Zs and the 80% RULE. What is it and understanding the differences between Tabulated and Measured

Поділитися
Вставка
  • Опубліковано 28 гру 2024

КОМЕНТАРІ • 156

  • @learnelectrics4402
    @learnelectrics4402  3 роки тому +4

    SEE ALL VIDEOS - To view a list of all our LearnElectrics videos, click on the link below.
    There are many videos on many electrical topics including Installation, Part P, 18th Edition, Testing, Certification, Lighting, Sockets, Ring Circuits and much more.
    ua-cam.com/channels/YaJQnpO4XAp0yCgqzMkmfA.html

  • @mattheww3116
    @mattheww3116 Рік тому +5

    You have saved me! I'm revising for my C&G Level 3 exam, there's no way I would pass without an understanding like the explanation in your video. Subscribed, and shared with the rest of my class.

    • @learnelectrics4402
      @learnelectrics4402  Рік тому +1

      Glad I could help Matthew, that's what they are there for and thanks for sharing the channel with the class. I really appreciate that. Good luck, keep learning, it's a good trade - it's taken me around the world working. Dave.

    • @learnelectrics4402
      @learnelectrics4402  4 місяці тому

      Thank you, appreciated. Really appreciated. Dave.

  • @amberrose6827
    @amberrose6827 2 роки тому +6

    These videos are SO HELPFUL! They make confusing subjects easy. Thanks for all your hard work putting them together

    • @learnelectrics4402
      @learnelectrics4402  2 роки тому

      Glad you like them Amber and thanks for watching. The more people they help, the better. Dave.

  • @xtiberiu
    @xtiberiu 2 роки тому +4

    It really helps me to understand all the misunderstandings from class, your videos are so clearly explained ...
    I love what you're doing, please keep the good work up !
    Thank you so much, Dave.

    • @learnelectrics4402
      @learnelectrics4402  2 роки тому +1

      Thank you Tiberiu, much appreciated. Lots more to come.
      Dave.

    • @jameshansing5396
      @jameshansing5396 Рік тому

      Agreed. That's what I use the videos for! :)

    • @ahmedalazazi2895
      @ahmedalazazi2895 Рік тому

      @@learnelectrics4402 many thanks to you
      It’s really a great job
      Can you please tell me how to get the Ze?

  • @kbagheri9026
    @kbagheri9026 4 місяці тому

    absolute pleasure to see these videos. You are so good at explaining these topics. Thank you Dave❤❤❤❤

    • @learnelectrics4402
      @learnelectrics4402  4 місяці тому

      Glad you like them and lots more to come. Thank you. Dave.

  • @nabilbekhli6840
    @nabilbekhli6840 Рік тому +1

    That was an excellent explanation, thanks so much

  • @NaseerAhmed-sx1dk
    @NaseerAhmed-sx1dk 2 роки тому

    All tangled up wires in my brain opens one by one easily after watching your video.
    Respect

    • @learnelectrics4402
      @learnelectrics4402  2 роки тому

      That's fantastic to know Naseer. The videos are doing their job. Thanks for the support and keep watching, lots more to come. Dave.

  • @linksone6287
    @linksone6287 Рік тому

    Honestly gent! I wish I could embrace your gratitude to us by meeting you! It’s goes without saying; how much you’ve helped us.! Absolute genius you are. Thank you so much! 💯🙏🏽

    • @learnelectrics4402
      @learnelectrics4402  Рік тому

      Great feedback and truly appreciated comments. Thank you. Dave.

  • @matthewcox6490
    @matthewcox6490 Рік тому

    just passed my 18th edition, and in July 2023 these video's are still as useful as ever!

  • @TP-jm2gy
    @TP-jm2gy 2 роки тому +1

    I've worked in Engineering Technology (Electronic/Robotics) for years, but until recently with the Regularisation of my house wiring, never needed to fully grasp up-to-date wiring regs! Chanced on your video series today and would just like to say they are excellent - now fully understand why the electrician suggested using a lower rating MCB for the 1st-floor circuit and that checking the quality of all my socket Live and Earth (R1 & R2) connections might well find a reason why the Zs is on the high side. Many thanks for this and all the other videos - HIGHLY RECOMMEND 🙂

    • @learnelectrics4402
      @learnelectrics4402  2 роки тому

      That's great to hear. Really appreciate your comments. Dave.

