Control Techniques - Unidrive SP Drive only replacement via the smart card

Поділитися
Вставка
  • Опубліковано 18 жов 2024
  • Want more information or have a project and need help? Contact Us today!
    carolinamotion...
    (864)-458-9988
    For your automation and manufacturing needs, Carolina Motion Controls is a value-added distributor of the industry's leading electrical and mechanical control products. Carolina Motion Controls' experienced engineering staff is on hand for pre-sales engineering and post-sales support. Find out what that means to you.
    Visit carolinamotion... to see our full line of products we offer!
    Visit carolinamotion... to see the services we offer!
    Visit our What's Up blog page carolinamotion... to view everything from new products to tech how to's.
    Like US on Facebook: goo.gl/MlfZqD
    Follow US on Twitter: / carolina_motion
    Follow US on Google+: goo.gl/4530sO
    Connect with US on LinkedIn: goo.gl/zFu54R

КОМЕНТАРІ • 45

  • @anthonybarnes8500
    @anthonybarnes8500 6 років тому +2

    Is this shown in the Advanced Users Guide. I have always saved to the smartcard via the 0.30 set to program. This is written on the smartcard.

    • @Carolinamotioncontrols
      @Carolinamotioncontrols  6 років тому +1

      Hello, There are various ways to have to the smart card. When doing the save in 0.30 you can only save to file location 1. Where as with the way shown you can save up to 999 files depending on space on the card. In the advanced user guide you will see this command on Pg. 16 in a table of commands that can be given in Mxx.P00

  • @wendelm.c.6282
    @wendelm.c.6282 3 роки тому

    Hello!
    When I was performing autotune in an unidrive SP, before starting, I removed its SM-ETHERNET with the cable. After autotune, the drive lost address IP. Do you know if I must not remove the drive ETHERNET communication during autotune?
    Thanks

  • @pardeeptanwar9102
    @pardeeptanwar9102 2 роки тому

    ES 2403 my lift drive
    In which when parameters save then problem faces
    Parameters save time keypad display show LOCK
    Pls reactifie that if any possible solution

  • @Ivaneliud1
    @Ivaneliud1 4 роки тому

    i have a problem to power up unidrive sp3202, show Trip C.Acc and then C.Err, could you help me

  • @victornutsakpui8449
    @victornutsakpui8449 3 роки тому

    How do I solve the problem/troubleshoot fault 105 temperature problem

  • @ZaidKhan-cz4jd
    @ZaidKhan-cz4jd 4 роки тому

    Is it possible to set a password in this?
    If yes
    How to factory reset?
    ( talking about SP1403 )

  • @joseroldandomalanta3089
    @joseroldandomalanta3089 3 роки тому

    Sir how to restore the the parameter 17.03 it was in None mode cannot be change to rUN mode..

  • @dx16600
    @dx16600 6 років тому +1

    driver is changing auto to open loop to vector mode. what is the reason. do i need to do any changes for communicating with a plc

    • @Carolinamotioncontrols
      @Carolinamotioncontrols  6 років тому

      I am not exactly sure what you are referring too, if you would like to send an email with a little more information to our techsupport@carolinamotioncontrols.com email maybe we can get it figured out.

    • @dx16600
      @dx16600 6 років тому +1

      i figured it out. the problem was in the plc. dry joints and loose connections. removed it cleaned well re-solder and works fine. There was a problem in existing VFD. it is dead.then i fixed another vfd and re configured it by manually with led pannel. when i tried to configure 0.48 it shows Open Loop. but i wanted to change this to closed loop vector to communicate with plc but it didnt hold. so then i found 11.31 also need to change and save in 1001. thank you for your earliest reply.

    • @Carolinamotioncontrols
      @Carolinamotioncontrols  6 років тому

      In order to change the drive mode from Open Loop to Closed Loop Vector, you must enter a "1254" into M0.P00 then change the drive mode from open loop to closed loop in 0.48. Please note when changing the drive mode it will default all parameters to the closed loop USA defaults. If you need EUR defaults then you will enter a "1253" into M0.P00 instead. There is no way to change the drive mode without defaulting the drive as different drive modes have different parameter sets. Hope this helps.

  • @ganeshKumar-bi6ls
    @ganeshKumar-bi6ls 6 років тому +1

    If we wrongly erased all parameters SP5401 Unidrive.
    How can we restore all parameters settings again ?

    • @Carolinamotioncontrols
      @Carolinamotioncontrols  6 років тому

      Hello, There is no way on-board the drive to restore all erased parameters if you have defaulted the drive. However as long as you have the parameter file (test.par) then you can use CTSoft to download the parameters back to the drive or use the smart card if you have downloaded parameters to the card to restore the drives parameters.

