Why Measure Compressor Discharge Line Temperature?

Поділитися
Вставка
  • Опубліковано 13 сер 2022
  • Bryan explains why you would measure discharge line temperature. He goes over the information that you could learn from discharge line readings and how to reduce excessive discharge line temperatures and compression ratios.
    The discharge line is the smaller line that exits the compressor and eventually feeds into the condenser. On a heat pump, it normally goes into the reversing valve from the top.
    The discharge line should not be confused with the liquid line, which goes out of the condenser. You can expect the discharge line pressure to be a bit higher than the liquid line pressure, but its temperature will be way higher than the liquid line temperature. That’s because the condenser desuperheats that very hot vapor, condenses it to a liquid, and cools it below the saturation temperature (subcooling).
    Like the suction line, the discharge line contains superheated vapor. However, the temperature of the discharge line is much, much higher than that of the suction line.
    You can use Bluetooth probes to measure the discharge line. Several things impact the discharge line temperature, including the location. Normally, we want to measure the discharge line temperature about six inches away from the compressor; the temperature can vary quite a bit depending on where we take our measurements, so the industry standard is typically lower than 225 degrees six inches from the compressor outlet. However, individual units may have higher or lower specifications. (The compressor may be around 70 degrees hotter, and the area near the condenser will be significantly cooler.)
    Normally, when the compressor exceeds 300 degrees, oil breakdown may occur. Higher temperatures result in oil with reduced viscosity, meaning the oil becomes thinner and cannot lubricate the bearings as well as it should. Mechanical wear in the compression chamber is another problem that can be discovered by finding a high discharge line temperature. So, we want to run compressors as cool as possible.
    High compression ratios may cause compressors to overheat. So, we want to do whatever is in our power to reduce the compression ratio. We can find the compression ratio by dividing the absolute head pressure by the absolute suction pressure, and we typically want that quotient to be ~3 for modern air conditioning equipment (refrigeration equipment tends to have higher compression ratios).
    We can reduce compression ratios by keeping the compressor cooler, such as by using interstage cooling or liquid or vapor injection to reduce discharge temperatures. Dirty condensers that restrict airflow also raise the head pressure, increasing the compression ratio and resulting in higher discharge pressures. Significantly overcharged systems may also raise head pressure.
    Low suction pressure also leads to higher compression ratios; low suction pressure may be caused by low loads or metering devices that feed the evaporator coil poorly. However, cooler suction lines don’t necessarily cause the discharge line to be cooler, especially if the mass flow rate is also low.
    Copeland Mobile can show you how operating a system outside its operating envelope can contribute to poor system performance (assuming you’re working with a Copeland compressor). You can adjust the conditions within the app to see what the discharge temperature, compressor capacity, and mass flow rate will be under various operating conditions. You may find it exceptionally helpful when used with the AE Bulletins app, which contains useful information about Copeland compressors.
    Read all the tech tips, take the quizzes, and find our handy calculators at www.hvacrschool.com/.

КОМЕНТАРІ • 47

  • @ciciedee5474
    @ciciedee5474 Рік тому +11

    You are a great teacher. I have spent all day watching your videos. They're not boring. They teach best practices as far as doing the job once. No call backs. Call backs are the biggest cause of me not using a contractor twice

  • @scottallen5182
    @scottallen5182 Рік тому +18

    Bryan, you have done more for our industry than anyone in modern times. Your training is always over the top. You are appreciated more than you could ever know!

  • @Pro_Tech01
    @Pro_Tech01 Рік тому +3

    bryan is the hvac carl sagan, thanks for all you do for our industry

  • @dickmick5517
    @dickmick5517 Рік тому +4

    Wow. Great explanations along with no repetition. Very difficult to speak this way. You have a teaching gift. Thanks

  • @mikedawe692
    @mikedawe692 Рік тому +3

    Brain your tutorials are excellent. I’m not glibly throwing throwing complements here, your work is truly superb. I have quite a library of the HVAC School tutorials and greatly admire your abilities as an educator.
    I do however have one tiny little problem and it’s not anything that you or I can do much about. I can’t use as much of your stuff in my class as I’d like to because of the F word. Fahrenheit… there I’ve said it. The one word that I will not allow students in my classes to use.
    How long would this video be if we had to recalculate every reference to temperature and how much would it break the flow of information. If only we all used the same method. I guess it won’t be last time we hear this lament and none of us will be holding our breath waiting for change.
    Again, thank you for your great work.

