How Submersible Pump Run by Smarten Superb 2500 va Inverter by LOOM solar 440 watt x 2 Panel.
Вставка
- Опубліковано 2 жов 2024
- This is information how you run your submersible pump with your 880watt bifacial panel. Important things to be consider before run your pump.
some solar system product -
loom solar 440watt bifacial panel-amzn.to/3tlYWK8
smarten inverter-amzn.to/3yQOBHj
smarten charge controller-amzn.to/3jQu6pN
Dc wire-amzn.to/3hbhcky
mc4 connector-amzn.to/3BJS108
dc clamp meter-amzn.to/2YAXubB
dc mcb-amzn.to/38KZy2D
bit.ly/3jVQWuY
solar Bifacial Panel-bit.ly/3AHAIfW
Solar Stand-bit.ly/3AKLZMx
Solar Inverter-bit.ly/3xHlDcd
Lithium Battery-bit.ly/3xL4j60
Solar DC wire-bit.ly/3jV1Ocy
All Solar Panel-bit.ly/2VLXioY
Charge Controller-bit.ly/3xERURn
Street Light-bit.ly/3m351cO
Inverter with Storage complete system-bit.ly/3m2q0N4
Installation kit( mcb/wire/meter/connector)-bit.ly/3jVIUSO
सही जानकारी दी आपने, धन्यवाद।
Sir you need to add 2 more panels to run your 1HP pump
1 HP Pump running ampere is from 5 to 8 A
This will take 1000 to 1700 watt load not 746watt
You have only 880 watt panels
It is taking extra power from battery, if you have sufficient solar power than battery volt will not be decrease.
It is maximum capacity to taking load from battery is 70A
You can calculate load capacity as given below
Battery V 27*70A= 1890W
Battery V 26*70A= 1820W
Battery V 25*70A= 1750W
Battery V 24*70A= 1680W
Battery V 23*70A= 1610W
Battery V 22*70A= 1540W
We can run 1 HP Pump in day time when Solar power is available
You need 1500 to 1800 W panels for 1HP pump
Absolutely correct and after some time it will shows 100% load because battery voltage is decreasing but required power remains constant. That is why for that time being load is increased compared to previous time.
Hello sir thank you for this information.. I have one question if i want to run 1 hp sub. pump on just one battery without mains then how much watts panel we required so that i can run this pump for 1000ltr tank twice in a day.
2.5kva = 2500*0.8 ( Power factor ) =2000 Watts
I think Maxim carrying load is 2000 watts for only for short period for this inverter but if for want to continuously run appliances on this inverter u have to only count 40% to 50% efficiency of peak power handling that is average from 800w to 1000w maximum beyond that it will show overload due to over heating in components then it automatically shut off .
If u want to continuously run a desired peak load continuously then u go for 12v = 1000Va = 400w continuous load
24v = 2500va = 1000w max continous load
36v = 3500va = 1500w
48v = 7000va (max @ 48v ) = 3500 w
I think above maximum values for safely continuous operation of inverter otherwise the inverter component life will decrease or it may damaged early
thanks for comments sir.. thanks for your valuable information
VA. AC voltage ka hota hai , DC ka nehin
Nahi bhai esa nahi hai ye inverter 1400-1450W tak load chala leta hai without overload . And auto shutdown 1600W par ho jata hai toh 2000W k load toh ye 1 sec bhi nahi chalata hai and ye load increase iss liye ho raha hai kyoki dhere dhere se battery ki voltage kam hoti jaa rahi hai . 1HP pump 746W nahi balki 1300-1400 W load leta hai kabhi check kar k dekh lena
2hp submarsal pump run karne kai liye 4 kva smarteen mppt inverter sai kiya chalega??
Use copper motor pump. Aluminum motor pump draws more and more ampere the longer you run it.
Brother mere pass waree535 watt bifacial ke 3 panels hai to kya 1hp submersible pump acche se chal jayega . Approx 1600watt ka system ho raha hai ?
surely sir.
4 panel 540watt
Parfact run moter
1HP pump 746W nahi balki 1400-1500 W ka load leta hai kabhi check karke dekhna meter se . And load % iss liye increase hoo rahe hai because battery k voltage dhere dhere se kam hote ja rahe hai 23.8 se 22v tak aa chuke the . And tumhare solar panel 647W produce kar rahe the 1 panel or laga lo yehi pump 40 Min tak aaram se chalega fir or 1 hour tak bhi chal sakta hai .
