clearer explanation, or at least a different perspective on the same learning points. Being an older learner who has recently changed to the electrician career, this series has been brilliant. Thank you!

    • @learnelectrics4402
      @learnelectrics4402  3 роки тому +1

      Thank you Mike for the very positive feedback. Our aim is to produce videos that tackle just one subject each week and they are based on all the questions and difficulties that electricians and learners have had over the years during the time that we ourselves have been working on the tools and as assessors and instructors. There are many more to come yet, keep watching and thanks again. Dave.

    • @hingninwong
      @hingninwong 3 роки тому

      Mike.
      How about the Domestic Electrician course in EC4U? I also want to join it.

    • @MS-Patriot2
      @MS-Patriot2 3 роки тому

      @@hingninwong yes, look them up on google. The website is easy to navigate. Good luck!

    • @hingninwong
      @hingninwong 3 роки тому

      @@MS-Patriot2
      does the domestic electrician couse fit your purpose, such as capable for you to do the minor electrical work ? Any comment to this course?

  • @paulward143
    @paulward143 2 роки тому

    Very clear and easy to understand 👌

    • @learnelectrics4402
      @learnelectrics4402  2 роки тому

      Great. That's exactly what we wanted to achieve. Thanks for watching. Dave.

  • @dwelby101
    @dwelby101 Рік тому

    Great video, very well explained, clear and to the point. Thank you very much

  • @elitorres1192
    @elitorres1192 7 місяців тому

    First video I see from your channel, amazing 👏. Thank you for your content sir.

    • @learnelectrics4402
      @learnelectrics4402  7 місяців тому

      Keep watching, lots more to come. Thanks for the comments. Dave.

  • @iqbalnuthoo1566
    @iqbalnuthoo1566 3 роки тому

    Again very well explained. totally at ease with the way you explain things. very well done

  • @shiawrzgar1745
    @shiawrzgar1745 Рік тому

    you're the great explainer.

    • @learnelectrics4402
      @learnelectrics4402  Рік тому

      The great explainer, sounds like a song. Thanks for the great feedback, really appreciated. Thanks for watching. Dave.

  • @danielteyehuago1633
    @danielteyehuago1633 2 роки тому

    You made it simple for us...

  • @aleko_
    @aleko_ Рік тому

    Thank you so much for these valuable videos. Much appreciated 🙏

  • @SterIingM
    @SterIingM Рік тому

    I think it’s worth mentioning that when you’re calculating your design current, if it is a 3 phase system you would put root 3 at the bottom of the fraction and if you have a power factor you would put Cos(power factor) at the bottom of the fraction aswell

  • @aarondunlop-p4k
    @aarondunlop-p4k Рік тому

    Fantastic video. What would change in the calculations if it was on a tt system. ?

    • @learnelectrics4402
      @learnelectrics4402  Рік тому +1

      Nothing should change. Install conductors with sizes as if they were in a TN-C-S system. They still have to take overload currents. Its just that your measured ZS will be all over the place. Dave.

  • @annamhaid4047
    @annamhaid4047 2 роки тому

    A fantastic help. Thanks for the video!

  • @hooshangkhamayezi9427
    @hooshangkhamayezi9427 3 роки тому +1

    First of all I want to say thanks a lot for all
    Your excellent video. I would like to ask about 3 phase circuit how we can find out about Ib and cable size .

    • @learnelectrics4402
      @learnelectrics4402  3 роки тому

      Thanks for watching, glad you found it useful.
      We will be posting a video soon on 3 phase cable sizes, lots of people asking for information. Good request. Dave.

  • @CommonInvesting
    @CommonInvesting 3 роки тому

    What a video, great at explaining and making things more clear and easier to understand! Bravo!

    • @learnelectrics4402
      @learnelectrics4402  3 роки тому

      Thank you so much David. We really appreciate your positive comments. Dave.

  • @leehazelwood6471
    @leehazelwood6471 3 роки тому +1

    Love the video, the way it is explained is brilliant, grateful of the videos👍

    • @learnelectrics4402
      @learnelectrics4402  3 роки тому

      Thanks for the really positive feedback. We try our best. Lots more to follow. Dave.