  • @Chrisking85
    @Chrisking85 Рік тому

    oh my god. thankyou so much. your teachings are taking my learning to the next level

  • @AngelaPeters-fy1tc
    @AngelaPeters-fy1tc Рік тому

    Fantastic i took notes and paused and took photos then i will print them out and put in my file as im so determined to learn. Superb explanation, and watching once isnt enough but its great when you finally get it. Really enjoyed this thankyou.

    • @learnelectrics4402
      @learnelectrics4402  Рік тому +1

      That's how I learnt in the days before the internet. I took notes and made drawings of everything until it stuck. Keep going, keep learning, its a great trade to be in and you have the right attitude to make it. Good luck. Dave.

  • @joto4587
    @joto4587 Рік тому

    Super useful as usual! Thank you for your efforts and an in-depth explanation.
    The only things the pages are different now in the actual BS7671 and On-Site Guide.

    • @learnelectrics4402
      @learnelectrics4402  Рік тому

      Glad it was helpful, yes, this video uses the blue Regs book and OSG. But what an excellent opportunity for me to rewrite and improve the video to the brown Amendment 2 Regs.
      Thanks for bringing this up, appreciated. Watch this space, I'll get it done.

  • @beskras9266
    @beskras9266 3 роки тому +2

    What a great guy.
    You make it so simple to understand and absorb. Amaising learning videos. Thank you to Learn Electrics and the team behind this. God Bless.

    • @learnelectrics4402
      @learnelectrics4402  3 роки тому

      Thank you very much for the great feedback. Your comments are truly appreciated.
      Lots more videos to come. Dave.

  • @smail6594
    @smail6594 2 роки тому

    You are one of the best people in this world

    • @learnelectrics4402
      @learnelectrics4402  2 роки тому

      Nice of you to say so, thanks for the feedback and thanks for watching. Dave.

  • @krazylad84
    @krazylad84 3 роки тому +1

    Even if I know the topic , I always watch your complete videos as there is always something new to learn. Thanks

    • @learnelectrics4402
      @learnelectrics4402  3 роки тому +1

      Thanks for that. Watching the whole thing also helps me too, it moves the channel up the rankings. Great, spread the word my friend. Thursdays video all about calculating voltage drop and exam questions. Take care. Dave.

  • @Dog-whisperer7494
    @Dog-whisperer7494 3 роки тому +3

    So simple to understand when it’s explained in simple terms.
    Thank you Dave for another fantastic video 👍👍

  • @ScottZimmerman-s1r
    @ScottZimmerman-s1r 8 місяців тому

    Hi Dave. You mention the 0.8 factor to be because of the fluctuations of temperature due to weather. But in the 18th edition Regs book page 410, it states it is a factor due to temperature increase from load current.
    Thanks a lot for your videos and help, Scott

    • @learnelectrics4402
      @learnelectrics4402  8 місяців тому

      Any reason or combination of reasons that affects the temperature of the copper conductors. thanks for the input.

  • @rowles13
    @rowles13 3 роки тому

    Great video pal.......great to have what I call a refresh regs video.

    • @learnelectrics4402
      @learnelectrics4402  3 роки тому

      Absolutely right. We all need a refresher from time to time. Thanks for watching. Dave.

  • @roystonpereira2887
    @roystonpereira2887 3 роки тому +2

    Wow, perfect timing, was doing this in class todaythank you🙌

    • @learnelectrics4402
      @learnelectrics4402  3 роки тому

      Excellent Royston. Glad it helped, spread the word; it makes it all worth while for me.
      Many more videos to come, Thursday's is about Voltage Drop questions for the 18th Edition and 2396 exams. Take care. Dave.

  • @paulcarroll7905
    @paulcarroll7905 Рік тому

    Really excellent videos, very clear and to the point. I very much appreciate them.

  • @hussmortada
    @hussmortada Рік тому

    Dave no one does it better! Thanks again

    • @learnelectrics4402
      @learnelectrics4402  Рік тому

      My pleasure Hussein, thanks for your continuing support. Dave.

  • @abrehamish
    @abrehamish 3 роки тому +1

    Thank you for your detailed explanation

  • @4addevelopments139
    @4addevelopments139 Рік тому

    Loving this channel. Thanks so much!

    • @learnelectrics4402
      @learnelectrics4402  Рік тому

      Great to hear that, thanks for your support, appreciated. Dave.

