Coordination, Overcurrent Protective Devices

Поділитися
Вставка
  • Опубліковано 22 жов 2024

КОМЕНТАРІ • 50

  • @reynaldomartinez4742
    @reynaldomartinez4742 11 місяців тому +8

    Happened to me at work. Old building with a brand new main panel- 2000A breaker tripped. Buildimg with labs and experiments that had been testing for years. Everyone freaking out. Lucky for me i was aware of instantenous tripping and new that a short had most most likely been the cause. Had a feeling there had to be a tripped small breaker somewhere. Took two hours to go to each floors electrical room and to find panels in other places to see that everything was ok. Finally found a three phase 480v 15amp tripped breaker for a compressor which i checked for ground fault. I left that breaker tripped and went ahead suited up and energized the main. Power was restored. Alittle of knowledge, safety and common sense goes along way

    • @MikeHoltNEC
      @MikeHoltNEC  11 місяців тому +1

      Wow, a 2000A breaker... My largest was 800A.

  • @bajothesparky2445
    @bajothesparky2445 Рік тому +2

    The best Sensei in the Electrical World.POINT.Thanks Mike also for responding to all guys that try to reach out to you. Big Cheers from Chicago.

    • @MikeHoltNEC
      @MikeHoltNEC  Рік тому +1

      Thank you, you guys are very important to me.

  • @Gman737e
    @Gman737e Рік тому +4

    Hey Mike, thanks for all the work you do. Ive learned so much through your programs. I constantly find myself going back to rewarch & reread material. Your journeymen program aided me in getting licensed in Chicago. I passed with a 93% the first time. Meanwhile, my brother did not use your program, he failed twice and finally got it on his third try with a 71% (70 passing) lol. You are clearly doing something right. Thanks a lot! I love the content. I plan on getting the estimating program soon as now i am an electrical contractor and i cant wait to see what great info is packed in there Thanks a lot Mike!

    • @MikeHoltNEC
      @MikeHoltNEC  Рік тому +1

      Thank you for the great news and the kind words.

  • @tfun101
    @tfun101 Рік тому +2

    Wow love the look of these new videos with the filming room, cameras, etc...every code cycle Mike gets more high tech with the filming!

  • @vivianledonghae4eify
    @vivianledonghae4eify Рік тому

    OMG. I cant believe that I just found your channel.
    the materials are so useful for my upcoming PE exam

    • @MikeHoltNEC
      @MikeHoltNEC  Рік тому

      The PE exam has significantly increased the NEC portion of the exam. Enjoy

  • @Sparky-ww5re
    @Sparky-ww5re Рік тому +4

    In the apartment I lived in 8 years ago a cookie sheet fell behind the stove and shorted the prongs of the 3 wire range plug and tripped the main that was in the mechanical room of the building, but the 40 amp breaker in my unit didn't trip.

  • @Tipperjoxford
    @Tipperjoxford Рік тому +1

    Awe man.. look at those updates!!! looking great!!!

    • @MikeHoltNEC
      @MikeHoltNEC  Рік тому +1

      Thanks, we are really getting to the next level. One day at a time.

  • @krishnasimhavemulapalli7124

    Hi,your lectures are inspiring and informative.Thank you for these.

  • @latcocina1220
    @latcocina1220 9 місяців тому +1

    Thank you Mike 🙏

  • @robertlitman2661
    @robertlitman2661 Рік тому +1

    I think this is a topic that needs more time spent on it, as so many electricians in the field simply have no idea how this works. Working in a data center, I have experienced two avoidable breaker coordination failures. In one instance, a contactor flashed over internally, tripping the internal 600A breaker of a UPS unit, the upstream 600A breaker in the adjacent bypass panel, and the further upstream 600A supply breaker in the main electrical room. All three breakers have tunable magnetics, and were left at the factory setting of lowest instantaneous threshold, when the upstream breakers should have been set to the highest instantaneous threshold. At least the main breakers above those were all computerized.
    The second incident had a 20A PDU breaker trip, a 30A breaker in a busway tap, and the 225A busway main breaker trip simultaneously. Again, the 225A breaker was dialed to the most sensitive magnetic setting from the factory, when it should have been changed to the least sensitive. Unfortunately, circuits near busways can have high short circuit currents just like circuits near panels.

  • @iphlueable
    @iphlueable Рік тому +5

    I see this happening on a regular basis. (Industrial) Very frustrating.
    If only there was a way to coordinate gfci breakers? I once (20+ years ago) by chance shut down the ENTIRE Chevron world headquarters in san ramon ca by simply working on lighting and messing with the neutrals in a ceiling light box. Yes, the entire building was on gfci close to or at the service. My boss was pissed but not at me. Rather at whoever designed such a thing. An interesting day to say the least.

    • @Sparky-ww5re
      @Sparky-ww5re Рік тому

      Very interesting.

    • @MikeHoltNEC
      @MikeHoltNEC  Рік тому +1

      OMG... I know the feeling. I was teaching at Texas Instruments World Headquarters and the power to the entire facility turned off for about three hours! People were freaking out. The 'high-voltage' fuse at the street somehow dropped out... true story.

    • @bitzyc5308
      @bitzyc5308 29 днів тому

      but there is a way to coordinate the gfci brakers! what i'm i missig here?

