DOD SETTINGS OF SMARTEN SUPERB 2500VA Inverter. Solar hybrid inverter. solar panel. Inverter Setting
Вставка
- Опубліковано 2 жов 2024
- this is all about DOD setting of smarten superb 2500 VA inverter.
loom solar 440watt bifacial panel-amzn.to/3tlYWK8
smarten inverter-amzn.to/3yQOBHj
smarten charge controller-amzn.to/3jQu6pN
Dc wire-amzn.to/3hbhcky
mc4 connector-amzn.to/3BJS108
dc clamp meter-amzn.to/2YAXubB
dc mcb-amzn.to/38KZy2D
bit.ly/3jVQWuY
solar Bifacial Panel-bit.ly/3AHAIfW
Solar Stand-bit.ly/3AKLZMx
Solar Inverter-bit.ly/3xHlDcd
Lithium Battery-bit.ly/3xL4j60
Solar DC wire-bit.ly/3jV1Ocy
All Solar Panel-bit.ly/2VLXioY
Charge Controller-bit.ly/3xERURn
Street Light-bit.ly/3m351cO
Inverter with Storage complete system-bit.ly/3m2q0N4
Installation kit( mcb/wire/meter/connector)-bit.ly/3jVIUSO
Bhai aap kahne ka matlab kya hei???? Agar mei grid charge off kar rakha hei aur mei koi bhi for example 40 % kar rakha hei, kya mei 40% battety consume karne ke bad fir main light se battery charge hoga ya ghar ka connection main light mei hoga???? Agar battery fir charge hoga to fir grid charge off kis kaam ke liye hei???
Kahna kya chahte ho 😂
Bhai mera 2500 va wala sham ko har roz restart hota hai ek baar jaise he dhoop khatam ho jati hai. Iss se pareshani hoti hai kyuki iss se connected router b fir restart hota hai light jane par. Kya ye issue sabne hota hai?
Everything is fine , voice not clear
And there is a option that grid charging disable. Then how it will take charge from main line
Sir, I would like to consume more power from solar.if I fix DoD 50% after sunset is it run up to 11volt of battery and then charge from main? If I fix Charge from main Disable is it automatically charge from main when battery volt is 11
thanks for comment sir...when you set DOD 50% , then your main will automatically connect to inverter if your battery voltage is 11v or more.(for 24 volt system it will be 11x2=22volt). consumption of solar power is another topic. Your inverter is always use max power from solar, rest amount will collect from main grid. and connect and disconnect of main with inverter will depend on your DOD settings and battery voltage.
@@NSSOLARENERGY sir if the grid charging is off and i set 50% dod. Then whether it will charge the battery after 50% dicharge of battery???????
Sir ye inverter kaisa h.. Aur ktna load kya kya chala sakte h.. Kya 1.5 ton inverter ac chal sakta h.. Kya ye inverter solar k liye best rahega. Plz riply..
thanks for comment.. sir isme apka 1.5 ton ac nahi chalega. 1 ton ac chal shakta he. is range me e apka best inverter he
Emi par mil jayega kya
अबे तुझे कुछ नहीं पता
तो खुद नहीं जानता
पता नहीं क्या क्या बोल रहा है👊
Very informative vedio
Is this possible to compensate load without battery and only on solar panels and grid
In day time
Actually dod setting use to control the connection the main grit line with our inverter in day time. That means how long inverter will take supply current from to charge you battery
Kuchh bhi samaj nhi aaya
सर 2500 एम पी पी टी में आटो कट कितने वोल्टे पर है 🙏🙏
28पर मेरा तो मैन डिस्कनेक्ट हों जाता
Bhai bihar siwan me established ka kya cost padega
Inverter ki battery jb bilkul down ho jaye tab mains se charge ho uske liye konsi settings krni hogi
Bhai ye btao agar hum chahe ki poori raat battery se power de grid km se km use kre to dod 50 rakhni h ya 20%
Mere pass 2500va model hai.iska piche ka 50amp connector 4 mahine mein 2 baar jal gaya aur mera system 1 mahine se shutdown hai.100rs ka connector ko inn logo ne courier karegenege aur 15 din laga denege..do not purchase this device.if you are ok with system shutdown for 1 month or so buy this cheap device.go for Nexus or some other brand.
How 12 v battery 40%dod voltage it's 7.2 how you are saying 11.5.
Mera invrator beep kyo krta ha full charge ho jane pr or backup nhi de raha ha thik se
Sar maine abhi solar panel Nahin lagvae hain mera inverter manpower se hi chal raha hai to kya ismein DOD set karna padega
Sir aap ye batayye ki smartan2500va ka chaging & discharging seting kaise kre
सर sar mene 2+2 ki sirij me lggya 6penal 320vAt ka
Sir i have 100 ah lead acid battery and 40 ah tubular battery . I had connec it in series with mppt but it is draining in 5 minutes . After full charge also. Why
Sir back-up to app ko 40ah k hi milegaa ager app dono battery 100ah ki lagao gae tb backup bad jaega
sir mere pas 3050va inverter or 4×400 mono panel and 2×200ah ki battery....sir mera que. ye h ki mai night me battery se maximum backup lena chahta hu ...so mujhe dod setting kitni set krni chaiye...plz reply
20
The DOD is not working correctly in my Smarten Superb 2500 VA. I have two 24V battery connected and the DOD set to to 50%. So the battery should be charged from Mains only when the VBatt goes around 22V but when it is less than 27V itself it's charging.