And 1 more thing ye jis model ki Exide ki battery hai tumare pass se bhot local quality ki hai . 1 youtuber ne sari battery test kar k dekhi thi toh ye model baki se half hi backup deti hai and same inverter bhi test kiya tha 1500W tak chal jata hai without overload
Vaia, mera pump havells ka 1.5hp ka hai. Lekin Power consumption 1.1 Kilowatt hai. Toh kia smarten ka ish inverter mera pump ko Chala payega? Mera 2 battery Luminous ka hai. (150ah+150ah)?
Sir,
Is this inverter capable to run 1.1 KW load? As I have Havells 1.5HP pump which is 1.1KW.
अब कैसा चल रहा है आपका सेट । कोई वीडियो नहीं आई बहुत दिनों से।
sorry sir, thodi busy tha..video ayegi.
Aapne kaunsa company ka pump use Kiya Mera Ghar mein yah inverter he Magar Kam nahin karte Mera battery c 20 ka he Shayad vahi Karan hoga please reply me thank u dhanyvad
thanks for comments sir.. sir me CRI company ka pump use karta hoon. suraj ka shine accha hone chaiye pump chalne ke liye.
@@NSSOLARENERGY thank you sir battery c-20 hone mein koi dikkat nahin hai kya yah achcha inverter he me 1 sal se esthimal karthahnm achcha chij hai
Sir battery drain hone ki wajah se
स्मार्टन 3050va सबसे घटिया प्रोडक्ट एप्रो 3000 va इसका बाप का बाप है.
ग्रेट से शेयर चार्जिंग करता है क्या
Ji !
Sir viraj solar pcu 2.5kva acha hoga?
thanks for comments sir.. i have no idea about viraj pcu. go for any branded pcu for long lasting
Viraj mere pas h smarten or viraj me jaada farak nahi h maine viraj pe 2000 watt load test kiya h aaram se chalta h i think smarten bhi itna load le lega.... Baaki quick fix tech pe dekh lo viraj k baare me..
Ghatia smarten 2500inverter.in 4 months 2 connectors brunt and now my 2kva solar system is now useless as it's not working as inverter is not working due to connector brunt.because of bad service.once connector brunt means u have to wait for 100rs connector by courier that takes 20 days.after that their technician comes after one. Week..this is horrible after sell service .i m sure all will suffer who purchased this device.sasta cheez hamesha bakwaas hota hai.. technically igbt controller is missing costing 7-8k here they did 200rs relay changeover switch.. As o cheap.even one standing fan 3500rs now brunt due to low voltage.this is a huge loss.u keep solar system for future but not with this bakwaas inverter.do not buy this device.after sales service is horrible.u have to wait for one month.
thank for sharing your information to all.but till now i don't face any problem like u in my any customer.
if you don't mind , can u share your details connections of solar panel with this inverter.
@@NSSOLARENERGY 4x440 watt bifacial panel.load is max 40-50% in daytime.i m using changeover switch which chages around 9.00pm as battery drains out by that time and reconnect at 6.00am.
Sir meri 1hp ka submersible pump stating load 10amp Or raning load 7amp sir smartan 2.5kva my college?
Thanks for comments sir
Nahi chalega
Minimum 1000w pannel lagana hoga, bifacial ka back site generation ka koi guarrenty nehin hota hai. You have to add 1 more pannel
Thanks for comments sir..sahi he
Yes if you add 1 more panel than it should easily run 40-60 min
Sir mera 1hp havells ka submersible start krta hu to voltage 190 aur amp 10 ho jata hai jisase overload ka beep aane lgta hai.
Maine 150mah ki 2 battery lagyi h aur pannel 150 watt ke 2 hai.
Plz solution bataye.
Apka inverter ka details boliye.
@@NSSOLARENERGY smarten 2500 mppt
Sar 6penal 2+2+2+ka सीरीज sirij kaneksan पोली poli 320 war ,, Yes ya Rong jabab Dena जी
Ager panel bda diye jaye to chalega sahi ya tb b yahi problem krega plz reply
aram se chalega. I have installed it to one of my customer
Heating k karn ho skta h sir.. Kyuki electronic component heat jab hota h to efficiency kam ho jati h... To muje lgta h yahi karn h load bhadane ka... Dusra karn y b ho skta h ki battery ki voltage kam hoti h tab b load badta h...