  • @johnkeys368
    @johnkeys368 Рік тому

    Very good explanation

  • @GregoryBryant-fj9bz
    @GregoryBryant-fj9bz Рік тому

    Hi Dave, at 1:50 you mention the current being 're-energised' when it passes from the neutral through the transformer winding and then down the phase again. Could you please explain a bit more about what you mean by the re-energising? I.e., what is the difference between the current between the neutral and the phase? With thanks.

    • @GregoryBryant-fj9bz
      @GregoryBryant-fj9bz Рік тому

      Worth also noting that the formula at 5:50 will produce the same value whether you multiply the voltage by Cmin before diving the sum by the fault current (as per the formula), as one would by diving the voltage by the fault current, then multiplying the sum by Cmin (your method).

    • @GregoryBryant-fj9bz
      @GregoryBryant-fj9bz Рік тому

      Further to this Dave, you describe the Max. Permitted Measured Zs as Zs(m), which is fair enough. When denoting on test sheets, how would you then distinguish between a circuit's Zs that was measured using an MFT and that of a calculation from Ze+(R1+R2)? Typically, in order to check circuit functionality after re-energising, I physically measure the Zs and have been calling this figure the Zs(m), but if just relying on R1+R2 obtained I call this Zs(c) for calculated - am I potentially wrong in this approach?

    • @GregoryBryant-fj9bz
      @GregoryBryant-fj9bz Рік тому

      For anyone wondering, you cannot just deem the max. permitted measured Zs to be a percentage of the raw value. It is typically 76-77% but it doesn't exactly match up to the figures provided in the books, as there is presumably an element of rounding down.

    • @learnelectrics4402
      @learnelectrics4402  Рік тому

      The IET will always round to two decimal places. You've missed a step out here, take a look at the video that comes out next week. Thanks for the input. Dave.

  • @mrtennents2924
    @mrtennents2924 Рік тому

    Thanks for all your help

  • @garyplant487
    @garyplant487 3 роки тому +1

    Great video again Dave, well written and explained. Another A*

    • @learnelectrics4402
      @learnelectrics4402  3 роки тому

      Thanks Gary. I'm collecting these A stars and hoping they translate into a few beers when I get to Spain. Lots more to come my friend. Dave.

  • @pinchermartyn3959
    @pinchermartyn3959 2 роки тому

    Very good. So useful and educational. Awesome material.

  • @robertwainwright5441
    @robertwainwright5441 Рік тому

    Great video as usual 👍

  • @train4905
    @train4905 10 місяців тому

    Wow outstanding sir,😊

  • @matthewparkinson7730
    @matthewparkinson7730 Рік тому

    Thank you for all your hard work.
    At 7.45 you mention that the tabulated values in BS 7671 are set at 20 degrees. I also thought that the zs values in BS 7671 where set at 70 degrees, then the values in GN3/OSG where set at 20. Due to the temperature on site etc.
    Please could you outline if I am wrong and where it started 20 degrees in BS 7671.
    Thank you for your time.

    • @learnelectrics4402
      @learnelectrics4402  Рік тому

      70C is the maximum, the limiting temperature. In order not to exceed the Zs max at 70C, what should the Zs be at 20C as it will increase in ohms as the temp rises. Hope this helps.

  • @AndrewCook7
    @AndrewCook7 Рік тому

    Hi Dave. What is the rule of thumb 1.2 value used for

    • @learnelectrics4402
      @learnelectrics4402  Рік тому

      1.2 or the 80% rule is to make allowances for temperature variations in the copper conductor. As temperature goes up, the resistance increases which makes Zs worse or even unacceptable. By making the starting point 20% lower, we can be certain that even at 70 degrees C the Zs will still be ok. Hope this helps.

  • @fairisfairfairisfair9788
    @fairisfairfairisfair9788 2 роки тому

    Really appreciate this video...thank you so much...God bless you

  • @dimitrisblane6368
    @dimitrisblane6368 Рік тому

    Thank you. You make THE. BEST. VIDEOS ;)

  • @darrenglover2601
    @darrenglover2601 2 роки тому

    Brilliant 👌explained really well, thanks

    • @learnelectrics4402
      @learnelectrics4402  2 роки тому

      Glad it was helpful Darren, the video has done its job. Lots more to come. Dave.