Thanks for comments sir...as per your comments your inverter's DOD working properly. If u set your DOD upto 50% your main will automatically connected when your battery voltage 22v. So your battery is 27 v so it will connected . If u want to connect your main less time with inverter then set 20% or 30%. in case of 20% main will connect only battery voltage 25v .
@@NSSOLARENERGY Thanks for your quick response. I am a consumer and new to these technical terms. My understanding was if the battery voltage is less than 22V the battery capacity is low then it should connect from Mains. If i set to 20% can you explain how it will connect less time with Mains?
Night m load kese chlta h
Sir mere pass smarten superb 2500 inverter h or waree 335 watt ke 4 Polly panel h kya me waree ka 445 watt mono crystalline 1 panel connect kar sakta hu kya mono or Polly ko eksath connect karne par koi lose hoga plz reply and make a new video on Polly and mono both connection
Thanks for Comments sir. sir poly and mono ek sath add na karnai acche he. actually dono ka VOC , VMP alag hota he.
sir apke pass already 4 nos 335 watt panel he, so 4x335=1240 watt he, as per company recommendation max pv voltage support by inverter is 1500 watt. so mere hisab se 445 watt panel na add karna acche he..
@@NSSOLARENERGY sir 335×4= 1340
335 ek or Polly aad kar sakte h kya?
hmm.. you can add..
@Soul Feeder thanks for information..
Sir apko itna sob kuch knowledge he to please smarten company ko boliye . O logoko uska user manual change karne ke liye.. company ka products manual me clear sob kuch dia hua he.. max pv wattage support 1500watt. So how can ignore this.. ap to bohut kuch karsakta he sir.. to company ko boliye user manual change karne ke liye.
Agar jada panel add korne ke bad machine jal gaya to koi warranty claim nahi kar payenge...e batt dimak me laylieje.
नमस्कार सर, मेरे पास 2500va superb mppt मॉडल है। इसमें कितना DOD सेट करू। यानी आप DOD की सेटिंग बताए। PLEASE।
30% set kijea sir
भाई जी मैंने हाल ही में स्मार्ट टन एम पी पी टी 2500घर पर लगाया है बिजली बिल ज्यादा आता है घर पर 4पैनल 335वाट के लगाए हैं अब आप इन्वेंटर की DoDसेट कितने पर करनी है आप इसके बारे में जानकारी दो बिजली बिल कम हो जाए🙏🙏
ap agar apka inverter ka DOD 20%korenge to main se sob se kom current lega. or ap agar 50% korrnge to apka inverter max current lega main line se.
ap mera circuit diagram video dekhea or change over switch se connection kijie , main line k supply off korke rakhiea. issea apka faida hoga
Total Kitna kharcha hua
Can we set dod to 80percent , 5kva smarten solar inverter.
No
Battery se raat me 80 percent backup lene ke liye kya setting karni hogi
Mere yaha bijli nhi (off grid ) hai only solar se he charge hota hai
Ap ke pass agar off grit he, to dod setting ka kohi jorurat nehi he, baki setting same hoga
@@NSSOLARENERGY thankyou sir
Smartron ka 2500 hia solar se kitne 200 ah ka 2 battery hai kitne ampere se charge Hota Hai
thanks for comments. sir apka panel se jitna ampere milega usme e charge hoga. Agar ap inverter ko mein line se charge korenge to 15 amp charge leta he
Sir mere paas light ka conection nhi he to dod thode hi set krna pdega
dod ka jururat nahi apka
Aap Agar practical Mein dikhte To Achcha Hota .
Thanks for comments sir..i will be do is as soon as possible
Not clear
Kya bolu raheho kuch bi samaj nahi aya...
Slowly explain karo bhai
Thanks for comments sir.
Night time dod kam nahi krega
Thanks for comments sir, kaam karta he...ap apka DOD % change korke dekhiye with battery voltage..
Can it run 1hp motor
Yes ..it can with min 1kw solar system for some time (10-20min) that is totally dependent on you solar power generation . if you run for continuously then you have required a VFD.
Not all pump only some pump 😂
आपने वहुत अच्छी प्रैक्टिकल जानकारी देते है । आपका वीडियों अक्सर देखता हूँ । डी0ओ0डी0 के सम्बन्ध मे आपने वहुत अच्छी जानकारी दी है । धन्यवाद । आपसे एक रिक्वेस्ट करनी है कि यह जो 24 वोल्ट के इनवर्टर होते है उनमे 2बैटरियों को सीरिज मे लगाना पड़ता है ।दो बैटरियों को पैरलर मे जोड़ने पर उनकी क्षमता मे कोई कमी नही आती है जबकि इसके विपरीत सीरीज कनेक्सन मे समय के साथ दो बैटरियों मे से एक की क्षमता धीरे धीरे प्रभावित होने लगती है । इस दिशा मे टैक्निकली क्या काम किया जाना चाहिये । कृपया इस पर कोई वीडियों बनाने का कष्ट करे ।