  • @deviprasadpattanaik4634
    @deviprasadpattanaik4634 3 роки тому

    Sir how to do servo motor homing through emerson drive

  • @mosharofhossen1666
    @mosharofhossen1666 7 років тому +1

    Parameter no 0.01 to 0.50 all are not edit.Please help me.Model no UNI 4404.

  • @jacob-mo8zg
    @jacob-mo8zg 3 роки тому

    Pr0.00 to 0.50 not edit . If try to edit CODE indication blinking ..any ideas

  • @mosharofhossen1666
    @mosharofhossen1666 4 роки тому

    Model no UNI 4403 message blinking HF88 but not reset.please help me

  • @meghdadbolouri2271
    @meghdadbolouri2271 7 років тому +1

    how can we replace 1024 pals inkuder and add 2500 pals inkuder in uni drive sp 3403

    • @Carolinamotioncontrols
      @Carolinamotioncontrols  7 років тому

      Hello, if you are changing out an encoder you will want to change parameters in Menu 3. Specifically M03.P034, lines per revolution, and M03.P038, Device type if you are using a different type of encoder.

  • @comercialmoxasesoria3028
    @comercialmoxasesoria3028 5 років тому

    We have SP1406 with resolver and it is indicating SL3.Er (Option module bay X trip: Option module in bay X has detected a fault
    ) and SL3.HF (Option module bay X trip: Option module X hardware fault). What can we do for solve it? Thank you

    • @Carolinamotioncontrols
      @Carolinamotioncontrols  5 років тому +1

      I apologize for the delay in response. If you are receiving a SL3.HF fault, that is typically due to an issue that is outside of your control to fix. We have seen where if the module is not making good contact with the drive (not fully seated on the drive) then this can cause a HF fault. You could try to move the module to a different slot to see if they works. Otherwise you may need a new module. If you visit our website we do offer option modules for sale.

    • @AngeloSilva-k7b
      @AngeloSilva-k7b 2 місяці тому

      Por favor whatsapp pra contatos,?
      ​@@Carolinamotioncontrols

  • @AngeloSilva-k7b
    @AngeloSilva-k7b 2 місяці тому

    Alguem q vende esquema eletrico do SP3403 DRIVER??

  • @mosharofhossen1666
    @mosharofhossen1666 7 років тому

    How can set motor pole 2.

  • @mosharofhossen1666
    @mosharofhossen1666 7 років тому

    Parameter no 0.49,Display showing 110 but not edit.
    How can edit or delete process?Please help me.

    • @Carolinamotioncontrols
      @Carolinamotioncontrols  7 років тому +1

      M00.P49 will be the security code for locking the drive from parameters being written too or read. If you go to M00.P00, enter the 110 and perform a reset, the drive should be unlocked after that.

  • @sathishkumarg7802
    @sathishkumarg7802 2 роки тому

    Hello sir hf28 problem not solve

  • @mosharofhossen1666
    @mosharofhossen1666 7 років тому

    Parameter no 0.01 to 0.50 all are not edit.Please help me.

  • @mosharofhossen1666
    @mosharofhossen1666 7 років тому

    Parameter no 0.42,pole is edit but not save.
    How can save this parameter(2pole)

    • @Carolinamotioncontrols
      @Carolinamotioncontrols  7 років тому

      You will perform a save by entering a "1000" into M00.P00 and selecting the Red Reset button. If you do this after you change the pole value it will be saved in the drives memory.

  • @maricelcabrera9569
    @maricelcabrera9569 2 роки тому

    Necesito el plano en español gracias

  • @monusinghshivasingh510
    @monusinghshivasingh510 4 роки тому

    Hf 30 faults remove kese kare

  • @jasveersingh3576
    @jasveersingh3576 4 роки тому

    Sp series da cover demand

  • @j.souza.utilidadesedecorac7057
    @j.souza.utilidadesedecorac7057 5 років тому

    HZ MAXIMU

    • @Carolinamotioncontrols
      @Carolinamotioncontrols  5 років тому

      The max Frequency for the SP in Open loop mode is 3,000 Hz and in closed loop vector or servo mode is 40,000 RPM.

  • @j.souza.utilidadesedecorac7057
    @j.souza.utilidadesedecorac7057 5 років тому

    HELLO

  • @j.souza.utilidadesedecorac7057
    @j.souza.utilidadesedecorac7057 5 років тому

    Hello parâmetro start externo

    • @Carolinamotioncontrols
      @Carolinamotioncontrols  5 років тому

      Hello, I am not exactly sure what a external start parameter is. Unless you are referring to controlling the drive via communications then you could write to a Menu 6 bit or to the control word in menu 6 as long as you enable control word control.

  • @tungla9859
    @tungla9859 Рік тому

    😂