Tan Delta testing of Current Tranformer (CT) - Theory & Practical Procedure

Поділитися
Вставка
  • Опубліковано 15 вер 2024
  • Tan delta test is an AC low voltage dielectric test that is carried out on insulation to determine its health. Tan Delta test is also called as loss angle test or dissipation factor test.
    Tan Delta test is carried out on various electrical equipments such as :
    1) Current Transformer
    2) Potential Transformer
    3) Transformer Bushing
    4) Transformer Windings
    5) Capacitive Voltage Transformer
    6) Coupling Capacitor
    Purpose:
    Detecting incipient weakness in HV insulation
    Predicting remaining life of the equipment under test
    To get “benchmark reference reading” of the equipment when it is new, clean, dry and free from impurities
    -----------------------------------------------------------------
    Recommended Videos:
    Power Transformer Nameplate Details Explained in Hindi: • Transformer Nameplate ...
    Difference between Metering CT & Protection CT : • Difference between Met...
    Nameplate details of Current Transformer: • Current Transformer (C...
    Testing of Various Substation Equipments: • Testing of Substation ...
    Testing of Lightning Arresters/Surge Arresters: • Testing of Lightning A...
    --------------------------------------------------------------------------

КОМЕНТАРІ • 54

  • @truptimali6856
    @truptimali6856 8 місяців тому

    Thanks Sir for this Informative Video 🙂

  • @sisir22
    @sisir22 9 місяців тому

    very nice elaboration abt tan delta testing, its easy & digestive, pronunciation is very clear. thank you a lot.

  • @angrycap999
    @angrycap999 2 роки тому

    Maa Shaa ALLAH zaberdast

  • @kananbiharibehera5749
    @kananbiharibehera5749 3 роки тому

    Thank you sir,i gain more tips from this video, plz sir upload more video

  • @garvalnaran9972
    @garvalnaran9972 4 місяці тому

    Good

  • @KRISHNAKUMAR-pu9tq
    @KRISHNAKUMAR-pu9tq 10 місяців тому +1

    How tan delta = Ir/Ic
    Calculated using this data?

  • @fazleazim8125
    @fazleazim8125 4 місяці тому

    great

  • @subratamohapatra6478
    @subratamohapatra6478 Рік тому

    Very good lecture.

  • @bibhubisoyi525
    @bibhubisoyi525 2 роки тому

    Nice explanation

  • @indrajitchatterjee4752
    @indrajitchatterjee4752 2 роки тому

    Helpful.Thank you

  • @karanparmar4754
    @karanparmar4754 Рік тому +2

    What is tan delta point and where is it connected ,i am having a hard time understanding it.

    • @that90sguy77
      @that90sguy77 8 місяців тому

      You have to open the CT terminal box under or on the side of the CT

  • @surendrakverma555
    @surendrakverma555 Рік тому

    Very good 🙏🙏🙏🙏🙏🙏. Thanks

  • @user-oi3rk1gm2b
    @user-oi3rk1gm2b 3 роки тому

    شكرا

  • @sjamesking6605
    @sjamesking6605 Рік тому

    Thanku

  • @Assistant_User
    @Assistant_User 2 роки тому

    Thank you. In which standard appears values of permissible limits shown for Tan Delta?

  • @birbahadurpal5080
    @birbahadurpal5080 8 місяців тому

  • @aviralsingh2776
    @aviralsingh2776 3 роки тому

    Nice man

  • @asywadsaferi5565
    @asywadsaferi5565 Рік тому

    Using gst mode do we need to connect to earth?

  • @ravikumarkoyyana12
    @ravikumarkoyyana12 3 роки тому +1

    If tan delta point is not available in CT,then where to connect the Tan delta terminal of the kit

  • @deesingh3330
    @deesingh3330 2 роки тому

    Thank u so much sir for sharing your knowledge 🙏🏻 ..& purely explanation

  • @juakoedge
    @juakoedge Рік тому

    Thank you for the information, i have a question: The HV terminal must be connected to the primary terminal of the CT, we all know CT's have 2 terminals, usally P1 and P2, do i have to short them, or just connect the HV to P1 terminal?
    In terms of secondary windings, theyre shorted and grounded, am i right? i whould be so grateful if you could clear my doubt

    • @substationtestingandcommis3452
      @substationtestingandcommis3452  Рік тому +1

      P1 and P2 are internally connected, you should not short them.

    • @substationtestingandcommis3452
      @substationtestingandcommis3452  Рік тому

      Secondary windings are connected to meters or relays.

    • @therisencomrade3452
      @therisencomrade3452 10 місяців тому

      Secondary alrdy connected to meter and relay so, secondary is not open circuit even during tan delta test. The P1 is first remove from the main line only and then the connected to tan delta HV side. P2 is usually left like that since isolator is alrdy open during test(or maybe earthswitch need to be closed?) . I have performed this test once,I think we usually test with 2kV and 10kV at 50Hz and 100Hz frequency. The current being injected inside CT is around 100A.(For 132kV)

  • @ashishvitekar3474
    @ashishvitekar3474 2 роки тому

    Sir,
    When tan delta Test required?
    As per your best explanation I realized as same as IR Test done by HT megger.
    Can we this test by HT megger?
    Thank you very much

  • @tb.casenjo2680
    @tb.casenjo2680 2 роки тому

    in which standard appears this procedure?

  • @rushirajsinhsolanki2990
    @rushirajsinhsolanki2990 4 роки тому +1

    CT secondary terminal short and measured??

  • @anilshemade6048
    @anilshemade6048 3 роки тому

    Good info...If ct has no tan delta point,then where the lv lead of the kit be connected?

  • @vinodmusicprogamer9503
    @vinodmusicprogamer9503 2 роки тому

    What if cvt and CT tan delta points are not earthed plz reply

  • @CutieSamriddhi357
    @CutieSamriddhi357 3 роки тому

    If we left the tan delta point in grounded then what happens

  • @RAMBABU-gk8kx
    @RAMBABU-gk8kx 2 роки тому

    What's UST and gst mode

  • @mathewsksamuel6508
    @mathewsksamuel6508 8 місяців тому

    hello bro

  • @substationtestingandcommis3452
    @substationtestingandcommis3452  4 роки тому

    Recommended Videos:
    Power Transformer Nameplate Details Explained in Hindi : ua-cam.com/video/6HrTgIOZC5k/v-deo.html
    Difference between Metering CT and Protection CT: ua-cam.com/video/VSwLHAZLj6Y/v-deo.html
    CT Nameplate Details Fully Explained: ua-cam.com/video/eznFythQz3c/v-deo.html

  • @ashok2m
    @ashok2m 3 роки тому

    Great

  • @AnilKumar-bz4rj
    @AnilKumar-bz4rj Рік тому