EMERGENCY Job Means One Thing (Earth Rods) - Electricians Life Uk

Поділитися
Вставка
  • Опубліковано 2 бер 2023
  • Check Out Tradify
    (USE CODE “JRC50” FOR 50% OF FIRST 3 MONTHS:
    bit.ly/3KIBMIs
    Thanks for watching, if your enjoying our content as much as were enjoying making it then please consider subscribing to the channel and smash the bell icon so you dont miss future uploads.
    Join this channel to get access to perks:
    / @jrcelectrical
  • Розваги

КОМЕНТАРІ • 212

  • @stuartjones2242
    @stuartjones2242 Рік тому +11

    Hi jack , just a bit of advice mate , A lot of sparks make the same mistake with outside earth rods, The outside earth rod needs a bigger and better sealed box cover to stop corrosion at terminals, this is where most faults happen , the original box and new one fitted are to small with poor seals, keep your chin up regarding work it has been slow start but it is starting to pick up 😃😃👍👍

    • @JRCElectrical
      @JRCElectrical  Рік тому +7

      Thank you good sir, rather than a crap comment slating it that’s an awesome comment giving advice so thank you, yeah it’s picking up now to be fair it’s just been really crap start 👍👍 cheers dude

  • @metrotechguru5863
    @metrotechguru5863 Рік тому +13

    Brilliant, Jack. No need to apologize for a shorter vid. Sorry to hear that business is down. Hang in there mate and things will come back up again (soon, I hope).

    • @JRCElectrical
      @JRCElectrical  Рік тому

      Cheers dude, it’s picking up to be fair just been slow the last few weeks

  • @HeathenGeek
    @HeathenGeek Рік тому +3

    take the camera round to the roofing site and show all the sparkies what real hard work looks like 😁

    • @JRCElectrical
      @JRCElectrical  Рік тому

      🥱 you are right tho I did it for about 2 years and it was GRAFT, not so much now with all the fancy conveyors and things I see but yeah it’s defo graft 😂

  • @martin54123
    @martin54123 Рік тому +6

    I have the Linian SDS+ driver attachment too, plus the one use drill bit screw on that goes on the end of the rod if it's rocky, brilliant kit and as you say makes it easier.👍👍👍

    • @JRCElectrical
      @JRCElectrical  Рік тому +1

      What a fantastic invention 👏

    • @stringlarson1247
      @stringlarson1247 9 місяців тому +1

      I gotta get one of those. Here in 'the states' there are a lot of Al rods with no threading. Around here, they come in 6' lengths and I grind/file a point on the end.
      You kids in the UK (EU?) have some pretty interesting kit.

  • @eddtheduck
    @eddtheduck Рік тому +4

    I would personally put the earth cable in flexi conduit then a wiska box on the outside wall, just to protect the cable

    • @JRCElectrical
      @JRCElectrical  Рік тому +1

      Would have been better to be fair, it’s out the way there anyway so won’t get damaged, protection from UV would have been good tho

    • @markrainford1219
      @markrainford1219 2 місяці тому +1

      @@JRCElectrical In the US the wire would be bare.

    • @JRCElectrical
      @JRCElectrical  2 місяці тому

      @@markrainford1219 US 👏 legend

  • @marktaylor7288
    @marktaylor7288 Рік тому +4

    Really interesting for a sparkie like myself who hasn’t done lots with earth rods, not common. Loved the bit to drill the rods in

    • @JRCElectrical
      @JRCElectrical  Рік тому +1

      Thanks dude, yeah there’s loads round here but any closer to a city and there rare 😂

  • @appliancetesting2021
    @appliancetesting2021 Рік тому +1

    Great video good to see something on TT rods 👍

  • @dwmdinamo123
    @dwmdinamo123 Рік тому +2

    Solid video, learned a few things👌

  • @ayresomemaintenance4627
    @ayresomemaintenance4627 Рік тому +2

    Another great video Jack 🙌🏻

  • @garylatto4191
    @garylatto4191 Рік тому +2

    Enjoy the quite time mate , makes up for when it's crazy busy, good interesting video mate 🤙

  • @johnmcfadden7418
    @johnmcfadden7418 Рік тому +2

    Nice Video Jack that Linian tool is a must thx

    • @JRCElectrical
      @JRCElectrical  Рік тому +1

      Thank you sir, yeah it really was awesome

  • @Anthony-mz8ci
    @Anthony-mz8ci Рік тому +1

    Thanks Jack, interesting bit of fault finding.

