HOW TO FIX BATTERY FAULT IN FIRE ALARM PANEL ?

Поділитися
Вставка
  • Опубліковано 18 жов 2024

КОМЕНТАРІ • 29

  • @niloyu105
    @niloyu105 2 роки тому +1

    Watching from Al Khafji Saudi Arabia

  • @simonegelormino3277
    @simonegelormino3277 2 роки тому

    Nice work Elmer! I rwally enjoy your videos!Waiting for a video on fault finding for common faults found on Ewis panels, wip phones, break glass, speaker line etc😉

  • @niloyu105
    @niloyu105 2 роки тому

    😂😂😂 masipag Ngayon ang Ads start and end video 20sec. Completed support Filipino Vlogger especially Ads 😂😂😂

  • @ericchoi1610
    @ericchoi1610 10 місяців тому

    thank you for the video. How did you find a magnet door was the problem? is it common failure or based on your experience? if you didn't know, how would you troubleshoot in general?

    • @fireprotectionguy7943
      @fireprotectionguy7943  10 місяців тому

      Fire system auto battery test once a day (old system) or once a week (new model). For old system, it's an hour test. Any magnet or external power devices cause the battery to depleted earlier. In this site, it's only the magnet that causing it. From the day I introduced a new power source for the magnet, the problem never re-occur.

  • @niloyu105
    @niloyu105 2 роки тому

    Welcome back hehe! Watching from Al Khafji Saudi Arabia

    • @fireprotectionguy7943
      @fireprotectionguy7943  2 роки тому

      My PC Motherboard was off. Under warranty, so I sent it back to the supplier. I can not wait for the repair so I bought another PC. Thnxs Ingat.

  • @maskarangvlogger7196
    @maskarangvlogger7196 Рік тому

    Bago nyo pong taga suporta sir.

  • @o_z_b
    @o_z_b Рік тому

    Thank you so much for this video

  • @niloyu105
    @niloyu105 2 роки тому

    Ah! Naka panood din ako Ads 😂😂😂 30sec. Ads completed keep watching and support from Al Khafji Saudi Arabia...

    • @fireprotectionguy7943
      @fireprotectionguy7943  2 роки тому +1

      Daya...pinagkakakitaan na nila ang video ko.

    • @niloyu105
      @niloyu105 2 роки тому

      @@fireprotectionguy7943 Hehehe! Oks lang yun Sir Elmer alam ko naman po naglilibang ka nalang sa buhay 😂😂😂

    • @fireprotectionguy7943
      @fireprotectionguy7943  2 роки тому

      @@niloyu105 ... tama ka dyan...dadagdag lang sa tax na babayaran ko yan.

  • @roderickbalolong6795
    @roderickbalolong6795 5 місяців тому

    Hi Sir. Elmer, maybe during the design stage the magnetic lock current was not included in the battery calculation.

    • @fireprotectionguy7943
      @fireprotectionguy7943  5 місяців тому

      True. But magnets must not be included in the normal power supply of the fire system. It should have it's separate power supply. Either with back-up batteries or not.

  • @workonmyranger6336
    @workonmyranger6336 2 роки тому

    I like your videos

  • @stevehunter532
    @stevehunter532 Рік тому

    Does the system need to be shut down to replace the batteries? Or can be done while running on mains power?

  • @maskarangvlogger7196
    @maskarangvlogger7196 Рік тому

    Bagong palit din po ang battery naun eh..slamat po advance

  • @crisdeorbz8986
    @crisdeorbz8986 Рік тому

    Good day sir may video po ba kayo procedure replace battery ng consilium fire alarm panel?

    • @fireprotectionguy7943
      @fireprotectionguy7943  Рік тому

      Replacing batteries are very basic. When replacing, make sure you have your normal power "ON". Once you removed one terminal, it will fault buzz and just acknowledge it to clear the noise. Just do make sure you got the correct polarity.

    • @crisdeorbz8986
      @crisdeorbz8986 Рік тому

      @@fireprotectionguy7943 ok sir no need to switch off the main power, only disconnect the battery wire

    • @fireprotectionguy7943
      @fireprotectionguy7943  Рік тому

      @@crisdeorbz8986 ..correct. Never remove a battery with MAIN POWER OFF cause your battery is the back-up power source.

  • @maskarangvlogger7196
    @maskarangvlogger7196 Рік тому

    Sir,itanong ko Lang po Kung ano dahilan nang battery deplited?simplex po addressable

    • @fireprotectionguy7943
      @fireprotectionguy7943  Рік тому

      Flat batteries. Mostly cause of system that is running on batteries most of the time due to power blackout. Once a battery reached it's low voltage threshold - it's hard to charge using the fire alarm system battery charger. Best to charge it using an external charger. Another is, the system is in auto battery test every day. Once a week is okay for 30 mins only based on program setting. If it failed in 30 mins, your system requirement is bigger than the battery can supply. That's the time you sort out which equipment should not be included in the normal battery test and should be separated from the fire system. These are magnet door holders mostly.

  • @carlh4279
    @carlh4279 2 роки тому +1

    For sure the magnets should have a dedicated power supply.

  • @francisaguinaldo968
    @francisaguinaldo968 Рік тому

    Hi! How to fix psu fault in zeta primier quatro? Thanks

    • @fireprotectionguy7943
      @fireprotectionguy7943  Рік тому

      I am not familiar with zeta. But the trick is all fire supply fault are the same - Battery Missing, Battery Fault, Blown Fuse, Battey Flat ( just replace it!), Low Battery Voltage, No Power Output or Input, Output voltage is too low ( Normally output is between 26.1 - 27.4 volts DC). Good Luck