IGG Fuel oil I/p converter calibration for Kangrim inert gas generator
Вставка
- Опубліковано 4 жов 2024
- #kangram #igg #ship #fuel oil #capacity #valve #fuel oil capacity valve # calibration #marine #igg #burner #Kangrim #f.o capacity valve calibration #inert gas generator #Burner problem #f.o capacity valve problem #i/p converter
good explanation
Hi sir...can you please make a video regarding how to trace electrical circuit diagram of kangrim inert gas system...
Hi Santosh it is impossible to explain full electrical diagram, as you know the electrical diagram runs lot of page. If u want any particular page I can explain.
when zero calibration (0.2bar) time must be waiting 2min, that was need time to stabilize
Hlw sir, in my case the O2 content reducing(1.2) while increasing the capacity (60%). what could be the reason sir?
Try to do the air capacity valve calibration and I/p converter Calibration as I mentioned in video. Tell me r u facings this problem even after calibration of both ?
Run ur IGG at different load from 25% to 90% and check ur air capacity valve and fuel valve position and compare it with maker trail run valve.