  • @saeid6780
    @saeid6780 Місяць тому

    Thanks for your all effort ,I passed my 18th with getting help from your channel,however I found 2391-52 online exam difficult to pass,I’m wondering if there is any advice that might be useful to me to pass the exam xx

    • @learnelectrics4402
      @learnelectrics4402  Місяць тому +1

      Well done, brilliant. Learn a little every day rather than try to cram in lots the week of the exams. I've just come out of hospital but will be doing some more exam practice videos very shortly. Thanks for watching.

    • @saeid6780
      @saeid6780 Місяць тому

      @ Hello mate,hope you’re well. Sure I’ll do me best to pass and looking forward to seeing your next videos xx

  • @jamesw7624
    @jamesw7624 7 місяців тому

    Passed my 18th edition and 3 other exams. I failed my condition reporting and pat testing so I need to study some more but thanks for all your videos

    • @learnelectrics4402
      @learnelectrics4402  4 місяці тому +1

      Well done on the ones you passed. look on the others as a practice run. I used to draw the drawings from the books and label them. Throw them away and draw them again, throw them away and draw them again. You get the idea. Anything you think you are weak on, do this, over and over again. It works.

    • @jamesw7624
      @jamesw7624 4 місяці тому

      @@learnelectrics4402 passed my periodic exam today I’m so happy thankyou. I just need to do my practical assessment now

  • @Paul_Holmes
    @Paul_Holmes 2 роки тому

    That's a really helpful video, just like all of your others. The current returning from the transformer to trip the breaker has confused me though. Doe this mean that if there is an external PEN fault then the breaker will not trip? Many thanks.

    • @learnelectrics4402
      @learnelectrics4402  2 роки тому +1

      If there is a break in the PEN conductor you probably won't get much current to energise the house depending on the severity of the damage/fault. Yes, it could affect tripping ability which is why we do PFC tests. Thanks for asking. Sorry for the delay in answering, your question was in the spam folder, but can't see why. Dave.

  • @hamidbazmi7948
    @hamidbazmi7948 Рік тому

    Great video.
    Thanks

    • @learnelectrics4402
      @learnelectrics4402  Рік тому

      Glad you liked it, and thanks for the positive feedback. Appreciated. Dave.

  • @dennisfowler7873
    @dennisfowler7873 3 роки тому +1

    Another great video as usual keeping us all in tune...but does this Cmin * 80% applies to BS88 fuses or is there a different way of calculating its value...usually they are used for distribution circuits

    • @learnelectrics4402
      @learnelectrics4402  3 роки тому

      The Cmin and 80% values set the Zs resistance or impedance value which determines how much fault current flows. The manufacturer of any fuse or breaker will make their device blow at a certain amount of fault current. We use the Zs as a measure to check if this current will flow in this circuit. Just make the Zs right for the different fuse sizes and types and everything else will drop into place.

  • @robertpeters8531
    @robertpeters8531 2 роки тому

    Another excellent easy to understand video. Am I correct in thinking that every single circuit has an existing zs value and any addition or alteration may alter or affect the Zsm value of said circuit. Cheers Dave.

    • @learnelectrics4402
      @learnelectrics4402  2 роки тому

      That's correct. The circuit max Zs is determined by the circuit breaker rating and type. Any measured values will be affected by additions and alterations. You can't change the Zs for a particular breaker but you can change the breaker to alter the permitted max Zs for the circuit. Going down in breaker size will increase permitted Zs max. Hope this helps. Dave.

  • @truthwillout7909
    @truthwillout7909 2 роки тому

    Brilliant, explained clear and concisely, many thanks.

  • @highhurstfarmandholidaycot526
    @highhurstfarmandholidaycot526 3 роки тому

    Excellent video. Many thanks.

  • @mundent
    @mundent Рік тому

    Looking at the table, it takes 160a of current to trip a 32a breaker. Why doesn’t the cut out fuse blow when the fault current flows through it before it gets back to the breaker.

    • @learnelectrics4402
      @learnelectrics4402  Рік тому

      The cut-out is a part of a distribution circuit so a much slower response time. The breaker has tripped in less than 0.4 seconds so the cut-out just settles down again. hope this helps, good question. Dave.

  • @Hossin-x3i
    @Hossin-x3i 4 місяці тому

    Thanks alot ..very useful

  • @addz91
    @addz91 2 роки тому

    On schedule of test results, do we put the maximum permitted Zs values in from BS7671 or values from the on site guide? Many thanks

  • @paulward143
    @paulward143 2 роки тому

    Really useful 👍

  • @malachygallagher4936
    @malachygallagher4936 3 роки тому

    Hi
    Very well explained as usual!
    Rgds mg.

