Hydrogen (H2) filling procedure in Generator in Thermal power plant | H2 filling in Generator

Поділитися
Вставка
  • Опубліковано 26 жов 2024

КОМЕНТАРІ • 18

  • @petuskhileo6777
    @petuskhileo6777 11 місяців тому +1

    Great job sir.This channel is one point genuine reference for all power plant related information.

    • @kpatelbla
      @kpatelbla  11 місяців тому

      Thanks for watching

  • @gauravkr067
    @gauravkr067 11 місяців тому

    Thank u very much sir 🙌😇😇🙌

  • @SatyaPrakash-kx4cj
    @SatyaPrakash-kx4cj 10 місяців тому +1

    Sir aapne bola ki h2 filling ka rate slow rakhna hai taki h2 co2 ke sath mix na ho agar hum barring gear rakhenge to hamara h2 hamesha co2 ke sath mix hota rahega to barring gear stop karke filling karna theek nahi hoga

    • @kpatelbla
      @kpatelbla  10 місяців тому

      Nahi, actually barring gear always kept in service during filling to ensure it's healthyness but this speed not create much disturbance for mixing.

  • @ymw786.
    @ymw786. 11 місяців тому +1

    Co2 filling & H2 emergency venting pe video banavo sir

    • @kpatelbla
      @kpatelbla  11 місяців тому

      Okay, thanks for watching.

  • @manohardhaker423
    @manohardhaker423 9 місяців тому +1

    When Unit is running condition, H2 purity is disturb, What is H2 purging pr maintained and how to H2 vent, which side venting is better H2 (Top) side or Co2 (bottom)side for purity achieve.

    • @kpatelbla
      @kpatelbla  9 місяців тому

      During running of Unit H2 purging to be done from CO2 filling line (Bottom) of generator it is for purging out air by H2 and purging rate must be very low 0.005 kg/cm2 /sec.

  • @motive0507
    @motive0507 10 місяців тому +1

    Could you please tell me that when hydroogen refrigeration drying system is used

    • @kpatelbla
      @kpatelbla  10 місяців тому

      One dryer always be in service to maintain the dew point temperature of H2.

  • @abhishekpandey8773
    @abhishekpandey8773 9 місяців тому +1

    Co2 kyu jaruri hai.. plz explain co2 filling

    • @kpatelbla
      @kpatelbla  9 місяців тому

      To replace air then CO2 replaced by H2, actually when Air filled in Generator we can not fill H2 as below 85% purity of H2 in air become explosive that's why co2 filled to replace air.

  • @motive0507
    @motive0507 10 місяців тому +1

    Could you please tell me about BC exhaust fan

    • @kpatelbla
      @kpatelbla  10 місяців тому

      BC exhaust fan is used to exhaust gas plus vapour to atmosphere from Generator exciter end and Turbine end bearing housing.

    • @motive0507
      @motive0507 10 місяців тому +1

      @@kpatelbla what is that BC
      Does it Bearing Chamber?

    • @kpatelbla
      @kpatelbla  10 місяців тому

      Yes

  • @akashpatel1547
    @akashpatel1547 11 місяців тому +1