Sir,mera loom Shark ( 440x2)=880 + Vikram mono (370x2) =740=1620watt panel hai. Isko parallel lagake Smarten superb 2500 contact kiya.lekin Dc Mcb bar bar trip kor raha hai.kitne ka Koun sa DC Mcb use korunga please boliye.
thanks for comments sir. sir ap kitne amps ka dc mcb use kar rahe he? uske jada capacity ka use kijiye
@@NSSOLARENERGY Sir link share kor dijiyega Mcb ka, 32 amp use kor raha hu
@@MrSanat2012
U have to use 50 amp dc mcb for smarten 2500 va 50 amp solar charge controller.
It actually depends upon what solar charge contrer associated with your solar pcu.your four panels at least generate 40 amp current in sunny day but u have used 32 amp mcb how can it works?? So change mcb immediately.
@@debabratamanna9087 Thank u Sir.
63a 500v ka dc mcb lijiye
1hp pump aap 880watt pannels run karke dhikhya . 15 minutes chalaya .then it shuts off.if u instal 440w x 4 panel will it runs continually.hav u tested it.if so kindly reply me .
Thanks for comments sir..it is easily run..As it is installed one of my customer house..
Sir manelingh disble keshe kare. Day me
Voltage drop hone se amp badh jate hai esi liye over load bata raha hai
1 hp submersible 746 watts but you have to consider power factor of motor which is around 0.72 in case of submersible so power is around 1000 to 1100 watt. Smarten 2500va should handle load around 1500 to 1800 Watt. In your case it should work as you are already successful with surge power of motor dont know what happens with continuous load. This is quite surprising
Thanks for comments si
Because after some minutes battery voltage is drop 23.8 to 22v that's why inverter give overload sine and this 1HP motor cunsume 1300-1400W electricity
Agar hum 4 pannel Vikram ke 445 wat ke lagaye to kya aram se chalega din me overload to nahi batayega sirf one hp moter chalayenge jis time baki load band rahega
4 panel se 1hp pump easily run karega
Aapka solar se 330 watt aa raha hai to inverter to band ho hi jayega
Thanks for comments sir.
Why your load going to 100%. Smarton 2500 load capacity is 1600w+
Thanks for comments sir...as i have installed only 880 watt bifacial panel on it..
Sir mera issue same hey.maine 1600 watt ka panel lagaya or load hey 1ton 5 star AC.kya reason hey overload dekhatahey mujhe
ज़मीन के निचे पानी धिरे धिरे कमने के कारण लोड बडता गया है कुछ समय के बाद फिर ठीक से पहले जैसा ही चलता रहेगा
Thanks for comments sir..I am not sure regarding your thought.
Sir ya Cooper ma hai ya phir aluminium me hai please reply
thanks for comments sir..sir es inverter ka winding copper ka he
1500 wt ka induction chalega ??
thanks for comments sir.. Sir isme induction oven aram se chalega, lakin oven ko on karne ke bad oben ka wattage ko kam kar dena parega upto 800watt-700watt. isme apka cooking aram se ho jayega
Loom Solar panel is the most faltu panel in india.😡😡😡😡
Go for WAAREE, ADANI , VIKRAK SOLAR, LONGI , TRINA, CANADIAN SOKAR. They are top class quality cell , globally.
Sir viraj 2.5kvs solar pcu Acha hoga?
no idea sir..Go for good brand sir
₹29000
আপনার ছবিটি চেঞ্জ করবেন
thanks for comments sir
ভাইজান স্ট মার্টিন এর 2.5kv আমি একটা অর্ডার করেছি
Battery low ke karan
Thanks for comments sir
bhai solar km hai apka 2 panel or lagayie
thanks for comments sir. ha sir hamko malum he or do panel lagane se sob ho jayga, lekin 880 watt bifacial se kaise pump chalta he ohi dekha rahaha hoon..
sir apki bettery ki gravity v down lagti hai km panel k karan gravity check kijiye 1200 plus honi chahiye
apki ki bettery bakup 10 %hi de rehi hai iski gravity check krayiesir
100 per load pe kitna watt hota hai?
2100 watt
Sorry 1800 w
Sir no kya h aap ka
Total price 2.5kva
Thanks for comments sir..The price of 2.5 kva inverter is 14500/- to 13800/-
SMARTEN 24 VOLT MPPT KOI FAIYADA NHI BECOUSE OF LOW VOC RANGE AND 1 TON AC LOAD TEST RUNNING TIME AND 1.5 TON 5 STAR AC LOAD TEST AND RUNNING TIME
Thanks for comments si