  • @fut_tczc8589
    @fut_tczc8589 Рік тому

    Im training as an electrician and your videos are very helpful, i can see this calculation wiuld be good for an individual radial or ring say for a shower or cooker, how would this woek with lighting circit or socket? I am starting my NVQ level 2 in september so sorry if this is a basic question.

    • @learnelectrics4402
      @learnelectrics4402  Рік тому +1

      There are standard sizes that we usually use for each type of circuit. The important thing is that the cable capacity MUST be equal to or greater than the fuse/breaker rating. I'll be doing a video on this soon. Stick with it, its a good trade to be in.

  • @lewisdebono6166
    @lewisdebono6166 Рік тому

    Thankyou for your amazing video.

  • @bharatgurung5848
    @bharatgurung5848 3 роки тому

    Thank you so much for the lesson. It was so easy for me to understand the way you explained.

    • @learnelectrics4402
      @learnelectrics4402  3 роки тому

      Brilliant. That's exactly the feedback that we want. One video, one topic, made easy.
      Lots more videos on the way. Dave.

  • @smartchip
    @smartchip 2 роки тому

    Really really good video, thanks,

  • @abrehamish
    @abrehamish 3 роки тому

    Thank you for your excellent video.

  • @danielteyehuago1633
    @danielteyehuago1633 2 роки тому

    Thanks for sharing it with us

  • @danielteyehuago1633
    @danielteyehuago1633 Рік тому +1

    Wow! This is very informative, thanks for sharing it with us. It worth it and the best tutorial on the topic for me...dl

  • @johnnyeboy33
    @johnnyeboy33 Рік тому

    Thanks Dave, your a Legend loving all of your video
    Have a great Christmas & take care

    • @learnelectrics4402
      @learnelectrics4402  Рік тому

      Thanks Johnny, thanks for the support and have a great Xmas yourself. Dave.

  • @paborlouise319
    @paborlouise319 3 роки тому

    I've been looking for this for a long time now. Well explained, thanks a lot.

    • @learnelectrics4402
      @learnelectrics4402  3 роки тому +1

      Great Pabor, glad it was helpful. Lots more to come, check out our other 50 plus videos.

  • @jasonturvey360
    @jasonturvey360 11 місяців тому

    another great video, i did miss the normal couple practise questions you put in though.

    • @learnelectrics4402
      @learnelectrics4402  11 місяців тому

      This is an older video, before I started doing that. Thanks for watching. Dave.

  • @mathukomanuraksilarat69
    @mathukomanuraksilarat69 4 роки тому

    Just wow this video is gold

    • @learnelectrics4402
      @learnelectrics4402  4 роки тому

      We're glad you like it. keep watching, more to follow. Dave

  • @drf16788
    @drf16788 2 роки тому

    Seems easy enough as you explained in great detail, I am looking to install panel heaters in my flat, can these just be added to ring main or need a separate circuit, if a separate circuit then can I do myself to save money?

    • @learnelectrics4402
      @learnelectrics4402  2 роки тому +1

      Consult the heater manufacturer's instructions. Some say that they can be plugged in, coming with a fitted plug is usually a good clue. Other heaters are recommended on their own circuit.
      Adding a new circuit assumes that you are competent and can notify the work to LABC afterwards. Only you will know if you can do this. If you are unsure, I would suggest using a REGISTERED electrician, but ask to look at his registration card (NAPIT, NICEIC etc) before giving him/her the job and before handing over any money. Tell them you want a Building Control certificate when the job is finished. And get three written quotes before making a decision.

