Open Loop Vaillant Arotherm Plus 10KW. Keep it Simple?

Поділитися
Вставка
  • Опубліковано 23 січ 2025

КОМЕНТАРІ • 57

  • @MetodiStDimitrov
    @MetodiStDimitrov 24 дні тому

    Is open loop possible for both heating and cooling systems and hybrid heat pump and gas boiler? Like two floor house with both floors fully underfloor heating and then water convectors for cooling. Around here outdoor temp goes from -10 to 30 degrees C.

  • @loving-plumbing
    @loving-plumbing 10 місяців тому

    Cliff hanger at the end 😂. Good work.

  • @kenbone4535
    @kenbone4535 10 місяців тому +2

    Open loop amazing, shame the industry is about 2 decades behind.

  • @RyanMartindale-t1g
    @RyanMartindale-t1g 10 місяців тому

    Great video pal 👊🏻

  • @Liam_Hirst
    @Liam_Hirst 10 місяців тому +1

    Is the volumiser just for the defrost cycle?

    • @McOw123
      @McOw123 9 місяців тому

      I’ve just had the 5kW version installed with identical 50L volumiser, my installer (Heat Geek Elite) confirmed it was not just for defrost cycle but also ensuring there was enough volume in the circuit to prevent the ASHP cycling as much as it might without it (due to size of my system aside from the volumiser)

  • @theghostofsirjohnharveyjon8730
    @theghostofsirjohnharveyjon8730 10 місяців тому +2

    That's a tidy install fair play. What kind of cop do you think it will get?

  • @handle1196
    @handle1196 3 місяці тому

    What brand is the red and blue mlcp

  • @pmbpmb5416
    @pmbpmb5416 8 місяців тому

    I’m having two 12kw cascaded , I don’t know enough to be sure whether a none zoned open loop system would work . Ufloor on ground floor radiators on other two which I’m hoping to size sufficiently to balance . I’d like to get it down to 35 flow but currently spec is 50 , which worries me for running cost . Re insulated everything.

    • @griffithsheating
      @griffithsheating  8 місяців тому

      We’ve done a similar split upstairs / downstairs cascade with a pair Viessmann vitocals. You will have better low modulation performance and ultimate control in this configuration in my opinion. Not sure you could open loop a true cascade as it would probably need a buffer I would have thought. There is nothing wrong with a buffer, not everyone is interested in chasing the last few percentage of performance. Its a central heating system not formula 1 car

  • @joehaskett90
    @joehaskett90 10 місяців тому

    Does the system not have enough volume for the defrost cycle? Would of that you could of got away without the volumizer

    • @griffithsheating
      @griffithsheating  10 місяців тому +1

      I was thinking more of minimum run times when it’s mild out. I have seen Arotherms ice up though even when volume seems to be ok.

    • @kenbone4535
      @kenbone4535 10 місяців тому +1

      Nope, the open loop system becomes the volume you need for Defrost, been installing like this for decades already.

    • @pradhpatle
      @pradhpatle 9 місяців тому

      @@kenbone4535 Specially with UFH you have lot of energy mass around in case you need any excess energy for defrost.

  • @markfernandes2467
    @markfernandes2467 6 місяців тому

    Why fit the buffer?

    • @griffithsheating
      @griffithsheating  6 місяців тому

      @@markfernandes2467 it’s not a buffer

    • @markfernandes2467
      @markfernandes2467 6 місяців тому

      @@griffithsheating Is there a difference then? What does a vollumiser do then and why did you use one of those?

    • @griffithsheating
      @griffithsheating  5 місяців тому +2

      @@markfernandes2467 yes. A buffer provides a hydraulic break between the heat pump (primary side) and the system (secondary side). So an additional pump is required for circulation in the secondary side. If the flows are poorly balanced between the primary and secondary side you get what’s called distortion where the heat pump may be delivering 45 degrees but the buffer is only supplying 40 degrees so the heat pump has to run at 50 due to achieve 45 degrees in the system. The upside of a buffer is that you can get away with murder on the system design and the heat pump won’t notice but your efficiency will suffer.
      There is a bit of dogma around buffers amongst the pseudo online big brains. They’ll decry buffers from the rooftops and smugly rip an install apart because it has a buffer. I have Viessmann systems running buffers with scops almost touching 5 after nearly 2 years.
      A volumiser is essentially just a big tube of water sitting inline just to increase water volume in the system to help with defrost volume or to increase compressor run times when it’s mild out.

  • @lukeb6565
    @lukeb6565 5 місяців тому

    Shouldn’t volumizer have return come in from top and leave bottom?
    Is a PRV normal on a volumiser?

    • @lukeb6565
      @lukeb6565 5 місяців тому

      Is there no Tesla valve for maintenance on exspansion vessel on buffer?

    • @lukeb6565
      @lukeb6565 5 місяців тому

      Do you not need a bypass?