  • @StreamFeeds
    @StreamFeeds Рік тому +2

    Big up JRC! BIG up yourself! Great video, Jack.

  • @ElectricianTV
    @ElectricianTV Рік тому +3

    What great video really enjoyed that? That sds drillbit does look handy. Cheers Jack keep up the good work

    • @JRCElectrical
      @JRCElectrical  Рік тому +1

      Cheers mate, yeah drill bit saved LOADS of time

  • @tincanpete
    @tincanpete Рік тому +1

    Interesting vid thanks!

  • @cranefamily
    @cranefamily Рік тому +1

    Great vid mate thanks 👍🏻

  • @thomasnoonan4171
    @thomasnoonan4171 Рік тому +2

    Big up urself Jack, loving the content keep it up brother 🤙🤙

  • @Mike_5
    @Mike_5 Рік тому +2

    Quality vids like this Pal will grow your business for sure

  • @mikeenglish1492
    @mikeenglish1492 Рік тому +1

    That was interesting, not boring at all 👍

  • @ghspaelectricalservices9296
    @ghspaelectricalservices9296 Рік тому +1

    Nice mate, glad to see it’s not just my makita batteries thay go flat quick lol

    • @JRCElectrical
      @JRCElectrical  Рік тому +1

      Yeah there crap the last few years everything they bring out seems to be made of chocolate 😂

  • @richyc2397
    @richyc2397 Рік тому +2

    BIG up lennels gran. I hope she’s having a wonderful Tuesday morn, as I hope you are Jack and Scotty. I know I am ☝️❤️

    • @JRCElectrical
      @JRCElectrical  Рік тому

      Big up you sir, we’re all good thanks bro, Scott’s has left now tho he’s a roofer now

  • @train4905
    @train4905 Рік тому +1

    Exellent job sir

  • @hulkpoundstack5426
    @hulkpoundstack5426 Рік тому +1

    THESE NUTS!!😂😂 - Yes, you had to. Legend, great vid. I had to hit the subscribe button.👍👍

  • @lukeblake8849
    @lukeblake8849 Рік тому +1

    Good video first time watching 👌🏽

  • @BrandonTonner
    @BrandonTonner Рік тому +3

    We’re just up the road in Coventry mate and it’s the quietest I’ve ever been since I set up in 2019. Hoping as the end of tax year approaches work picks up again 🤞🏼

    • @JRCElectrical
      @JRCElectrical  Рік тому

      Yeah it’s a bit crap, picking up now tho so hopefully we’re on the up again

  • @Chris_In_Texas
    @Chris_In_Texas Рік тому +4

    8:14 quick question here, but it looks silver under there, are those solid copper rods or copper clad steel rods? Might just be the camera angle here. Here in the USA we are required for a minimum of two 8' rods that have to be 6' apart. You can get by with one if reading is less than 25 ohms, but most just put two in. Also the wire can not be cut between rods and has to be continuous. We also use #6 (16mm2) but solid, typically bare and not stranded to prevent corrosion between the strands on the copper wire over time. There are some guys around that like stranded because its easier to run.
    We also use UFER grounds on newer construction that is bonded to the rebar in the foundation and creates a grounding plane under the entire house in addition to the rods, and potentially any copper water lines, however with many new homes plumbed in PEX and their water meters to the house using POLY, there is nothing to ground to there.
    Keep up the good work man! 🤠👍

    • @JRCElectrical
      @JRCElectrical  Рік тому

      Wow you lot go all out over there, yeah the rods are usually coated in copper I believe.
      25 ohms is a rediculously low reading that would be awesome,
      Thanks for watching and commenting dude

  • @johnavery15
    @johnavery15 Рік тому +2

    TLC and Screwfix sell a bolt that has the same thread as the earth rod. You put the earth rod - earth rod connector on and screw in the bolt. I bought an inch? socket from a car boot sale and an SDS to socket adapter from eBay to do what your Linian one does. I didn’t know it existed. That’s why your vids are educational! Noice 😊

    • @JRCElectrical
      @JRCElectrical  Рік тому

      Yeah I’ve used the bolts before and just smashed them with the hammer 😂😂 Thankyou sir

    • @johnavery15
      @johnavery15 Рік тому

      @@JRCElectrical That works too!