    • @drf16788
      @drf16788 2 роки тому

      @@learnelectrics4402 thanks, the heater doesn't come with a plug, needs wired in to a fused switch

  • @hammadasif9881
    @hammadasif9881 3 роки тому

    Very good explanation

  • @naimsaby9473
    @naimsaby9473 10 місяців тому

    Love yr video's can you please make a video on two way lighting circuit and fault finding if the wire's mixed up on celling rose and the switch thankyou

    • @learnelectrics4402
      @learnelectrics4402  9 місяців тому

      We have lots of videos on all aspects of lighting on our website.
      Go to LearnElectrics.com and put lighting into the search box and you will get a list of all the videos about lighting and direct links to the videos.
      Hope this helps, thanks for watching.
      Have a look at lighting Differences on this link
      ua-cam.com/video/NEjCXO_ZC5c/v-deo.html

  • @hussmortada
    @hussmortada Рік тому

    Love it! Thank you once more

  • @aeneasbekele7084
    @aeneasbekele7084 3 роки тому

    I'm glad to get ur channel sir,10Q

  • @franciscogago5961
    @franciscogago5961 Рік тому

    Well done again...

  • @angelofranklin1
    @angelofranklin1 3 роки тому

    Hi Dave, very well explained thank you.

  • @lawrencer25
    @lawrencer25 Рік тому

    ❤fabulous video ❤

  • @hadesbearer
    @hadesbearer 2 роки тому

    Thank you for the video. What is the difference between "rating" and load" in the table on page 64. Is this assuming diversity of 80% e.g. the shower is off for at least 12 minutes in every hour of use?

    • @learnelectrics4402
      @learnelectrics4402  2 роки тому

      Load is the amount of current you put through a fuse. A kettle might put a load of 13A on the circuit.
      A table lamp might have a load of half an amp
      The rating of the breaker in the consumer unit might be 20A or 32A if a ring
      Hope this helps. Dave.

  • @mohsenk5985
    @mohsenk5985 11 місяців тому

    Great information

  • @hingninwong
    @hingninwong 3 роки тому +1

    Thanks for your prompt reply. In your video, you said you choose 6mm cable is based on method 100 in 2nd row, but 3rd row also has method 100. So may I ask to explain more by based which Wiring Reg. , we should choose 6mm but not 10 mm cable? I have confusion to choose one between them. Thanks.

    • @learnelectrics4402
      @learnelectrics4402  3 роки тому

      You need to look at all the information on each line. With 6mm cable the maximum cable length is 63 metres which is more than long enough for most domestic dwellings and this matches up with the rest of the information on the slide. If you install 10mm you can take the length to 105 metres. Hope this helps.

    • @hingninwong
      @hingninwong 3 роки тому +1

      @@learnelectrics4402
      Yes, i got it that based on the length of cable for the house dwelling in this case. Thanks.

    • @kevinkearney9179
      @kevinkearney9179 3 роки тому

      A 6mm cable (6 sq mm) is fine when the insulation stays the same and the shower remains at 7000 W. A 6mm cable is near the limit. The user may well fit a 8000 W shower when a 7000 W shower becomes unavailable on replacement by a plumber. Or the insulation is upgraded. On balance I would install a 10 mm (10 SQ mm) cable.

  • @hingninwong
    @hingninwong 3 роки тому +1

    Thanks useful video. For the video of playing at 8:57, may I ask why not choose cable size of 10mm/4mm?

  • @lylewatts6370
    @lylewatts6370 3 роки тому

    Again an excellent video and thank for the great explanations.

  • @stepheneurosailor1623
    @stepheneurosailor1623 2 роки тому

    Great ,subscribed.

  • @NaciMahmut-rf5xf
    @NaciMahmut-rf5xf 9 місяців тому

    When working out design current, you may have to apply a power factor, depending on the efficiency of the install equipment. If the equipment has a poor power factor this will have an effect on the cable under full load conditions.
    When applying the power factor you multiple the nominal voltage by the power factor & then divide the power of the installed circuit.
    Three phase design current is 400v x square root of 3 x power factor / power.

    • @learnelectrics4402
      @learnelectrics4402  9 місяців тому

      Excellent support. Take a look at our power factor video on this link
      ua-cam.com/video/bXiE9bdFLsU/v-deo.html

  • @kennethfajardo9554
    @kennethfajardo9554 4 місяці тому

    hello Sir can I ask what book you use for the tables amd charts you used in the video? thank you in advance

    • @learnelectrics4402
      @learnelectrics4402  3 місяці тому

      These are taken from the OSG (blue version). The brown version of the OSG will have different page numbers. Perhaps I should do another video for the brown books. Dave.

