How To Troubleshoot Carrier 30XA |Cooler Flow Switch Setpoint Configuration Failure Alarm|

Поділитися
Вставка
  • Опубліковано 7 жов 2024
  • Please Do subscribe us ‪@UATechnicalSolutions‬
    In this tutorial we will explain how to troubleshoot cooler flow switch setpoint configuration failure alarm.
    After checking the current alarm, make sure the flow switch 5 pin connector and cable are in good condition by performing continuity test.
    Step 2 is to make sure there are 24 volt ac on the power supply connector video.
    Step 3 make sure the grey wire is connected well as shown
    Step 4 is to check the flow switch relay wires white and black are having 24 volt ac each.
    After confirming all above then go to menu and enter master access password 88 , than go to configuration and enter the service menu
    Scroll down to flow switch setpoint and make sure the setpoint is selected as per chiller model shown in the chart. To change the setpoint press enter and change to the required value and press enter again to save.
    Thanks for watching, do share and subscribe to UA Technical solutions . let us know in the comment section the topics of your choice to make this channel more relevant to you.

КОМЕНТАРІ • 7

  • @sonusomarajan1735
    @sonusomarajan1735 10 місяців тому

    York vsd chiller pcb to pcb communication how can check ?( plz make a video)

  • @sonusomarajan1735
    @sonusomarajan1735 10 місяців тому

    Plz make video vsd chiller york ( yvaa)

    • @UATechnicalSolutions
      @UATechnicalSolutions  10 місяців тому

      Here is the video link on how does york VSD Works.
      ua-cam.com/video/nP848fOBZIE/v-deo.html
      Please share the VSD Model so we can upload the video for the specific VSD drive you want to learn.
      Thanks

  • @AlexHales-x3y
    @AlexHales-x3y 10 місяців тому

    We have Trane RAU 500 & 600 Air cooled Condenser Units. On RAU500 It is showing COMM LOSS: ....... For every transducers and temperature sensors. First I thought that the card might be faulty so I replaced the power communication card from RAU600. But still it's the same.

    • @UATechnicalSolutions
      @UATechnicalSolutions  10 місяців тому

      Thanks for your comment,
      Basically in Trane units each time you disconnects or install a new sensor / Transducer you need to bind it using the trane techview below is the link of the video on how to bind a device after replacement in Trane units
      ua-cam.com/video/OPCBo4IZ37s/v-deo.html

  • @MeandMyShadow-hg7xd
    @MeandMyShadow-hg7xd 7 місяців тому

    Can you please tell me the override error in 30xA080-501 Air cooled liquid chiller

    • @UATechnicalSolutions
      @UATechnicalSolutions  7 місяців тому

      Please confirm what is the alarm code showing in the display?
      Or its just showing override ??