  • @mb-electricalservices
    @mb-electricalservices Рік тому +2

    New sub mate. Nothing wrong with a short video at all! I'm a sole trader and, like you, have my quiet times and busy times but you just have to muddle through and it all seems to work out in the end. Hope work picks up for you soon!

    • @JRCElectrical
      @JRCElectrical  Рік тому

      Ahhh welcome sir, thanks for the comment and yeah I hope it picks up, we have to ride the waves of busy and not, this time has just been crazy tho, from the mad rush the last 2 years

  • @smiffysmiffy123
    @smiffysmiffy123 Рік тому +1

    Good video, hate spashing rods down, drainage, mains water pipes aswell.

    • @JRCElectrical
      @JRCElectrical  Рік тому +1

      😬 always a brown pants moment 😂😂

  • @whatwhenwherewhyhow9094
    @whatwhenwherewhyhow9094 5 місяців тому +1

    Great job, nice to see people using dedicated tools etc. If I had to criticise the obvious would be the so called earth box, I'd just the weather proof ground box and like the other guy said put some form of conduit with a bend dug in to prevent water egress into said earthbox. That being said I understand on an emergency you have to deal with what you have. My second point would be that pointless crimping tool, while ideal for doing car audio crimps it doesn't give enough crushing power to those solid lugs, SWA do a reasonably priced kit with every lug and hole size you'll need as we only now use metal clad consumer units its worth having, the kit comes with a crimp tool that looks like a set of bolt croppers and has 10x the force of those little crimps. In essence you'll get a far better reading on your Ze if it has a more solid connection. But still great video 👍🏼

    • @JRCElectrical
      @JRCElectrical  5 місяців тому

      All fair points sir Thankyou for your comment, I agree about crimpers but the ratety I use them it doesn’t warrant buying expensive ones, these ones do a tight crimp so will do for me.
      Cheers mate appreciate it

  • @peterprice8393
    @peterprice8393 8 місяців тому +1

    We use the conductive compound that we use when fitting large cable lugs to help with wet corrosion on the rod connector .🤔

    • @JRCElectrical
      @JRCElectrical  8 місяців тому

      Ahhh never seen this, I have only done a few to be fair

  • @ForTheBirbs
    @ForTheBirbs Рік тому +2

    Hey Jack, thanks for another video. So sorry to hear your work has been down, but hopefully the quotes come through ok. Earth rods are the normal thing here in Aus as we use the Multiple Earth Neutral (MEN) system. I gather this is called PME in the UK. The neutral and earth blocks in the consumer unit are strapped together. It is typical here for the supply authority meter etc to be in the same cabinet as the fuseboard. The neutral lines are also earthed at supply and transmission poles. I know I've simplified the description, but...

    • @JRCElectrical
      @JRCElectrical  Рік тому

      Hello sir Jim, yeah it sounds the same as PME most properties here are either PME or TNS where the earth is strapped onto the outer of the incomming cable, most TT is gone now as they are earthing the neutral at the pilon where they can and upgrading them

  • @ashleyrogers7192
    @ashleyrogers7192 Рік тому +1

    Big up jrc yeah

  • @StuartTownsend.
    @StuartTownsend. Рік тому +2

    Up the boys! Keep watching and keep learning every episode no matter no long it is, big up ya self ❤

    • @JRCElectrical
      @JRCElectrical  Рік тому +1

      Big up and Thankyou for your support u legend

  • @padders1068
    @padders1068 Рік тому +2

    NOOOIIICCEEEE! Big up yourself Jack! Now I know why earth rods have threads at each end, as you eloquently explained it's so you can join them together. Never thought of that. 🙂

  • @Bespokeelectrics
    @Bespokeelectrics Рік тому +1

    Never used the adaptor, but may well pick one up!

