Daikin error code - E5 inverter pcb board compressor problem emergency mode run standard compressor

Поділитися
Вставка
  • Опубліковано 18 вер 2024
  • ‪@plushvac‬
    please subscribe my channel 🙏
    Brand - Daikin vrv 3
    error code - E5
    Today attended compliant Aircon blinking.
    check on site and found thermostat blinking error code - E5 inverter pcb board and compressor problem.and than we try with normal mode cannot run again error code E5.
    system have inverter and standard compressor, so we try to run system for emergency mode.
    after emergency mode standard compressor can run, waiting for replace inverter compressor and inverter pcb board,after that we change to normal mode setting
    thanks for see my video 🙏
    • #PlusHVAC error code.
    • #plusHVAC shorts
    • #plusHVAC repair & ser...

КОМЕНТАРІ • 12

  • @PriyankaSingh-pr4sd
    @PriyankaSingh-pr4sd 8 місяців тому

    Very good 💯

  • @riteshkumar6554
    @riteshkumar6554 Рік тому

    Nice 😎

  • @jeelanjeelu470
    @jeelanjeelu470 Рік тому

    VRV 3 Multi outdoor units emergency setting plz share...

  • @glennbesin27
    @glennbesin27 11 місяців тому

    I ask questions..wat is model# that unit sir? Can u show?.

    • @plushvac
      @plushvac  11 місяців тому

      VRV 3 rxq10pay

  • @user-xn9vh3ri5w
    @user-xn9vh3ri5w 6 місяців тому

    After bypass again how back to normal mode?

  • @hamdanchaus2940
    @hamdanchaus2940 Рік тому

    Hello boss I have one question if the inverter pcb will damage then how get the power for standard compressor can you explain that

    • @plushvac
      @plushvac  Рік тому +1

      Hi bro .in this video please see 5.18 minutes show one contractor.this contractor 3 phase supply take from main power source and after contractor power go to standard compressor.
      Standard compressor power not come inverter pcb board.
      It come from contractor and main 3 phase supply.
      Thanks for see my video 🙏
      Please 🙏 subscribe my channel.

    • @IMRANKHAN-rr5ut
      @IMRANKHAN-rr5ut Рік тому

      i also work in daikin but i want vrv3 and vrv 4 sitting list

    • @plushvac
      @plushvac  Рік тому

      I learn with my engineer.