  • @robertbeckler5058
    @robertbeckler5058 Рік тому

    Groovy, send the young techs your stuff all the time. Actually got one to watch and he subbed you.

  • @mikaelg5840
    @mikaelg5840 Рік тому +1

    Great video, thanks for your excellent explanation

  • @brianmcdermott2430
    @brianmcdermott2430 Рік тому

    Super great info. Thank you Bryan.

  • @resurgensix
    @resurgensix Рік тому

    Always bringing phenomenal education!🤘

  • @retsbew8954
    @retsbew8954 Рік тому

    Very good, and as always, I learned something new.

  • @jacobsibanda3531
    @jacobsibanda3531 Рік тому

    your teachings are too helpful ,you are pro dude

  • @hvacresidentialbasics7684
    @hvacresidentialbasics7684 Рік тому +2

    Thanks Bryan

  • @jamesgray1469
    @jamesgray1469 Рік тому

    Thanks for the video, it answered a few questions I had as to why the high and low pressure lines are not insulated together, as the low pressure line needs to be cool to keep the compressor temp down. Or why my ac man thirty years ago recommended a 4 ton air-handler with a 3.5 ton condenser since we ran the liquid line inside the drain pipe.

  • @jasonjohnsonHVAC
    @jasonjohnsonHVAC Рік тому

    As a commercial tech....you are speaking my language.....we dont hardly ever see a liquid line port. I will say though....ran into a weird situation 2 weeks ago. Mammoth WSHP it has a discharge and liquid port.....and no suction port.....i was like what the heck is this. Great video

  • @robertotrinanes1744
    @robertotrinanes1744 Рік тому +1

    Thanks for info

  • @phillipjoy1305
    @phillipjoy1305 Рік тому

    Great videos 😜

  • @raymondwollitz5582
    @raymondwollitz5582 Рік тому +3

    I used to install a small stick-on dot on the discharge line that would change color so I could tell if the compressor had overheated.

    • @T_cole_g
      @T_cole_g Рік тому +1

      Would it not fade?

  • @honestman276
    @honestman276 9 місяців тому

    Thanks from Bangladesh.

  • @2bnax
    @2bnax 2 місяці тому

    WHAT IS THE RIGHT WAY TO CHECK DISCHARGE PRESSURE WHILE USING SUPERHEAT METHOD? OR WHAT SHOULD THE PRESS. BE? MANY PEOPLE DON'T HOOK UP HIGH-SIDE

  • @shannonhill3356
    @shannonhill3356 Рік тому +1

    Bryan, Hi!
    I recently had a pretty bad experience due to a UV light that evidently did it’s work on my eyes before I disconnected it (was unaware it was in the system prior to opening it - lovely!) that won me a trip to the hospital, along with some terror of blindness.
    It’s cleared up now, but I’m looking into buying some safety shades and unsure what code or specification to look for - if my research serves correctly, ANSI Z87 with orange tint should be what I’m looking for, but would like some guidance from the community to keep safer on the job!
    Thanks guys! It’s hot here in SW Florida!

  • @animalslover7132
    @animalslover7132 Рік тому

    What is the different between cooling type air cooling chiller and heating and cooling type air cooled chiller.

  • @andrewgowens1175
    @andrewgowens1175 11 місяців тому

    Had a system not maintaining super heat. Checked airflow and checked subcooling wich were both where they should be according to manufacturer I also checked discharge line temp which was about 175 F the superheat was very low so I replaced txv. Started it up had the same issue. I called carrier and was told that a discharge temp above 160 meant that the compressor was the issue. I to thought that 175 was acceptable but not according to Carrier. They claim that on residential condensers with a scroll compressor that anything above 160 is to high even on a 100 degreee day. Also compressor was pulling normal amps according to manufacturer data plate.

  • @flyvide00
    @flyvide00 Рік тому

    Question, can poor evacuated or, un-evacuated system cause high head temperatures?

  • @iqbalchaudhary218
    @iqbalchaudhary218 11 місяців тому

    If a low discharge temp presents with low compressor amperage, how can it be fixed? Thanks

  • @Brisket9392
    @Brisket9392 Рік тому

    Bryan. Your hair looks f'n awesome. Jelly.

