    I have a QX451BP touch screen. Does the new version of CScape support LAN configuration for this legacy touchscreen?

    • @LionsIndy
      @LionsIndy Рік тому

      The QX451 is supported by Cscape 9.90 - which is still the current version. When Cscape 10 is released, it will NOT support the QX series - but you will still be able to use Cscape 9.90 (and all other previous Cscape versions) to work with the QX product.

    • @SuperRob32
      @SuperRob32 Рік тому

      @@LionsIndy Hello again. Is it possible to communicate between PLC Mitsubishi FX5U and QX451 via Ethernet or is communication only via RS485?

    • @LionsIndy
      @LionsIndy Рік тому

      @@SuperRob32 From the little bit of research I've done, it appears that the Mitsubishi will support Modbus TCP, but only as a client (Master). If you configure the QX as a Modbus TCP server (slave), you would be able to exchange word data between the two.

    • @SuperRob32
      @SuperRob32 Рік тому

      @@LionsIndy Thanks a lot. So I will have to use RS 485. Do you have a video on your channel describing how to set up a touch screen to control a PLC?

    • @LionsIndy
      @LionsIndy Рік тому

      @@SuperRob32 not specifically. But here are a couple of links to videos that I think would be helpful…
      ua-cam.com/video/ARQfptbP8zU/v-deo.htmlsi=-RlTzpIDcJSUDyCx
      ua-cam.com/video/Txh0Zt946mA/v-deo.htmlsi=VAmlx-J8C1DqeATx
      And while it won't help you out in the short term, I will schedule that exact topic later this fall…