Change voltage settings of growatt inverter by shine phone application
Вставка
- Опубліковано 18 кві 2024
- Normally, when there will be fluctuation in grid side voltages. No one can predict when voltages will increase or decrease but when increases inverter will go into error mode " AC V outrange" because standard voltage setting will fixed in manufacturing unit.
To avoid this error, make sure before changing voltages check grid voltages in acdb by turning off inverter. If everything looks fine then for
1phase :
Low Voltage : 170v
High voltage: 280v
3phase :
Low voltage :320v
High voltage :480v
Low frequency : 47hz
High frequency : 52hz
Good work
Great helpfull
I have 3kw on grid solar system but it generates only 4 unit per day what to to ?
My growatt ongrid 10kv inverter has 14 panels of 580 watt attached which is 8kv system in total. But it's only producing 20 to 23 units per day instead of it should actually produce more than 40 units per day. Please guide what settings should I fix or what should I do?
@@Noor-vr4xj plz check any shadow is there or not on panels, panels were clean or not, panel to panel looping, date and time setting in inverter
Is working ok now?
sir please advise me i have growatt SPH 10KW 3 Phase but now show anything correct as u show the list its not show me please advise
This isnfor on grid inverter . For your type of inverter model contact regional growatt service engineer. If possible if I get the data i will post you
@@Gosach796 sir its hybrid 10kw SPH TTLL3B3BHH--UUP
Hi, plz tell the setting for three phase parameter
For 3phase
high voltage will be 480v and low voltage will be 320volts
High frequency will be 53,low frequency will be 47
i want to shear with you my growatt if you can set please its SPH 10KW
@@roz6829 plz share I will try to change
Hi, growaat 10kw,3 phase settings please
For 3phase
high voltage will be 480v and low voltage will be 320volts
High frequency will be 53,low frequency will be 47
Bro i have Growatt 10 KV Inverter with 3 phase electricity meter it works fine but after 2 PM grid voltage falls to 170 to 180 and inverter trips and shows error 300 AC Voltage Outrage is there any solution?
@@waleedmalezai as it is 3phase inverter, grid side phase to phase voltage should be balanced and should be with in range . It should not be above the range or below the range. In ur case it is below the range. For this u have to contact grid people . Growatt engineer can't do anything for this grid side issue
@@Gosach796 ok thanks bro
@@waleedmalezai subscribe to the channel if u like the content bro
@@Gosach796 subscribed.
I checked settings of my growatt inveter “set grid voltage lower limit” is 332.5 should i change it to 320 or not?
@@waleedmalezai no use bro issue is in grid side
My growatt not connecting to internet
Didn't understood ur issue plz elobrate the issue