  • @nathanwildman6404
    @nathanwildman6404 Рік тому

    Can't get the Copeland Mobile App out of the States it seems, looks like it would be a handy tool to have.

  • @billbaber6653
    @billbaber6653 Рік тому

    Like you better than sports talk!

  • @thealeons3179
    @thealeons3179 Рік тому +4

    I'm a technician for Fluid Chillers Inc. Damn this is a fasciating video. I have run ultra low temperature Chillers with as low as -20/ or 20Hg suction line pressure. These are two stage Bitzers with interstage subcoolers. So the discharge of the interstage H/E helps cool down the compressor?

    • @jasonjohnsonHVAC
      @jasonjohnsonHVAC Рік тому +1

      Yup. We service many centrifugal low pressure chillers. Evap side is in a vacuum and the high side can be or at the most barely over 0 psig of pressure. I believe the relief valves/ burst disk pop on those at like 15 psi or something close to that.

  • @wildman8601
    @wildman8601 Рік тому

    now this is more for Southern or western issues w more year round hot weather I'm assuming ... because in New York area and the north east we have less of thay hottet weather... so would you still recommend this for us guys up this way ?

    • @michaelnash8435
      @michaelnash8435 Рік тому +1

      Discharge temperature is a pretty critical measurement and while it might not be as huge of an issue up there (I don't know), it would still be a great tool to use when determining the lifespan of a compressor. Like he implies in this video, the hotter the discharge temp, generally the shorter the lifespan.

  • @jaysongoff
    @jaysongoff Рік тому +1

    So, the general industry standard is not to exceed approximately 250 degrees, 6 inches down the discharge line. What is the minimum temperature standard to keep from damaging the compressor? I know that most compressor mfg. say not to go below 20 degrees superheat on the suction inlet, but what is the minimum temperature on the discharge line?

    • @michaelnash8435
      @michaelnash8435 Рік тому

      The real concern of low discharge temperature is low discharge pressure which increases the velocity of the refrigerant. Not really a concern for your average HVAC tech, but it comes into play in refrigeration now and then, especially with evaporative condensers. You can exceed the limitations of the system piping, sometimes fairly quickly on old systems.

  • @stevedixon2414
    @stevedixon2414 Рік тому +1

    Thanks ...from Sheffield UK:)

  • @JahonCross
    @JahonCross Рік тому

    How do I measure it without burning my hands?

  • @guyduke12
    @guyduke12 Рік тому

    Hey Brian! Any chance y’all could update your playlist on your Chanel?

  • @arcticzone9223
    @arcticzone9223 Рік тому

    Condenser too small?! (Modified system)

  • @elgringoec
    @elgringoec Рік тому

    Good info, but I think this video flow could have been a little better organized - all your other videos I've seen were organized better, imo.

  • @joshschumacher7984
    @joshschumacher7984 Рік тому

    You hiring lol?

  • @sammyd7857
    @sammyd7857 Рік тому

    Unless you have put a thermometer inside a compressor head you have no idea how hot it is.

    • @michaelnash8435
      @michaelnash8435 Рік тому +1

      Pretty cocky to assume the manufacturers don't know how hot their components run. The information is out there, read it.

    • @sammyd7857
      @sammyd7857 Рік тому

      @@michaelnash8435 so this guy doesn't know what he is talking about when he says at around 300 F the oil starts to break down? So with a discharge of 225 what did he say the head temperature would be?

    • @michaelnash8435
      @michaelnash8435 Рік тому +1

      @@sammyd7857 no, this guy knows exactly what he's talking about. 300° will break down oil.
      225 what? PSI? Degrees? Either way, You can't say for 225 discharge temperature or pressure that the other would be anything since it's a superheated vapor. It won't follow a normal PT relationship.
      Edit: 300° CAN break down oil.

    • @sammyd7857
      @sammyd7857 Рік тому

      @@michaelnash8435 I see you like contradicting yourself

    • @MegaDysart
      @MegaDysart Рік тому +1

      Youre being pedantic about something that was a hypothetical meant to reinforce an idea, not an all out statement of fact. That being said, you can be pretty reasonably sure about numbers like that since there's a huge repository of manufacturer data available which they do extensive testing on before releasing.