  • @jakehughes7521
    @jakehughes7521 4 місяці тому

    Boss explanation this is.

  • @Trade920
    @Trade920 3 роки тому

    Fantastic video again thank you, if you were installing a domestic cooker circuit for a 16.5kw cooker and induction hob (very large i know) how would you go about that?
    Would you install a 16mm cable that would be able to handle the full maximum load of 67amps or with diversity included would say a 10mm cable would be sufficient?
    Installation method ref method c no insulation and 8 meters of cable for the circuit
    Sometimes these scenarios confuse me a little and i don’t feel 100% confident with selecting the correct size cable.
    Any help would be greatly appreciated thank you

    • @learnelectrics4402
      @learnelectrics4402  3 роки тому

      Thank you for watching and the great comment.
      We have a video that will show you how to calculate diversity for your cooker.
      The example in the video is for a 7kW cooker, just change the necessary numbers.
      Cheers, Dave.
      To view the video, DIVERSITY and MAXIMUM DEMAND, click on the link below
      ua-cam.com/video/TV2IZtmydm4/v-deo.html

    • @Trade920
      @Trade920 3 роки тому

      @@learnelectrics4402 thank you very much your videos are extremely well presented and helpful keep up the great work

    • @learnelectrics4402
      @learnelectrics4402  3 роки тому

      Thanks again. Happy to help. Dave.

  • @rezamaddah2010
    @rezamaddah2010 3 роки тому

    Thanks for help

    • @learnelectrics4402
      @learnelectrics4402  3 роки тому

      Always happy to help Reza, it makes the world go round. Dave.

  • @aliherati5069
    @aliherati5069 4 місяці тому

    Hi
    Thanks for good clips . I am a bit confused though When I calculate for 63 meter 6 mil cable the voltage drop will be 14 volts which is over the allowance voltage drop . example in this clip according to table 7.1 onsite guide
    (7.3*30.43*63)/1000=13.99voltage drop which is more than 11.5 volts allowance

    • @learnelectrics4402
      @learnelectrics4402  3 місяці тому

      Some of the pre-calculated tables take diversity, RCDs, and other factors into account. I will be revamping this video to the brown OSG later this week. Thanks for the input.

  • @karamathussain3488
    @karamathussain3488 3 роки тому

    Thank you for the breakdown it always helps when it’s explained correctly. Please keep up the good work you have my full support. Regards Karamat Hussain

  • @aliherati5069
    @aliherati5069 2 роки тому

    thank you so much for clear clips. can I ask you if we have 63 meter cable length and use voltage drop formula vd={(44/6)*63*32 }/1000 the result will come to 14.7 volts and because its greater than 5% allowance means 11.5 volts is it acceptable ?

    • @learnelectrics4402
      @learnelectrics4402  2 роки тому

      A 14.7 volt drop isn't acceptable as its above the values in the Regs. You would need a bigger cable size. Dave.

  • @mohantyagi5740
    @mohantyagi5740 2 роки тому

    ETAP design and simulation software has already been introduced long back merging formulas, considerations, conditions,standards and requirements.

    • @learnelectrics4402
      @learnelectrics4402  2 роки тому

      It has Mohan, but unfortunately its not allowed in an exam. Thanks for watching. Dave.

  • @powercoolmarine6322
    @powercoolmarine6322 2 роки тому

    Can you explain the digital scale on a multimeter for measuring resistance? The only thing I can find is a old vid from perkies talking about ohms scale?! Many thanks do you have an e mail I like to talk about the course I’m doing !

    • @learnelectrics4402
      @learnelectrics4402  2 роки тому +1

      Thanks, I've put this on the to do list of videos. Dave.

  • @Jim804
    @Jim804 Рік тому

    Hi Dave, When you mention @3.23 "larger cable " "paying for extra copper that you do not need". Is this the only reason? Will a larger cable not affect anything else, only cost?