  • @alextaramsari
    @alextaramsari 3 роки тому

    Thank you! Thank you! Is there anywhere you are teaching in face to face?? Please let me know! After 4 years in this trade I think I am start learning much easier and better with your videos! Please let me know where you are based?
    Best
    Ali

    • @learnelectrics4402
      @learnelectrics4402  3 роки тому +2

      Ali, great feedback, thank you so much.
      lots of people ask if I am still doing face to face teaching but the answer is no. Covid made the centre unworkable last year at which point I decided to put how I teach into videos. Hopefully you will still get the most out of them, especially the inspection and test videos.
      Thanks for your confidence in me and I will try my best to give you all the knowledge that I can. The secret really is to learn a little bit every day. By learning something for a few minutes at a time, perhaps 4 or 5 times a week, you give yourself the best chance of understanding and remembering. Good luck and take care my friend. Dave.

    • @alextaramsari
      @alextaramsari 3 роки тому

      @@learnelectrics4402 honestly Dave, I watch your video everyday on my way to work and coming back! It helped me to passed my AM2 and give me lots more confidence! I am also getting ready for my nic assignment again big thanks to you for your amazing videos! God bless you sir!
      Best regards
      Ali

    • @learnelectrics4402
      @learnelectrics4402  3 роки тому +1

      Ali, glad you passed your AM2, well done. Good luck with the NIC assessment. Don't forget we have a couple of videos on Part P and joining the schemes. They will give you some idea of what NIC expect from electricians. It all helps. Good luck and thanks for your support for the channel. Thursday's video is about voltage drop calculations. Dave.

    • @alextaramsari
      @alextaramsari 3 роки тому

      @@learnelectrics4402 youbqre star Dave! I already watch those videos but will do it again this week ✌🏼✌🏼🙏🏻

    • @learnelectrics4402
      @learnelectrics4402  3 роки тому +1

      Always learning, that is the secret. It's a good trade to be in, it's taken me around the world several times. Everybody everywhere needs a GOOD sparkie.

  • @jahanmoh
    @jahanmoh 2 роки тому +1

    you are a star

  • @markandrews8437
    @markandrews8437 3 роки тому

    Hi Dave another excellent video mate can I just confirm that I've absorbed this info with a zs reading we have taken EG: we have a 16amp type c 60898 mcb. from the regs book a zs of 1.37 has been found if I know take 1.37x0.8=1.09 i know take my measurement at fuse board and get a reading of 0.38 this falls under the 1.09 so is a pass . Sorry if this is coming across as a bit dim after your explanation just making sure I'm listening 👍

    • @learnelectrics4402
      @learnelectrics4402  3 роки тому

      Mark, thanks for the comments, great.
      Yes, type C breaker is 1.37 tabulated and 1.09/1.10 for measured depending which table you use.
      If you have tested correctly then 0.38 is a good reading.
      You don't say if it is a ring or radial but the two videos below may help to confirm your testing is all good. Thanks for watching and lots more on testing in the pipeline. Dave.
      Ring Circuit testing
      ua-cam.com/video/-PAruseUf04/v-deo.html
      Cable testing
      ua-cam.com/video/tT3eGK1b0Yk/v-deo.html

  • @sajad459
    @sajad459 2 роки тому

    The problem with time-current graphs of MCBs on BS7671 is that you can't read an accurate or even small range time for fault currents. For example when we consider a type B 10 amps MCB , we see that the knee happens at 50 amps but we read a time between 0.1 and 10 seconds , we can not detect the time. So we just can say that with multiple 5 of the nominal current, It will trip under 0.4s , but the graph gives us nothing.

    • @learnelectrics4402
      @learnelectrics4402  2 роки тому

      You are right Sajad. It is difficult to "guess" just where the line falls sometimes. Dave.

    • @sajad459
      @sajad459 2 роки тому

      @@learnelectrics4402 Thank you Dave, have a good weekend.