  • @ted5hhh1241
    @ted5hhh1241 Рік тому +2

    You could’ve paralleled up with the old rod to get an even lower reading 👍

    • @JRCElectrical
      @JRCElectrical  Рік тому +1

      There has to be a certain distance between rods and the land wasn’t big enough to achieve it 😞

  • @samparsons5580
    @samparsons5580 Рік тому +2

    Keep it up bud. Chin up and keep cracking on. Honest hard working trades always come up trumps and you’re deffo one of those. Keep plugging away and letting your hard work and personality shine though. Oh and….’RUN THE TIIIING’ 😄

    • @JRCElectrical
      @JRCElectrical  Рік тому

      Cheers bro that’s an awesome comment I appreciate that ❤️ big up

  • @adriatikkrasniqi1453
    @adriatikkrasniqi1453 Рік тому +1

    That was interesting great content.,

  • @loriAlessiroberts118
    @loriAlessiroberts118 7 місяців тому +2

    Just had a scary experience where the box on the utility pole energised the lead on my supply cable which energised my earth rod, water pipes and all metal in my home! Got electric shock! Box replaced and my cable to boundary. Box was one hundred years old!

    • @JRCElectrical
      @JRCElectrical  7 місяців тому

      Did that really just happen 😮

    • @loriAlessiroberts118
      @loriAlessiroberts118 7 місяців тому +1

      @@JRCElectrical Last week and the next day two supervisors and electricians arrived and told me the lineman who repaired the box and cable left me with a live neutral (whatever that means?). They said he was bad and shook their heads. I'm now terrified to touch anything even though it's been fixed.

    • @JRCElectrical
      @JRCElectrical  7 місяців тому +1

      @@loriAlessiroberts118 wow that’s not good at all 😮 if your worried you could always get an electrician you can trust to test it for you just for peace of mind

    • @loriAlessiroberts118
      @loriAlessiroberts118 7 місяців тому +1

      @@JRCElectrical What is a live neutral? Please excuse my ignorance😕

    • @JRCElectrical
      @JRCElectrical  7 місяців тому +2

      @@loriAlessiroberts118 so the live power has gone down the wrong cable into the property, all the switches switch off the live, so with it going down the neutral there’s a chance of shock

  • @dave0smeg
    @dave0smeg 10 місяців тому +1

    8 FEET! 😮 I worked with a spark on a site that ManWeb insisted on the spark installing a 1m earth rod. The location they wanted it was inside the building. After 2 hours of hammering away with a lump hammer, the rod had only gone in 13 inches. Must have hit the foundations and not gone any further.

    • @JRCElectrical
      @JRCElectrical  10 місяців тому

      That’s not so good 😂😂 I’ve heard some right horror stories in the past, lucky this one wasn’t too bad

  • @stevedebbiemoore
    @stevedebbiemoore Рік тому +1

    BG gas engineer's have a socket and see that just gives a range, below 1 above 1 but the white goods engineers have a Megger MF1720 and enough knowledge to make an assessment of the eli based in the earthing arrangement.

    • @JRCElectrical
      @JRCElectrical  Рік тому +1

      Ahhh ok yeah that defo wouldn’t have picked it up then 😂😂

  • @Arachnoid_of_the_underverse
    @Arachnoid_of_the_underverse Рік тому +2

    I was going to say if you dont have an sds tool Ive seen sockets used on a hammer drill in videos before now. Nice tidy job, keep a positive and well earthed outlook 👍

    • @JRCElectrical
      @JRCElectrical  Рік тому

      Never ever thought of this that’s an awesome idea, this tool is mint tho 😂 if someone doesn’t have sds socket adaptor

  • @stephencarter6634
    @stephencarter6634 Рік тому +1

    Big up the channel 👍👍👍😁

  • @LeedsElectrician
    @LeedsElectrician 8 місяців тому +1

    Would defo use the larger earth inspection pits if using outside, i did one on friday but managed to get it under the hall in a void and luckily got 21.5ohm it was to supliment a TNS that was a bit high, Thing i need to get one of these sds adaptors so i can stop using a hammer

    • @JRCElectrical
      @JRCElectrical  8 місяців тому

      Hammer is a nightmare isn’t it 😂 and then the rod gets smashed up on the end 😬 Jesus that was a high reading if even with a rod it was 21.5ohm
      If we get high readings on tns or cs we report it to western power and they come and sort it

  • @TheMartyMarf
    @TheMartyMarf Рік тому +2

    Nice shorter one Jack. Stick a few more rods in to reach Oz 😂 Big up yourself

    • @JRCElectrical
      @JRCElectrical  Рік тому

      Few more Martyn I would have been in China I recon 😂😂😂😂

  • @tommahoney7940
    @tommahoney7940 Рік тому +1

    Mr Bundy wants his Bosch SDS back to put back with his collection ( Got Given), hope the work picks up m8,enjoy the vlogs.

