Live Troubleshooting Video Of A Diesel Generator.

Поділитися
Вставка
  • Опубліковано 22 лип 2024
  • Live Emergency Maintenance of a diesel generator.This generator is 60kva PowerLink generator with Perkins engine and LEROY-SOMER alternator. It also has a control panel named PLC-920. It can carry out functions including pre-alarm,warning & electrical trip,fail monitoring and control etc.It has some following features:
    -Parameter configuration via RS-232 serial communication
    -Log last 50 events & alarm information with measured values
    -Statistics records
    -Remote start/stop.
    -Speed sensing from alternator voltage
    -Configurable 3 inputs and 6 outputs
    -ATS and Engine control
    -Adjustable start ,load and stop timers and many more.
    This generator has dependency with lift. So it was to rectify the issue within very short time. In this video it has been mentioned the technique of quick solution . How to identify the real reason of malfunction within a very short time , how to apply logic to get a quick solution , these have been also mentioned. However as it was emergency case , team moved to short cut way . If any one is not highly expert , he should not follow this way . He should follow standard procedure . In this video details of any option have been skipped . Hope we will come with details of a diesel generator very soon.Till then have nice journey of life.Thanks
  • Наука та технологія

КОМЕНТАРІ • 72

  • @ramalingeswararaobhavaraju5813
    @ramalingeswararaobhavaraju5813 6 років тому +1

    Namaskar to TECHNICANY and thank you so much sir for generator troubleshooting video.

    • @technicany
      @technicany  3 роки тому

      You are most welcome brother....

  • @yaredmuluabay2066
    @yaredmuluabay2066 2 роки тому

    thank you sir for yr illustrative teaching.

  • @DIlic-iz9tx
    @DIlic-iz9tx 2 роки тому

    _Excellent generator._

  • @jalalkhan-om7iz
    @jalalkhan-om7iz 8 місяців тому

    thanks

  • @hussienabduro9515
    @hussienabduro9515 2 роки тому

    Thanks
    But would you explain megnetic pickup sensor

  • @miketm8200
    @miketm8200 Рік тому

    I have the same fuel pump and not pumping on injectors. The solenoid valve is fine. No air on the fuel lines. Any idea?

  • @elwpoqerwituyvnu
    @elwpoqerwituyvnu 2 роки тому

    Which pump is installed? I have a problem CAT / Olympian GEP44 starts and stalls after a while. Fault code 190

    • @technicany
      @technicany  2 роки тому

      Please see the user manual of that generstor.May be it is ECM related.Would you please reconnect the ECM connection?

  • @exclusivesafar
    @exclusivesafar 3 роки тому +1

    Very easy solution this problem only fuel problem

    • @technicany
      @technicany  3 роки тому

      thanks....yes it about fuel problem....you know problem is either simple or critical we must solve. This is called troubleshooting.

  • @cagmito76
    @cagmito76 5 років тому

    What sensors ? did you mention , thanks .

    • @technicany
      @technicany  3 роки тому

      Thanks bro....would you please mention the specific point?

  • @busayoolatundebukunmi8129
    @busayoolatundebukunmi8129 4 роки тому +2

    What may caused hard starting on 20kva perkins generator?

    • @technicany
      @technicany  3 роки тому

      thanks.....would you please simplify your word ?

  • @suraj6988
    @suraj6988 7 років тому +1

    could you send me the process of installatin of new generator on field with load observation and earthing process

    • @technicany
      @technicany  3 роки тому

      Thanks for your comments....i will try bro....

  • @dereseshumi9171
    @dereseshumi9171 2 роки тому +1

    I have pekins generator no start canbus error

    • @technicany
      @technicany  2 роки тому

      CAN refers Controller Network Area.Please check the connections of control module. As messages come from different parameters, so there may have connection problem.

  • @user-kd8it3qg9i
    @user-kd8it3qg9i Рік тому

    الف الف شكر وتحيه لحضرتك بعض طلمبات الديزل فيها5او6وايرماذاتدعم

  • @Leonardovaldueza1971
    @Leonardovaldueza1971 4 роки тому +1

    What do call this part , you supply dc voltages

    • @technicany
      @technicany  3 роки тому

      thanks for your comment.....12v dc voltage has been applied for extracting air from fuel.You know this can be done by manual hand pump..but this generator has no manual hand pump.Also this can be done by another way by disclosing cranking relay which is located in control module box..So it's your wish which process you will follow...Thanks again brother...Also sorry for late response....as i was not connected with youtube for a long run....

  • @Hunter684357666
    @Hunter684357666 7 років тому

    Hello,what was the reason?

    • @technicany
      @technicany  3 роки тому

      thanks for your response...it is due to presence of air in fuel line.

  • @bharatchauhan5505
    @bharatchauhan5505 6 років тому +1

    how to remove water from this genrator please answer me i need help urgent

    • @technicany
      @technicany  3 роки тому

      i am sorry ....i am late as i was busy with my other task.... i uploaded a video which is directly related to your topic...pls find it from my channel.

