Cable Size Calculation for Medium Voltage or 11kV Electrical Systems

Поділитися
Вставка
  • Опубліковано 21 жов 2024

КОМЕНТАРІ • 58

  • @olalekanmagbade8763
    @olalekanmagbade8763 8 місяців тому +1

    Thanks for making this video. It's the best I have found on this topic. Can you please provide info on how the reference materials used on this video? The derating factors and cable size tables will be especially helpful.

  • @akbarshokrifirouzjaee1837
    @akbarshokrifirouzjaee1837 Рік тому +2

    آفرین جوان

  • @amiselectricals5553
    @amiselectricals5553 Рік тому +2

    Thanks for sharing these valuable details.
    Kindly send the link to get this chart.

  • @juanlotta2925
    @juanlotta2925 2 роки тому +1

    It would be helpeful if you share the standards you're taking into account

  • @martync8724
    @martync8724 2 роки тому +2

    Very thorough and clear - thx.

  • @faisalbukhari4119
    @faisalbukhari4119 Рік тому +1

    Very Good. Keep it up. Make more videos.

  • @karthickd.n8403
    @karthickd.n8403 Рік тому +2

    de rating factor reduces the current carrying ability of the cable , so 187A x 0.76 = 142A , as the FLA of transformer = 131A, selection of the cable size of 50sq.mm is good. correct me if iam wrong.

    • @adamdhible5704
      @adamdhible5704 Рік тому

      That is what I thought myself. De-rating means reducing the rating of something and they should be multiplied.

    • @cedarxeda2665
      @cedarxeda2665 3 місяці тому

      You re wrong

  • @foras87
    @foras87 2 роки тому +3

    Do you know about any software for a medium voltage cabling calculations?

    • @electricalknowledge2654
      @electricalknowledge2654  2 роки тому

      Softwares are usually rough estimates and calculations vary according to the Cable manufaturers specifications or tables. So you must understand the cable size Calculation for right selection of cables.

  • @sniperchanel3917
    @sniperchanel3917 3 роки тому +1

    Thanks for share verry interesting content

  • @charinath5445
    @charinath5445 Рік тому +1

    what is the difference between HV and LV cable sizing?

  • @MuhammadAwais-ob2ib
    @MuhammadAwais-ob2ib 2 роки тому +2

    Appreciate your effort.

  • @sumedhaweb1809
    @sumedhaweb1809 Рік тому +1

    how can u add Rcos@ and X sine@ .these are complex numbers. it should be

  • @hidayahsahudi4567
    @hidayahsahudi4567 Рік тому +1

    How to calculate if we want to use 2 or 3 nos of cables per phase?

  • @tariknawazkhan3764
    @tariknawazkhan3764 2 роки тому +3

    Thanks Man... really appreciate

  • @azhar204
    @azhar204 Рік тому +1

    hi sir, i gave one doubt if the length is 15000 MTR as my able length is 15KM shall i need to divide it my 1000 or 10000..

    • @electricalknowledge2654
      @electricalknowledge2654  9 місяців тому +1

      Brother you need to divide by 1000 if you are taking length in Meter. If your length is already in KM, then no need to divide by 1000. Means if you are taking 15km then no need to divide by 1000

  • @pradeeppoojari2786
    @pradeeppoojari2786 8 місяців тому +1

    Current after derating factor why it is devided by 0.76..it should be 131*0.76 apprximately 100 Amp

    • @electricalknowledge2654
      @electricalknowledge2654  8 місяців тому

      When you divide with derating factor, you will get the value of current, including derating factor margin. When you multiple with derating factor, you will get a value of current after deration which means you need to add additional derating margin to find out the value of current to be selected from cable table.

  • @dank9625
    @dank9625 7 місяців тому

    Hello! May I ask the references for the derating factors Tnx

  • @joginderpal4461
    @joginderpal4461 2 роки тому +1

    120Kw motor need to cable size , with copper and aluminum, please brief example with formula

  • @tuleanhvt
    @tuleanhvt 3 роки тому

    Hi H N, As I have known for the motors, we should be aware of voltage drop in both steady state & starting of motor. Could you explain for these cases of Motors?

    • @electricalknowledge2654
      @electricalknowledge2654  2 роки тому

      Please watch my separate video on cable size Calculation for motors and group of motors

  • @foras87
    @foras87 2 роки тому +1

    many thanks

  • @thrinadnadh9125
    @thrinadnadh9125 2 роки тому

    Hello Sir, what are you showing the tables to calculate HV/MV Cables from which IEC Code?