    • @JRCElectrical
      @JRCElectrical  Рік тому +1

      😂😂😂 that drill was given to me by Bosch to be fair you can apply to test there tools and they sent that a couple years ago it’s a beast

  • @philipoakley5498
    @philipoakley5498 Рік тому +1

    More expensive, but the Condudisc may be an option in some locations, especially industrial.

    • @JRCElectrical
      @JRCElectrical  Рік тому

      Ooo I shall have a look

    • @philipoakley5498
      @philipoakley5498 Рік тому

      @@JRCElectrical ua-cam.com/video/tYcXE9W2AKQ/v-deo.html for a John Ward review.

  • @pikricky
    @pikricky Рік тому +3

    Nothing boring about it Jack,it's good to get different content in video's,variety is the spice of life as they say

  • @Ant86744
    @Ant86744 Рік тому +2

    I have only been required to install only a handful of earth rods over the years as not as common in my area. if only the that sd adapter was around then it would have made the job so much easier especially in clay ground.

    • @JRCElectrical
      @JRCElectrical  Рік тому

      Yeh a few people have said there’s not many there way either, there’s thousands here 😂

    • @Ant86744
      @Ant86744 Рік тому +1

      Need to look at heading to Shropshire/ Telford way on then 😂as a lot of the old over heads are being replaced with pme etc

    • @JRCElectrical
      @JRCElectrical  Рік тому

      @@Ant86744 it’s the same here slowly 😂😂

  • @freezefoot
    @freezefoot Рік тому +3

    Very helpful video. How far do you normally step out TT rod from building to avoid foundations? Thanks again. New subscriber.

    • @JRCElectrical
      @JRCElectrical  Рік тому +2

      Welcome Sir, we normally have a rough guide by the rod that was previously in, but normally a couple of feet and it’s been clear in the past 👍

  • @eded6163
    @eded6163 Рік тому +1

    good job, as far as i know if ze much higher then that,hou may not achieve maximum permited zs on some circuits even if it's Rcd protected

    • @JRCElectrical
      @JRCElectrical  Рік тому +1

      I thought all max zs if it’s protected is 1667, I could be wrong tho 😂

    • @eded6163
      @eded6163 Рік тому +2

      @JRC Electrical yes, you're correct in this case up to 1667 ohm is accepted 😁

    • @JRCElectrical
      @JRCElectrical  Рік тому

      @@eded6163 miles under then 😎 😂😂😂

  • @peterigrenyi9176
    @peterigrenyi9176 7 місяців тому +1

    Lets remember we dont need 16mm Main earth on TT system! Saw company C2 6mm main earth to Rod!

    • @JRCElectrical
      @JRCElectrical  7 місяців тому

      You don’t but If I was changing it I would defo use 16mm

    • @peterigrenyi9176
      @peterigrenyi9176 7 місяців тому +1

      Just a tad o waste on longer runs sticking 16mm in. Also, a tip use your R2 lead to test the rod resistance before u botherwith clamp at the top. Speeds it up if u need more rods.

  • @AaronMall33
    @AaronMall33 Рік тому +1

    Big up

  • @onewheelnut
    @onewheelnut Рік тому +3

    Great content as usual, thought you might have left the polythene sleave on the rods to stop corrosion 😂

    • @JRCElectrical
      @JRCElectrical  Рік тому

      Cheers dude, I would have to be fair but I needed a better reading not worse 😂😂

  • @pauljames4498
    @pauljames4498 Рік тому +1

    British gas have a plug tester. They did it in my sisters house

    • @JRCElectrical
      @JRCElectrical  Рік тому

      Does it test zs tho? I’ve not seen one, they normaly just have socket tester with leds on

  • @calvinmcmahon2714
    @calvinmcmahon2714 7 місяців тому +1

    Should have contacted the DNO pal the service could be PME now and saved you a chew on good job though

    • @JRCElectrical
      @JRCElectrical  7 місяців тому

      I check the pilons whenever I get a job like this and they have labelled the ones that have been upgraded
      This one wasn’t labelled so didn’t do it