  • @bryanz5904
    @bryanz5904 6 місяців тому

    An important task, especially for fire protection types of equipment such as the Fire pump panel that feeds two or more individual pumps. Each of the main breakers and sub-breakers needs careful coordination.
    When I design the Nuclear Command Center for PWRs, I also need to consider that long-distance low voltage routing brings too much high impedance and makes the instantaneous rate, not enough sensitive to trip in time.

    • @MikeHoltNEC
      @MikeHoltNEC  6 місяців тому

      Well, I never considered the length of the conductors (impedance) when designing 'selective coordination.'

  • @domcic5295
    @domcic5295 Рік тому

    I was working on a 20A 277V lighting circuit and pinched a wire in the fixture so when I turned the breaker back on, not only did the 20A breaker trip but so did the 800A main!😅

    • @MikeHoltNEC
      @MikeHoltNEC  Рік тому

      OMG… I did the same thing and tripped a 800A main. Freaky if you don’t understand, and I didn’t understand.

  • @vivianledonghae4eify
    @vivianledonghae4eify Рік тому

    Mike, you are basically A living NEC book;)!

    • @MikeHoltNEC
      @MikeHoltNEC  Рік тому

      Just what I do everyday to help others.

  • @bitzyc5308
    @bitzyc5308 29 днів тому

    here in europen the manufacturers of the brakers will also give a table with the selectivity of the brakers froma certain type of product, starting from the smallest to the biggest in that type, and the relation between them. u will get a table of the values of the current foult for witch, let say a 16A braker it will trip before a 25A or 32A and so on ..

  • @christheother9088
    @christheother9088 Рік тому

    A main breaker in the panel seems very handy until you learn they may not reset if finicky.

  • @jolyonwelsh9834
    @jolyonwelsh9834 Місяць тому

    Sounds like the straw that broke the camel's back so to speak.

  • @stevewhite4598
    @stevewhite4598 Рік тому

    Hey Mike... I just wanted to ask whether 408.3A(3) is meant to apply to panelboards as well. Please respond. Thanks.

    • @MikeHoltNEC
      @MikeHoltNEC  Рік тому

      I don't see 408.3(A)(3)...

    • @MR-backup
      @MR-backup Рік тому

      What cycle are you using?

    • @MikeHoltNEC
      @MikeHoltNEC  Рік тому +1

      More importantly what cycle are you using?

    • @ngrogan93
      @ngrogan93 6 місяців тому

      408.3(A)(3) was in the 2017... it is now 408.3(A)(2) in 2020, since our jurisdiction is using this cycle now. Just an fyi if it helps. Cool video. Thank you for your continued knowledge @MikeHoltNEC. I will apply it to my study.

  • @Nobo35
    @Nobo35 8 місяців тому +1

    I’m still not sure how you selectively coordinate

    • @MikeHoltNEC
      @MikeHoltNEC  8 місяців тому +3

      Neither do I. This is an engineering design issue by those that are trained in this field.

  • @TwinQuan
    @TwinQuan Рік тому

    Mike, whats your diet like? You are looking young.

    • @MikeHoltNEC
      @MikeHoltNEC  Рік тому +1

      I'm not a 'food freak,' I just try to avoid process foods and fast food joints. I love my steak and ribs!

  • @raymonddonovan3297
    @raymonddonovan3297 Рік тому +3

    What is the point of this video? It is just a 15 minute explanation of what selective coordination is. There was 2 minutes of information that was repeated over and over. I feel like I’m missing something.

    • @MikeHoltNEC
      @MikeHoltNEC  Рік тому

      Nope you didn’t miss anything…

    • @3yolafeddy654
      @3yolafeddy654 Рік тому +1

      I feel like you act like this at work!! If this video isn’t for you, just move on. Sometimes people like to listen to discussions, there is a new electrician studying everyday. Get an attitude adjustment bud

    • @raymonddonovan3297
      @raymonddonovan3297 Рік тому

      @@3yolafeddy654There is much more free will involved in watching a UA-cam video as opposed to having a conversation at work, which makes the two less than comparable.
      Nevertheless it is true, I do act like this at work. I make a point of being effectual and efficient with language during my discussions of technical matters. It is not considerate to burden people with casual banter of dry topics when there are so many more impactful things to be discussing.
      Another bad habit of people particularly in corporate America in the desire to say words and sentences with no meaning, particularly during company meetings. It too is a burden to everyone involved, and makes leaders look desperate and foolish.
      Death and life are in the power of the tongue: and they that love it shall eat the fruit thereof.

    • @3yolafeddy654
      @3yolafeddy654 Рік тому +2

      @@raymonddonovan3297 your banter burdens people in life, and now on the internet, get a grip. Lay off the pvc glue

    • @allentisthammer4763
      @allentisthammer4763 5 місяців тому

      Ah yes, another of my people!

  • @REG3305
    @REG3305 Рік тому

    Very interesting. Not something engineers are likely to cause, more so to be caused by cheap product purchasing by the electrical contractor.

    • @MikeHoltNEC
      @MikeHoltNEC  Рік тому

      The electrical contractor just installs what the engineer specs out. If the engineer wants a 'selective coordinated system' then it needs to be designed for that feature.