    • @lukeb6565
      @lukeb6565 5 місяців тому

      Wouldn’t you rather air air vent top of volumiser

    • @griffithsheating
      @griffithsheating  4 місяці тому

      @@lukeb6565 volumiser is piped like that. Prv on volumiser isn’t normal but it is a good a place as any to put it. No valve on exp vess. No need. We could have put an air vent in but doing the vessel like that was a neat solution. Plenty of air vents on the system otherwise. 😎

  • @saadrasheed101
    @saadrasheed101 8 місяців тому

    Looks like a 3 port volumiser?

  • @alimack5489
    @alimack5489 10 місяців тому

    Going to sound stupid here but how does that comply with G3 requirements if it doesn’t have a two port on the DHW I take it’s interlinked with an overheat stat on the tank?

    • @griffithsheating
      @griffithsheating  10 місяців тому +3

      Not required (it's not shown on the vaillant schematics at least) I don't use 2 ports or over heat stat on gas either if I'm fitting a Viessmann boiler with an ntc sensor on 4 pipe. G3 police haven't arrested me yet... 🚓

    • @TheDickPuller
      @TheDickPuller 10 місяців тому

      @@griffithsheatingBuilding Control would not give you a completion certificate with no 2 Port on the UVC here in Jockoland mate!!!

  • @Allegedly2right
    @Allegedly2right 7 місяців тому

    How do you set the flow rate no one wants to tell you how to do it.

    • @griffithsheating
      @griffithsheating  7 місяців тому +1

      Ufh flow rate is set by the manifold flow setters and the rads can be set with either a flow balancer or flow setting rad valves. Or you could use what’s called a stad valve

    • @Allegedly2right
      @Allegedly2right 7 місяців тому

      @@griffithsheating Cheers it is a Grant Aerona with a low loss header only 9 rads the T1-T2 is only about 2-3 nightmare.

    • @griffithsheating
      @griffithsheating  7 місяців тому

      @@Allegedly2right bare in mind that your dt will only be at design (5, 7, 10 or whatever) when you are on a design day which is a day below zero degrees outside. Anything more than that the dt will narrow.

    • @gerardfry4876
      @gerardfry4876 4 місяці тому

      I’m getting to much flow through from heat pump to my diverter on my arotherm and it makes a chudder when switching. Any suggestions to help?

  • @stixstonesinvestors5413
    @stixstonesinvestors5413 9 місяців тому

    Lovely. Open loop 🔥🔥🔥

  • @gerardfry4876
    @gerardfry4876 9 місяців тому

    Are you bending the UFH down to lower temp or just running 45oc with rads?

    • @griffithsheating
      @griffithsheating  9 місяців тому +1

      No blending. Just letting the heat pump do its thing unrestricted.

    • @gerardfry4876
      @gerardfry4876 9 місяців тому

      @@griffithsheating it makes sense, less expensive mixer station/pumps better savings. Is this your standard going forward then? Do you just run one stat for the whole house?

    • @griffithsheating
      @griffithsheating  9 місяців тому +1

      @@gerardfry4876 there is a wireless Vaillant senso comfort controlling it so you can either run it as a room stat or just off a curve with no room influence. Not sure how the customer will want to run it yet.

    • @gerardfry4876
      @gerardfry4876 9 місяців тому

      And if the pump on the HP can’t supply the index circuit with enough flow, would you fit a buffer then?

    • @griffithsheating
      @griffithsheating  9 місяців тому

      @@gerardfry4876 yes if my calculations are wrong I’d have to convert the volumiser to a buffer and add another pump.

  • @androleum
    @androleum 10 місяців тому

    Which controller devices are used here?

  • @Foss1985
    @Foss1985 9 місяців тому

    Nice install! How do you find these compared with the Vitocals?

    • @griffithsheating
      @griffithsheating  9 місяців тому +2

      Vaillant is better priced, easier to get hold of, easier to quote for, better manufacturer support, no need for indoor unit so fits in a smaller space and vaillant seem to know Their product better than Viessmann BUT the Viessmann controls on the 150a are superior to the Vaillant.

  • @AdamSkelly-vz3ih
    @AdamSkelly-vz3ih 8 місяців тому

    Hello mate - nice install. What is the lagging internally with the " socks " for over the fittings. Only ever used Primary pro or Pump houses own products but this looks great

    • @griffithsheating
      @griffithsheating  8 місяців тому +1

      It’s just Armaflex taped with class zero tape 👍🏻

  • @Apexplumber
    @Apexplumber 7 місяців тому

    Good job

  • @jacbisgood2221
    @jacbisgood2221 10 місяців тому

    We need to talk about K̶e̶v̶i̶n̶ Viessmann

    • @griffithsheating
      @griffithsheating  10 місяців тому +3

      Let's just say we had a disagreement about the part L building regs 😄 They claimed all heating systems have to be designed to 45 degrees and I called 🐂💩 and 7 months later I'm still waiting for a BUS grant payment. I guess I'm not cool enough to join their club.

    • @jacbisgood2221
      @jacbisgood2221 10 місяців тому

      @@griffithsheating what did you design to? Sounds out of order to me

    • @griffithsheating
      @griffithsheating  10 місяців тому

      @@jacbisgood2221 designed to 55 due to rad space available but that's knowing the home owner is doing a load of additional insulation in the roof space and floor so will end up around 45/50 mark. It actually was finally signed off and grant paid today as it happens 😎