    • @calvinmcmahon2714
      @calvinmcmahon2714 7 місяців тому +1

      @@JRCElectrical dno,s pain in the arse pal they subby that much out and they don't give a - uck makes our job that bit tougher when it comes to mains earthing

    • @JRCElectrical
      @JRCElectrical  7 місяців тому

      @@calvinmcmahon2714 to be fair they have always been alright with me if we have had high readings a few people have said they told them to put rods in but they have always come and fixed it for me within a few hours

  • @BerlietGBC
    @BerlietGBC 5 місяців тому +1

    I believe British Gas engineers are issued with the Socket and See PDL234 plus part P loop testing kit

    • @JRCElectrical
      @JRCElectrical  5 місяців тому +1

      Ahh I see, I thought they just had a simple socket tester with leds to be fair
      Thankyou

    • @BerlietGBC
      @BerlietGBC 5 місяців тому +1

      @@JRCElectrical I was speaking to a BG engineer last week there very keen on checking everything now

    • @JRCElectrical
      @JRCElectrical  5 місяців тому +1

      @@BerlietGBC as they should be sir, that’s good because all the ones I’ve met just install meters and don’t really know much more 😂

    • @BerlietGBC
      @BerlietGBC 5 місяців тому +1

      @@JRCElectrical I had a very bad experience with a smart meter fixer last year , he spent an hour trying to undo a union in the wrong direction, then forgot to put the dummy in the cut out while working on it I had to shout at him before he got a whack , was scary he had no Idea

    • @JRCElectrical
      @JRCElectrical  5 місяців тому

      @@BerlietGBC they take some of them off universal credit and train them in just changing and installing meters so they have no electrical experience, scary really 😂

  • @xxmrksxx
    @xxmrksxx Рік тому +1

    Good work jack 👍 how you finding the scruffs?

    • @JRCElectrical
      @JRCElectrical  Рік тому

      Cheers dude, yeah there class to be fair.
      Trousers are awesome

  • @zippymo672
    @zippymo672 Рік тому +1

    Hey Jack one of your fans here.
    I have a question in regards to an earth rod installation.
    But how do you check for underground water mains pipes or other electrical mains cables etc before installing a rod?

    • @JRCElectrical
      @JRCElectrical  Рік тому +1

      Just pray 😂😂
      Normaly you can see roughly where they would be from the location of the gas meter, stop tap and mains in building.
      If you weren’t confident tho you can get a scanner or pay for a scan of the area to tell you exactly where the services are

  • @NBundyElectrical
    @NBundyElectrical Рік тому +6

    Makita was cutting it? Bring out the Bosch!!

    • @JRCElectrical
      @JRCElectrical  Рік тому +1

      😂😂😂 dead batteries and no Scott to charge them 😂

  • @koonholee3056
    @koonholee3056 11 місяців тому +1

    Hi jack, thanks for the video,is there anything has to aware of before you decide to drill the earth rod into that soil? Or how do you decide a point to be where you put the earth rod in?

    • @JRCElectrical
      @JRCElectrical  11 місяців тому +1

      Yes be aware of everything 😂
      Just note where the underground services would be, you can get a scan of the area if you pay or have a scanner or you can look at the plans to property which should show you where services are (gas, water, electric and drains)

    • @koonholee3056
      @koonholee3056 11 місяців тому +1

      @@JRCElectrical thx dude, appreciate that

    • @JRCElectrical
      @JRCElectrical  11 місяців тому

      @@koonholee3056 more than welcome sir

  • @TheChipmunk2008
    @TheChipmunk2008 Рік тому +1

    Best reading I've had is 9 ohms on a single 4-ft rod.... Admittedly that was at a marina so the ground was saturated in water

    • @TheChipmunk2008
      @TheChipmunk2008 Рік тому +1

      And yes work is slow for us too... Cost of living is killing domestic work

    • @JRCElectrical
      @JRCElectrical  Рік тому +1

      It’s terrible at the moment sir

    • @JRCElectrical
      @JRCElectrical  Рік тому +1

      That’s a class reading best I’ve seen is 88 at my own house 😂😂

    • @farmersteve129
      @farmersteve129 Рік тому +2

      3 ohms at mine on a single rod even after 10 years... but then we're only spitting distance to the tx.

