Generator Differential Protection - Percentage/Bias Setting

Поділитися
Вставка
  • Опубліковано 28 лис 2024

КОМЕНТАРІ • 52

  • @harshau3195
    @harshau3195 23 дні тому

    After this video, I just realised how incompetent my Eng.Lecturers were and the College which maintained beurocratic approach......God Bless You....

  • @ashokkishore4492
    @ashokkishore4492 Рік тому +4

    If there is any word that is more than Thanks i would like to say it ,but as far i only know thanks , this is very helpful to us no other channel explains alternator protection concepts this clearly keep continuing sir and make videos on HT motor, ACB breaker ,VCB breaker ,SF6 breaker protection scheme and 132kv switch yard protection, power and Distribution Transformers protection scheme.
    This is very useful channel for Electrical Engineers with lots of valuable industrial knowledge we can't find any where 🙏🙏🙏🙏🙏👌👌👌👌🙏🙏🙏👌👌
    Keep continuing 👌👌👌👌

    • @ElectricalTalks
      @ElectricalTalks  Рік тому +1

      Thanks from bottom of my heart for such beautiful words 🙏

  • @sankhajitpaul3562
    @sankhajitpaul3562 Рік тому +2

    Thank you sir for the very good explanation ❤️

  • @subhransupradhan2153
    @subhransupradhan2153 Рік тому +3

    The way you explain these topic is really amazing.
    Can you make video on NGR/NGT in alternator

  • @yagnikpansuriya1267
    @yagnikpansuriya1267 Рік тому +2

    Mast explanation!!!

  • @MySpace-vo6ok
    @MySpace-vo6ok 5 місяців тому

    excellent video for an no electrical person like me

  • @AsifAnsari-uw7vm
    @AsifAnsari-uw7vm 11 місяців тому

    Very informative video.

  • @AnswerAtlast
    @AnswerAtlast 10 місяців тому

    Wonderful sir..
    Nicely and thoroughly explained. I am working in 500MW thermal plant as a control room incharge. Today @08:04Hrs our Generator tripped on 87G protection. (Differential)
    After primary findings it was observed a sudden dip of 4KA in R phase current (Generator was delivering 12KA at that time)
    That dip of 4KA was only for 145milli Seconds.
    I want to ask you, can't we give time delay in settings so that it should not operate if fault resets in 100mS

  • @JunsiGaming
    @JunsiGaming 9 місяців тому +2

    Sir please ek video generator differential protection ki calculation kaise karte hai us par banao

  • @sanjayakumarpatel775
    @sanjayakumarpatel775 Рік тому

    Nice video Sir,
    Please prepare Generator Protection Relay testing video.

  • @malluvastrad5179
    @malluvastrad5179 9 місяців тому

    Sir The way you explain very well Sir.
    So please explain All Protections of Gen's and TRF's other also Sir, Hope sir you will Give information us for other protections also,

  • @sangeetajundhare2495
    @sangeetajundhare2495 4 місяці тому

    Nice explanation Sir

  • @arunkumaryadav7518
    @arunkumaryadav7518 Рік тому +1

    Nice explanation

  • @MrFahim-dg3fh
    @MrFahim-dg3fh Рік тому

    Nice tutorial. Please tell me as per international rules what should be the differential current trip setpoint with respect to nominal current of alternator on controller?

  • @rukmagoud
    @rukmagoud Рік тому +5

    Generator is grounded through high impedance and the fault current is restricted to just 10A to save the stator core. Differential doesn't act for such small currents. These faults are taken care by stator earth fault relay.

  • @ShailendraKumar-ic9lk
    @ShailendraKumar-ic9lk Рік тому

    Sir ct settings 10 % .. generator current..rakh sakte h kya sir

  • @connectingdots...3098
    @connectingdots...3098 Рік тому +2

    Sir please make a video on calculation part also. how to calculate settings value with numerical example and selection of ct ratio.

  • @mousumisingh6539
    @mousumisingh6539 5 місяців тому

    Great 👍

  • @surendrakverma555
    @surendrakverma555 4 місяці тому

    Thanks Sir

  • @GTROCKS1231
    @GTROCKS1231 Рік тому +1

    Great 👍👍👍👍

    • @ElectricalTalks
      @ElectricalTalks  Рік тому

      Thanks

    • @GTROCKS1231
      @GTROCKS1231 Рік тому

      U made it understandable to a mechanical background person like me... Thanks to you..... 😀🎉

  • @amitkalyan5435
    @amitkalyan5435 Рік тому +1

    Good

  • @prabhatsingh5377
    @prabhatsingh5377 Рік тому +1

    Excellent

  • @jhon5769
    @jhon5769 7 місяців тому

    Thank you

  • @laxmankumar-iw8lq
    @laxmankumar-iw8lq Рік тому

    i am Zero knowledge in stock market, like what is stock market, can i eligible for this class........?

  • @akashsenta3601
    @akashsenta3601 Рік тому +1

    Respected Sir,
    My relay Differential relay DTH31 (Electromagnetic relay)
    Relay name plate relay operating current 1A
    But i take Bias testing DC current inject 2.5 A and varying AC current.
    Why not relay burn out for 2.5 A current.
    Please explain briefly.
    Thank you

    • @ElectricalTalks
      @ElectricalTalks  Рік тому

      Rating for two coils - operating & bias coil may be different.

  • @AtindraTiwari-j2l
    @AtindraTiwari-j2l Рік тому +1

    Sir please explain transformer protection also sir

  • @baqarengr4823
    @baqarengr4823 Рік тому

    Thank you sir 😘

  • @vaibhava108
    @vaibhava108 11 місяців тому

    Sir, percentage bias ki value kya hogi Gen. And Transformer ke case me

  • @م.مهندحسن
    @م.مهندحسن Рік тому +1

    Where connect two ct for differential relay if the 4wire out from the generator

    • @ElectricalTalks
      @ElectricalTalks  Рік тому

      Good observation 😊
      Actually in practice, you will find total 6/9 terminals out of generator. Neutral point is made outside the generator casing.
      In inter turn protection, 9 terminals concept will be discussed.

    • @م.مهندحسن
      @م.مهندحسن Рік тому

      @@ElectricalTalks thats mean in generator we connect ct to inner protaction and out of protaction where connection

  • @parvezalam3843
    @parvezalam3843 Рік тому +1

    Sr T/F charging k uppar v ek video dijiye na Plz
    Aagar hum T/F charging krte hai to kya wo v inrush current leta hai?

    • @ElectricalTalks
      @ElectricalTalks  Рік тому

      Do you mean v/f?

    • @parvezalam3843
      @parvezalam3843 Рік тому

      Nai sir..
      Mera mtlb ye hai k jb hum T/F pr load connect krte hai to kya wo v motar ki tarreh hi inrush current pik krta hai
      Ya ki wo apne rating pr hi work krta hai?

  • @PappuKumar-jv7ck
    @PappuKumar-jv7ck Рік тому

    generator को ड्राई आउट पर लगाते समय हमें किस किस चीज का ध्यान रखना hai. Sir please make this topic video .

  • @MrPaul49414
    @MrPaul49414 Рік тому

    No, stator earth wil not operate differential protection. Bcoz cT is not connected on star point for differential prtn..

    • @MrPaul49414
      @MrPaul49414 Рік тому

      Thanks for the explanation sir

  • @ShailendraKumar-ic9lk
    @ShailendraKumar-ic9lk Рік тому

    Ps class kya h sir