  • @essamyouness
    @essamyouness 7 років тому +3

    how i can fix problem RPM

    • @technicany
      @technicany  7 років тому

      +Essam Youness Most of the cases RPM issue raises due to malfunctioning of fuel system. So check fuel line , fuel filter,fuel quality etc. Observe the result and it may solve RPM issue otherwise you have to move for hard step. Also would you please mention the details of RPM issue ?

    • @azharpathan6651
      @azharpathan6651 5 років тому

      TECHNICANY one k-19 Cummins engine have hunting rpm between 800 to 1600.. we was check all fuel line, change fuel water separator and check actuator also.. everything is ok.. but hunting issue not solved

    • @rawanjalloul4430
      @rawanjalloul4430 4 роки тому

      Then try to check the Diesel Injection Pump. Particularly the governor weights and their retainer.

  • @Hamid-ei2hg
    @Hamid-ei2hg Рік тому

    Brother can I contact you? I'm working in engine like this and it shut down after few minutes

    • @technicany
      @technicany  Рік тому

      It seems having problem in fuel system. If generator contains digital control module, then see the alarm.Have any alarm in control module?

  • @babariqbal2272
    @babariqbal2272 3 роки тому +1

    Water body se oil main water mix hota hai k nae

    • @technicany
      @technicany  3 роки тому

      i am sorry brother...i can't know hindi....i will try to translate ...and try to response against your comment ...

  • @akliluzawugicha1375
    @akliluzawugicha1375 6 років тому

    how to fix stop failure alarm in Pramac Diesel generator

    • @gandalfmarshal2867
      @gandalfmarshal2867 3 роки тому

      Trouble shooting in Cummins generator
      ua-cam.com/video/tucj4sotPYU-/v-deo.html "Excessive Accelecation Smoke
      "
      ua-cam.com/video/9rzGDjmaN8c-/v-deo.html "Engine Misses
      "
      ua-cam.com/video/RbDJXqep9ak-/v-deo.html "Hard Start or Failure to start"
      ua-cam.com/video/7kEEmb5dBNM-/v-deo.html "Excessive Smoke Under Load"
      ua-cam.com/video/RlslQ_Uai2c-/v-deo.html "Black Smoke at Idle"
      ua-cam.com/video/ZoPMzy4lixQ-/v-deo.html "White Smoke at Idle"

  • @ahmads40405
    @ahmads40405 6 років тому +2

    How i can fix low voltage

  • @exclusivesafar
    @exclusivesafar 2 роки тому +1

    Nice nice video

  • @dereseshumi9171
    @dereseshumi9171 2 роки тому +1

    Hi

  • @aijazshaikh7621
    @aijazshaikh7621 5 років тому

    Generator start but stop after few seconds (disel gen)

    • @technicany
      @technicany  3 роки тому

      Thanks for your comment.....it is due to many reasons....it needs to observe in practical ....or if you provide some information..Then it will be easy to find out the reason behind the problem.

  • @md.ansari6422
    @md.ansari6422 6 років тому +1

    please seing in hindi

  • @1972hattrick
    @1972hattrick 5 років тому

    A valve waa off?

    • @technicany
      @technicany  3 роки тому

      bro...please specify ...

    • @1972hattrick
      @1972hattrick 3 роки тому +1

      @@technicany there was a yellow valve in the off position. The first time I saw it, it looked like it was connected to a fuel tank hose. I just rewatched it and I'm pretty sure that was for the oil pan.

    • @technicany
      @technicany  3 роки тому

      thanks for your comment bro...yes that is for oil pan...it is not connected to fuel line....

  • @sheikhtuhin6280
    @sheikhtuhin6280 3 роки тому +1

    I am working dhaka Bangladesh diesel generators

    • @technicany
      @technicany  3 роки тому

      Welcome brother..................

  • @jaleelbhnam2331
    @jaleelbhnam2331 7 років тому +1

    fre nels lpLas wo hlf som thing strange voice But Geno Maco any Drolm no problem

    • @technicany
      @technicany  7 років тому

      +Jaleel Bhnam , would you please explain your word? Sorry i could not understand .

  • @exclusivesafar
    @exclusivesafar 3 роки тому +1

    I am generator mechanic

  • @dgc7321
    @dgc7321 5 років тому +1

    SPEAK ENGLISH!!!!!!!

  • @sobaransharma5559
    @sobaransharma5559 5 років тому

    Tu kuch nahì bata payega

    • @md.sahedkhan7234
      @md.sahedkhan7234 3 роки тому +1

      আসসালামু আলাইকুম

    • @md.sahedkhan7234
      @md.sahedkhan7234 3 роки тому +1

      হাবিব বাই বাই

    • @technicany
      @technicany  3 роки тому

      bro...please specify so that i can make you clear...thanks