    • @JRCElectrical
      @JRCElectrical  Рік тому +1

      @@farmersteve129 that’s an awesome reading 😳

  • @three-phase562
    @three-phase562 Рік тому +1

    Nice job with the new rod install 👍👍. Old rods do deteriorate over time, the copper coating disappears just leaving a steel surface that rusts, unless you go for the luxury of a 100% copper rod. We have had complete substations loose their earth reference before now. Hope you get back to winning quotes soon buddy.

    • @JRCElectrical
      @JRCElectrical  Рік тому

      Millionaires have full copper rods 😂😂 cheers dude it’s starting to pick back up to be fair it’s just a crap time with all the bills and things shooting up constantly

    • @Ragnar8504
      @Ragnar8504 Рік тому

      Some countries on the continent have been requiring stainless rods for quite a few years to avoid corrosion issues. Before that it was galvanised and that can rot quite badly.

  • @drred7481
    @drred7481 Рік тому +1

    It’s been a while, so my limited knowledge might be a bit rusty…
    … would a TN-C-S earth have worked in this case (and so dispense with the earthing rods all together?)

    • @JRCElectrical
      @JRCElectrical  Рік тому

      It could have if they have updated it, there doing a lot around here and changing it to tncs but with no sign on the cut out I don’t like to just connect into the neutral 😬

  • @WillmannElectrical
    @WillmannElectrical Рік тому +2

    Sydney is mostly clay, pushing an earthrod in by hand here is unthinkanble 😂I have an SDSMax rod driver bit 💪

    • @JRCElectrical
      @JRCElectrical  Рік тому

      🤮🤮 I can think of nothing worse than driving a rod into clay 😂

    • @TheEulerID
      @TheEulerID 11 місяців тому +1

      @@JRCElectrical try bedrock. Where I live in my garden there are parts with limestone very close to the surface. There certainly isn't 8 feet of soil above it.

    • @JRCElectrical
      @JRCElectrical  11 місяців тому

      @@TheEulerID 😬 that’s not so good 😂

    • @TheEulerID
      @TheEulerID 11 місяців тому +1

      @@JRCElectrical Fortunately built in the 1990s so TN-C-S. No ground rods for me, or at least there won't be until the DNOs change their rules and require supplemental grounding on TN-C-S systems as well, something already required in a lot of countries.

    • @JRCElectrical
      @JRCElectrical  11 місяців тому

      @@TheEulerID 🤢 don’t say that 😮

  • @imark7777777
    @imark7777777 7 місяців тому +1

    I'm curious what the UK requirements are? In the US are code dictates that you can use one earthride but it needs to be tested and if you do 2 it's automatically accepted. Either way the ground wire needs to be continuous from the panel ( < we'll go that to simplify things) down to the electrode and through the other rod with no break. Is it is it common to use more than one ground rod or uncommon? If I were in that situation and getting such a bad ground I probably would've doubled up the old one if it was still reasonably good.

    • @JRCElectrical
      @JRCElectrical  7 місяців тому

      In the UK we need to get the earth reading under 200 ohms and I’ve known people to put rods all over the place to get it under,

  • @Essexdrones
    @Essexdrones Рік тому +1

    Great content l what camera you using ..

    • @JRCElectrical
      @JRCElectrical  Рік тому

      Thanks dude, I use the Sony zv1 on a dji gimbal sir 👍

  • @Jakee112
    @Jakee112 Рік тому +1

    You definitely mean a lot of money

  • @starburst2203
    @starburst2203 Рік тому +1

    7:00 why didn't you just chuck the sds into reverse to take the adapter off 😂

    • @JRCElectrical
      @JRCElectrical  Рік тому +2

      Dunno thought it would have loosened the rod in the ground 😂😂

    • @starburst2203
      @starburst2203 Рік тому

      @@JRCElectrical 😂😂😂

  • @gino2465
    @gino2465 3 місяці тому +1

    Would you not have considered a second rod to get it down even more

    • @JRCElectrical
      @JRCElectrical  3 місяці тому

      It wouldn’t have been possible with the size of the garden area because of the gap needed between the rods

  • @fire_stick
    @fire_stick 4 місяці тому +1

    british gas have their own electricians. 👍

  • @tilidie5272
    @tilidie5272 Рік тому +1

    what do you do if you bang first rod in then go for second and half way down you hit stone or something?