    • @learnelectrics4402
      @learnelectrics4402  Рік тому

      A larger cable will carry more current more easily and will not heat up at the same rate as smaller cable sizes, We can always install bigger cable and know that we will not have a problem, except perhaps with getting the cable into the terminal holes, 10mm shower cable will work for a lighting circuit but no way will it fit in the switch (an extreme example, sorry). So yes, that little section comes down to cost. Good question and thanks for watching. Dave.

  • @orestismiaris4928
    @orestismiaris4928 Рік тому

    Hi Dave, another excellent video, we all thank you for all you are doing. I'm confused about the choice of cable size. On the chart on page 72 I see many entries with a rating of 32A that fit with the 100 installation method, why did you say there is only one?
    Also, do you know where in the book we could find the installation methods? Again, thanks for what you are doing.

    • @learnelectrics4402
      @learnelectrics4402  Рік тому

      You will find installation methods begin on page 433 of the Wiring Regs book.
      If it is flat profile twin and earth we choose the nearest size cable equal to or greater than 32A which is 6mm. See Table 4D5 on page 456. Hope this helps. Dave.

  • @edh4808
    @edh4808 3 роки тому

    Hi Dave, could you do a similar video for three phase?

  • @murwanashyakajustin2278
    @murwanashyakajustin2278 3 роки тому

    Thanks for good explanation
    But I need that book

    • @learnelectrics4402
      @learnelectrics4402  3 роки тому

      Thanks for the good feedback Justin.
      The book is the IET On-Site Guide 18th Edition.
      You will get it from Amazon or google search it or even Ebay.
      MAKE SURE that it is the BLUE 18th EDITION copy.
      Any other colour will have different data on some pages and different page numbers and is no good to you.
      Good luck, and thanks for watching. Lots more videos to come. Dave.

  • @cobydavies5304
    @cobydavies5304 4 роки тому +1

    Perfect thank you

  • @shannonj1000
    @shannonj1000 6 місяців тому

    Hi great video but ai am confused you say at 8:32 there are 2 entries for 32a when there are 9, & 6 of them meet the installation method 100.. am I missing something obvious this is a little old not as page 82 now.. your help here would be most appreciated.. Thanks

    • @learnelectrics4402
      @learnelectrics4402  3 місяці тому

      2 entries for that type of protective device. The OSG covers several devices, breakers, fuses etc. I will be re-vamping this video, this week to accord with the brown OSG and will take your comments into account for a better explanation.

  • @JC-NUFC
    @JC-NUFC 3 роки тому

    Is this an alternative method to using the 18th Edition BBB and using the design current x length of cable x mv/A/m x any grouping factors?

    • @learnelectrics4402
      @learnelectrics4402  3 роки тому

      This video is about Ib In Iz. Condition factors are covered in a different video.
      Thanks for watching. Dave.

  • @davepotter5679
    @davepotter5679 2 роки тому

    You do some great videos Dave and explain things really well but I think this method is incorrect.
    Table 7.1 of O.S.G assumes a max load of 26A for a 32A 60898 breaker where your shower has an IB of 30.43A.
    I have always used and taught cable calcs using the tables from App' 4. Keep up the good work though Dave your explanations are great.
    👍🏻

    • @learnelectrics4402
      @learnelectrics4402  2 роки тому

      No Dave, the video is correct for a dedicated shower circuit, nothing else on it. Are you perhaps looking at maximum length for a 32A Type C breaker which is 26 metres due to Zs limits? Great comments and support. Thanks, Dave.

    • @davepotter5679
      @davepotter5679 2 роки тому

      @@learnelectrics4402 Dave could I private message you tomorrow about this?

    • @learnelectrics4402
      @learnelectrics4402  2 роки тому

      By all means Dave, yes. There is also another table in section 7.1 that states assumed maximum is 26A, but this is not a :Should not exceed: value and has been used for cable length calculations. The Electricians Guide to the Building Regs also states that a 7kW shower can be installed on 6mm cable with a 32A breaker. Dave.