  • @zubairali744
    @zubairali744 2 роки тому

    from where you get the cos@ & Sin@ value? respectively 0.8 &0.6 please clear.

    • @electricalknowledge2654
      @electricalknowledge2654  2 роки тому +1

      Power factor assume to be 0.8 in the selected case study, however the value may changes according to your requirements or conditions. The value of @ will be be calculated from cos@ which further derive the value of sin@.

    • @foras87
      @foras87 2 роки тому

      @@electricalknowledge2654 could you please clarify the 'The value of @ will be be calculated from cos@ which further derive the value of sin@'?

  • @saeedahmed4651
    @saeedahmed4651 2 роки тому +1

    can you please share the excel sheet for the easy calculation for pakistan.

  • @foras87
    @foras87 2 роки тому

    Could you please advise how we can find the Max. Load Allowed on 1 Feeder @ HT = 5MW or 6.25MVA or 328A?

    • @electricalknowledge2654
      @electricalknowledge2654  2 роки тому +3

      Hi Artemois, It all depends on how much your concerned utility or electrical distribution company allowed on one feeder.
      I have shared the allowable load limit that is 5MW on one feeder referring to what allowed in Pakistan. It varies country to country.

    • @foras87
      @foras87 2 роки тому +1

      @@electricalknowledge2654 Thank you very much!

    • @amarnathmishra1461
      @amarnathmishra1461 2 роки тому

      It depends upon the current carrying capacity of the conductor used.with ACSR dog conductor, you may transmit 5 MVA load at 11kv

  • @mohamedali-tx4sb
    @mohamedali-tx4sb 2 роки тому

    How many transformers can feed from m v switchgear in one loop

    • @electricalknowledge2654
      @electricalknowledge2654  2 роки тому

      Ali, It depends upon what rating of transformer you are connecting to one feeder. However, 5MVA can be allocated on one feeder usually by WAPDA.

  • @hanhan2921
    @hanhan2921 2 роки тому +1

    Hi , Can you please send us the table for single core cables please ?

  • @ScholarshipTamil
    @ScholarshipTamil 2 роки тому +1

    Could possible to share supporting documents

  • @engr.saddamahamed4009
    @engr.saddamahamed4009 2 роки тому

    I think 2nd slid calculation is wrong. it will be only 2500KVA or you need to divided 1000 also. thank you

    • @electricalknowledge2654
      @electricalknowledge2654  2 роки тому +1

      Saddam, Answer is correct i.e 131A. However, you are right, the voltage is 11000V instead of 11kV thus to ensure the units are same.

  • @gamalhassan2769
    @gamalhassan2769 Рік тому +1

    thx

  • @aymankazem6982
    @aymankazem6982 2 роки тому

    current for low voltage side is incorrect because short circuit current must be calculate for medium voltage network 500 MVAS.C

    • @electricalknowledge2654
      @electricalknowledge2654  2 роки тому

      Ayman, These calculations are for medium voltage cables and short circuit fault current calculated at specified duration of time.
      I think you are mentioning about fault current of system which are require to be calculated on base MVA of system.

  • @aizazrahim8313
    @aizazrahim8313 2 роки тому +1

    Sir, plz share this cable catalog

  • @transientmatter6088
    @transientmatter6088 2 роки тому

    when you size mv cable , only short circuit power is enough ,

    • @electricalknowledge2654
      @electricalknowledge2654  2 роки тому

      You must comply three criteria i.e. Current Carrying Capacity, Voltage Drop and Short Circuit Current.

    • @transientmatter6088
      @transientmatter6088 2 роки тому

      @@electricalknowledge2654
      Experience of 30 years says
      Short circuit power enough for mv cable..

    • @electricalknowledge2654
      @electricalknowledge2654  2 роки тому +1

      ​@@transientmatter6088 It depends, you may be right. What would be your reference for short circuit current before selecting a MV cable.
      I would recommend to comply all the three criteria.

  • @arun4846
    @arun4846 2 роки тому

    👍😉

  • @nadim606
    @nadim606 10 місяців тому +1

    seen

  • @osamasadekadam321
    @osamasadekadam321 5 місяців тому

    Ok

  • @ZarghamAli-i7c
    @ZarghamAli-i7c Рік тому +1

    Hi. Can you please share your email id for a project?