    • @JRCElectrical
      @JRCElectrical  Рік тому

      Struggle 😂😂
      You can buy an attatchment for the end of the rod that turns it into a drill bit to be fair and it smashed through anything, £20 bit that gets burried with the rod tho

    • @tilidie5272
      @tilidie5272 Рік тому +1

      @@JRCElectrical 20 quid tho init maybe get shovel out and apprentice lol

    • @JRCElectrical
      @JRCElectrical  Рік тому

      @@tilidie5272 exactly dude 😂😂

  • @dennisreid4428
    @dennisreid4428 Рік тому +1

    Don't know what type of soil you have down there? Maybe the acid in the soil had eaten through the copper and down to the steel,making it rusty under ground. stopping a reading

    • @JRCElectrical
      @JRCElectrical  Рік тому

      Yeah really strange, I’ve not seen it before to be fair

  • @cjkokay
    @cjkokay Рік тому +1

    The second test is still somewhat incorrect. You have not proved the cable ohm are within spec

    • @JRCElectrical
      @JRCElectrical  Рік тому

      I mentioned it in the video, recommended max ze for TT is 200 ohms, if everything is rcd protected the max is 1667 ohms or something around that 👍

  • @bsesin
    @bsesin Рік тому +1

    no connection jb on the rod ?

  • @gordonmackenzie4512
    @gordonmackenzie4512 Рік тому +1

    You would never ever get an earth rod into the sub soil here. It’s crushed volcanic rock, due to the last ice age. In fact it’s not a subject that ever comes up here. Main earth is to incoming water supply.

    • @JRCElectrical
      @JRCElectrical  Рік тому

      No way where is that? Main earth to water that would be a mega no no here 👀😂

    • @gardenogauge
      @gardenogauge Рік тому +1

      ​@@JRCElectrical it's actually more common in the UK than you think with lead pipes. Normally comes to light when the pipes are replaced with plastic.
      Houses built on rock strata the option is to go for a bolted earth mat

    • @JRCElectrical
      @JRCElectrical  Рік тому +1

      @@gardenogauge never seen that, all around me is built on sandstone so some places are terrible to rod

    • @gordonmackenzie4512
      @gordonmackenzie4512 Рік тому +1

      @@JRCElectrical Asked my electrician today. Only once is entire career has he had to install an earth rod, on a farm. Scotland has a totally different supply structure apparently !

    • @JRCElectrical
      @JRCElectrical  Рік тому

      @@gordonmackenzie4512 ooo I’ve not seen this, here I come google 😂😂

  • @gmeadowcroft84
    @gmeadowcroft84 Рік тому +1

    How do I go about getting a JRC Beanie

    • @JRCElectrical
      @JRCElectrical  Рік тому +1

      There crap 😂
      I washed it once and All the elastic went rubbish I’ll try and get some better ones made

    • @gmeadowcroft84
      @gmeadowcroft84 Рік тому +1

      @@JRCElectrical or a baseball cap 🧢

  • @Mindsaw
    @Mindsaw Рік тому +1

    Hey Jack! Are you open to collab?

    • @JRCElectrical
      @JRCElectrical  Рік тому +1

      Depends on what it is sir, send an email to the email address in my bio on here 👍

    • @Mindsaw
      @Mindsaw Рік тому +1

      @@JRCElectrical Great! Email sent buddy.

    • @JRCElectrical
      @JRCElectrical  Рік тому

      👍👍

  • @cjkokay
    @cjkokay Рік тому

    What I didn't see from the start was using a fly lead was to check çomtinuity of the earth cable end to end!

    • @JRCElectrical
      @JRCElectrical  Рік тому

      This had already been checked sir, the job was booked in after a first call out where I checked these things

  • @deankos3309
    @deankos3309 Рік тому +1

    Mate I love you but the more you keep showing folk how to do electrics the less they need an electrician……

    • @JRCElectrical
      @JRCElectrical  Рік тому +2

      😂😂😂😂 aslong as they still need one in my patch I don’t mind

  • @kbagheri9026
    @kbagheri9026 12 днів тому +1

    Why do you need a rod? is this TT or tncs with additional Earthing???

  • @labelectrical
    @labelectrical Рік тому +1

    Big up yourself 🤟