By transducer output voltage or M-amp check analog voltage by max and min volt or 4-20 amp out aapko max 10 v Tak or4-29 ma milega usi se pressure me divided kar do , wahi limit hoga jisko pressure me measure karte hai
Bro I want to run 4 vibrator motors at same time in my factory. Each motor Amp 2.8/1.6... power unit 1 KW ...how These two parameters enter. I have doubt. Then output line MCB always trip...please any idea?
Thanks for your question , go through the below for your question . P1300 put 7 which is for V/F mode. Mean vector mode which can run multiple motor. Set total capacity example: 2amp+2amp+2amp= set point in 6 amp same calculate KW then put 20%extra KW # All connected motors will be run in parallel individual can’t be control. # must be cable pass through output protection such as MPCB etc. # If your MCB tripping that mean overload short circuit # If MCCB tripping means leakage, short, overload (check ELR,cable motor winding and breaker ) # If ELCB tripping means current leak. # for motor speed can be variable by AI, DI by same parameter as the video .
Is method me plc required nahi hota hai if you need variable then use potential controller otherwise you can select 3step frequency for D1,2,3 to use H M L speed
Then check your connection ,AI potential should work by 0-10 v if this is ok then check parameters where you applied 10 put 7. Otherwise check hardware also you can share me your WhatsApp for all conversations to short out the issue thanks
@@nawalkishorkumar9947 Aapko parameter P0756 me 2 set krna hai after aapka AI 1 input MA me ho jayega , agar 3 rakhte hai to monitoring with ma input ho jayega dono ek ek kar ke results dekh sakte hai Thanks
Very good sir
Thank you sir please make more
Sure
Good
❤
Sir pressure transducer sa pressure kaisa set kerta hn
By transducer output voltage or M-amp check analog voltage by max and min volt or 4-20 amp out aapko max 10 v Tak or4-29 ma milega usi se pressure me divided kar do , wahi limit hoga jisko pressure me measure karte hai
Thnks sir .
Frequency setting 75Hz ,in auto mode running drive shows 31Hz. What is problem but manual mode it shows 75Hz.
If you are running through DI then set your voltage accordingly with HZ and potential should reach on 100% as per the maximum speed set point
Hz can only 50 or 60 percent can go up to 100
Bro I want to run 4 vibrator motors at same time in my factory. Each motor Amp 2.8/1.6... power unit 1 KW ...how These two parameters enter. I have doubt. Then output line MCB always trip...please any idea?
Thanks for your question , go through the below for your question .
P1300 put 7 which is for V/F mode. Mean vector mode which can run multiple motor.
Set total capacity example: 2amp+2amp+2amp= set point in 6 amp same calculate KW then put 20%extra KW
# All connected motors will be run in parallel individual can’t be control.
# must be cable pass through output protection such as MPCB etc.
# If your MCB tripping that mean overload short circuit
# If MCCB tripping means leakage, short, overload (check ELR,cable motor winding and breaker )
# If ELCB tripping means current leak.
# for motor speed can be variable by AI, DI by same parameter as the video .
D01+ and D01- out put voltage is not coming sir. Any tip please....
Check PO731 fix 53.3 if not then fix 53.2 if setting are ok then check inverter internal DC fuse
In P732 r2815.0 setted how it works please explain
Plc use na kar ke bypass se vfd run hardware mode me kase kare
Is method me plc required nahi hota hai if you need variable then use potential controller otherwise you can select 3step frequency for D1,2,3 to use H M L speed
I have setted all parameters as per video
Now vfd is running in manual mode but not run in auto mode
Also configured di for auto mode
Then check your connection ,AI potential should work by 0-10 v if this is ok then check parameters where you applied 10 put 7. Otherwise check hardware also you can share me your WhatsApp for all conversations to short out the issue thanks
ভাই, আপনার হেল্প দরকার আমার, আমাকে হেল্প করতে পারবেন একটু?
Hi thanks for your comment, can you write in English please
M a ka vi bataye
M a ka vi bataye mean ?
@@gajendrapandey5202 4 ma to 20 ma analogs input and output ka parameter setting bataye
@@nawalkishorkumar9947 Aapko parameter P0756 me 2 set krna hai after aapka AI 1 input MA me ho jayega , agar 3 rakhte hai to monitoring with ma input ho jayega dono ek ek kar ke results dekh sakte hai
Thanks
Sir p0756 me 2 dalne ke baad me bhi nahi hua please aap ispar 1 video lade
Sir apka no. Mil sakta hai
Aap Numbers share kar dijiye mai msg krta hu by WhatsApp