    • @davepotter5679
      @davepotter5679 2 роки тому

      @@learnelectrics4402 how do I contact you?

    • @learnelectrics4402
      @learnelectrics4402  2 роки тому

      Dave, I looked for you under DavePotter on Facebook. There are six, which one are you? I was going to send you a friend request. Or you can send a friend request to FB for LearnElectrics or Dave Buckley. My profile image is me with a blue jumper and the union flag in the background. Speak soon buddy.

  • @Hff19927
    @Hff19927 9 місяців тому

    Ref method 100 @ 8:00. The maximum load is 26A but our design current is 32A. Wouldn’t you use the one below?

    • @learnelectrics4402
      @learnelectrics4402  9 місяців тому

      Have another look at the video. Max load is almost 31 amps. Thanks for watching, Dave.

    • @Hff19927
      @Hff19927 9 місяців тому

      ⁠​⁠@@learnelectrics4402apologies, not 32A I mean 30.43A. I was referring to the second you highlighted in the table. There’s a column that says “Load (A)” i wondered if that was the maximum load permitted, and if so, that is lower than the design current.

  • @jahanmoh
    @jahanmoh 2 роки тому

    Thank you

  • @richardhart7652
    @richardhart7652 2 роки тому

    Can I purchase a copy of the on site book in paper version as I find it hard reading from screens

    • @learnelectrics4402
      @learnelectrics4402  2 роки тому +1

      Yes Richard. Amazon is probably about your cheapest. The current 18th Edition is a blue book, BUT Amendment 2 is due to be issued very soon. Whether that is weeks or months we don't know. If you buy the blue OSG you may need to buy the new amendment 2 when that comes out. Current price for the On-site Guide is about £30 depending on what deals are on.

  • @williamdlamini3104
    @williamdlamini3104 Рік тому

    Morning is possible to get on side guide?

  • @markr452
    @markr452 2 роки тому

    Brilliant

    • @learnelectrics4402
      @learnelectrics4402  2 роки тому

      Thanks for the feedback. How is good old Shropshire, I lived in Shrewsbury for 20 years before heading south for the sun. Thanks for watching. Dave.

  • @emrysdavies6444
    @emrysdavies6444 2 роки тому

    Really useful videos for someone learning the trade.
    With regards to choosing the cable size, I'm just a bit confused, could you also choose the 10/4 mm too seeing as it also allows 100 as the installation method?

    • @learnelectrics4402
      @learnelectrics4402  2 роки тому +1

      You can always go up in cable size, the difficulty might be in getting the conductors to fit in the accessory. Thanks for watching. Dave.

    • @emrysdavies6444
      @emrysdavies6444 2 роки тому

      @@learnelectrics4402 Ah, I get it....thanks for answering

  • @Pgan803
    @Pgan803 Рік тому

    For Showers/Heaters shouldnt the RCD be 10mA in BS7671 18th instead of 30mA?

    • @learnelectrics4402
      @learnelectrics4402  Рік тому

      30mA is the recommended RCD. You can fit 10mA if you wish but you may find you get nuisance tripping,

  • @kylegreenslade9952
    @kylegreenslade9952 6 місяців тому

    Hey Dave just a quick question if the shower is taking 30amps on a 32 breaker but the cable rating is 34 so is that mean the shower is taking 34amps? Which will trip the breaker?

    • @learnelectrics4402
      @learnelectrics4402  4 місяці тому

      The cable can take up to 34 amps but the actual current in the cable depends on the load.
      A 1 amp bedroom lamp pulls the same current through a 10mm cable as it does for a 1mm cable - about 1 amp

    • @kylegreenslade9952
      @kylegreenslade9952 2 місяці тому

      @@learnelectrics4402alright thank you so if an appliance was taking 45amps and let’s say you wanted to use a 6mm cable what breaker size would you choose a 45 or 50?

  • @siuuu6724
    @siuuu6724 2 роки тому

    but will this table be inside the regs A32:2022 book ?