  • @todaysfigures598
    @todaysfigures598 3 роки тому

    thank you for the job done

  • @lemech
    @lemech 3 роки тому

    Hi Dave, if we have rcd installed, then even if Zs measured exceeds the 0.8 rule, it’s still a pass. Is this correct? Thanks

    • @huyongquan6554
      @huyongquan6554 3 роки тому +1

      If Zsm>((Zs41-Ze)/Cr@Tm)+Ze, In this circumstance, RCD replace OCPD'S ADS supply the fault protection.
      If Zsm

    • @learnelectrics4402
      @learnelectrics4402  3 роки тому +2

      A lot of sparkies think that if a 30mA RCD is installed then it doesn't matter if the Zs is over the stated figures on page 62 etc. as long as it is less than 1667 ohms.
      Two wrongs don't make a right.
      Table 41.5 on page 64 is for TT systems only, where it is known that achieving (say) 1.1 ohms is never going to happen because the earth path is soil not copper.
      The breakers and fuses are there for fault protection and the RCD for additional protection.
      For TNS and TNCS systems you should always get the Zs right.
      As an on-site assessor for one of the big boys, I would issue a non-conformance against your business if you tried to cover a high Zs in a TN system with the excuse of an RCD being installed.
      Hope this helps. Dave.

    • @lemech
      @lemech 3 роки тому

      @@learnelectrics4402 Thanks Dave, I agree. I should have included TT in my question. If it's not TT then it makes sense to get the value right regardless of whether RCD is installed.

    • @lemech
      @lemech 3 роки тому

      @@huyongquan6554 Thanks yongquan

    • @learnelectrics4402
      @learnelectrics4402  3 роки тому +2

      With TT systems, make R1+R2 right. In other words, what would R1+R2 be for a TNCS system. So, for a 32 amp breaker, Zs max is 1.1, minus 0.35 for Ze leaves 0.85 for internal wiring. If R1+R2 is less than 0.85 ohms then that is the best you can do. Even if Zs comes back as 200 ohms or 900 ohms, or whatever, you know you have done the best you can. Dave.

  • @huyongquan6554
    @huyongquan6554 3 роки тому

    0.8 is measured @ 10 degree, not 20 degree. You can check on OSG 3.
    From 10 degree increase to 70 degree, the resistance increase (1+(70-20)*0.4)/(1-(20-10)*0.4)=1.2/0.96=1.25. 0.8=1/1.25. That is why 0.8 produced

    • @learnelectrics4402
      @learnelectrics4402  3 роки тому

      Thank you Hu, great response. Dave.

    • @MS-Patriot2
      @MS-Patriot2 3 роки тому

      Hu, please can you explain the 0.4 factor and where in the OSG you make reference.

    • @huyongquan6554
      @huyongquan6554 3 роки тому

      @@MS-Patriot2 Please see OSG page 125 Appendix B first paragraph, p126 Note for the table B6, refer the 10 degree, page 132 note 1 indicate where the o.4 factor come from. So if we refer OSG B6 table, It is refer to the 10 degree. Regards

    • @huyongquan6554
      @huyongquan6554 3 роки тому

      Sorry the equation should be (1+(70-20)*0.04)/(1-(20-10)*0.04) , I made a mistake, It is not 0.4, it is 0.04 or 4%. Regards

    • @huyongquan6554
      @huyongquan6554 3 роки тому

      If Zsm>((Zs41-Ze)/Cr@Tm)+Ze, In this circumstance, RCD replace OCPD'S ADS supply the fault protection.
      If Zsm

  • @highgatehandyman6479
    @highgatehandyman6479 Рік тому

    3 cheers

  • @edh4808
    @edh4808 3 роки тому

    The measured values should be added in the table for ease? Anyone else agree?

  • @SSSwilliams
    @SSSwilliams 3 роки тому

    👍👍👍

  • @jezwarren-clarke2471
    @jezwarren-clarke2471 Рік тому

    Sorry sir, it’s was Jenkins, he made me laugh when you said C-min.
    🤔

    • @learnelectrics4402
      @learnelectrics4402  Рік тому

      Glad it helped you get through the day. Thanks for watching. Dave.

  • @smd-tech
    @smd-tech 2 роки тому

    Uhuhuhuh you said Cmin.

    • @learnelectrics4402
      @learnelectrics4402  2 роки тому +1

      Thanks for watching.

    • @smd-tech
      @smd-tech 2 роки тому

      @@learnelectrics4402 you are welcome. Love your videos, very helpful and well paced.

  • @ifyougetstucklookitup237
    @ifyougetstucklookitup237 3 роки тому +1

    Thank you appreciated as ever.