    • @learnelectrics4402
      @learnelectrics4402  2 роки тому +1

      Not that exact table, that is my own table to show you ta simple relationship. Thanks for watching. Dave.

  • @Sol6567
    @Sol6567 Рік тому

    You sis not mention factors like Ca for ambient temperature Cg for grouping ?

  • @Mok-l5i
    @Mok-l5i 3 роки тому

    Thanks really perfect

  • @ajmala7979
    @ajmala7979 3 роки тому

    Brilliant A1

    • @learnelectrics4402
      @learnelectrics4402  3 роки тому

      Thank you. Great comment, it makes our hard work worthwhile.

  • @lukabalic3541
    @lukabalic3541 Рік тому

    Do these tables are valid only for UK or for the whole of Europe?

    • @learnelectrics4402
      @learnelectrics4402  Рік тому

      The Regs are for the UK only. But I used the same data when I worked in France as many devices are BS EN approved. I should check with a local electrician in the country of your choice before relying on them.

  • @electricalstuff259
    @electricalstuff259 3 роки тому

    LOVE these

  • @legendsummoner1863
    @legendsummoner1863 2 роки тому

    I have some questions, if I calculated the design current to be 102 A and I need to choose a circuit breaker, as you said that the circuit breaker needs to be bigger than the design current, can I choose 125A, 150 A, 200A circuit breaker? what is the difference? Is it appropriate to choose the 200A like the bigger the better? Just cut out the cost issues and focus on the safety of the system.

    • @legendsummoner1863
      @legendsummoner1863 2 роки тому

      Thank you in advance for valuable lessons!

    • @learnelectrics4402
      @learnelectrics4402  2 роки тому

      No, bigger is not safer. Ideally you need the same size or the next size up that doesn't exceed the design current. We want to fuse as close as we can to the design current for safety.

    • @learnelectrics4402
      @learnelectrics4402  2 роки тому

      You are very welcome.

  • @elumalai-007
    @elumalai-007 Рік тому

    Thanks nice

  • @hingninwong
    @hingninwong 3 роки тому

    Thanks useful video. For the video of playing at 8:57, may I ask why not choose cable size of 10mm/4mm? (3rd row data)

    • @learnelectrics4402
      @learnelectrics4402  3 роки тому

      We have to show the method adopted by the Regs, which is the nearest size suitable. In this case 6mm is just big enough. I agree that in practice you may want to install 10mm cable.
      Thanks for the nice comments.

    • @hingninwong
      @hingninwong 3 роки тому

      Thanks for your prompt reply. In your video, you said you choose 6mm cable is based on method 100 in 2nd row, but 3rd row also has method 100. So may I ask to explain more by based which Wiring Reg. , we should choose 6mm but not 10 mm cable? I have confusion to choose one between them. Thanks.

  • @imogirie
    @imogirie 2 роки тому

    Hi, why not using Power Factor in Current calculation?

    • @learnelectrics4402
      @learnelectrics4402  2 роки тому

      These are the basic single phase calculations. We cover three phase power factor in another video.
      Thanks for watching.
      Dave.

  • @detroutspinners9933
    @detroutspinners9933 Рік тому

    This says In must be equal to or less than Iz - so in theory a length of 1.5mm flex is fine on a 16a MCB, given that they’re both rated for 16 amps?

    • @learnelectrics4402
      @learnelectrics4402  Рік тому +1

      Thanks for watching, appreciated. Have a look at this video. Dave.
      ua-cam.com/video/VtTUkUpQ-Rc/v-deo.html

    • @detroutspinners9933
      @detroutspinners9933 Рік тому

      @@learnelectrics4402Thanks for the reply, can I clarify something in the video you linked?
      It states the equation Ib ≤ In ≤ Iz, however the summary text states that Iz must in fact be greater than In.
      Just wondering, as the formula implies that selecting a breaker rated the same as the CCC of the cable is fine. So would a 10amp breaker be fine for a cable that can only carry 10 amps, for example?

  • @maryamyaseen6690
    @maryamyaseen6690 2 роки тому

    Thanks