We have a special surprise today! Another Fun Demo for Wednesday!! Please click the link below to see how easy it is to transfer from Unidrive SP to Unidrive M. #unidriveSP #UnidriveM #Smart #Card #Drives #SkipSpeed #Transfer #FDW
If unidrive SP has SM Application card how to transfer the card program to SI application card. Also for SM application replacement, we have to use SI Application or SI Application plus?
I am facing problem with nidec SP2401. We backed up program from old Emerson SP2401 and uploaded to new nidec sp241. But it is not functioning. Could you provide me solution??
Dear all I would like to know how can I use the CT-USB-CABLE (USB to RJ45 Programming Cable with USB to RS485 Converter, used with: SK, SX, SP, DST, EP & MP) to download the program, please ?
Hello, If you would like to send an email to Techsupport@carolinamotioncontrols.com we have a tech note for connecting via a CT-US-CABLE, but no video at this time.
Motor is 75KW but drive is 90Kw ,This time drive in side parameter setting usable? where drive in side KW parameter option and setting system? Please help me.
I am slightly unclear of the question, but the motor KW is not entered into the drive. You will need to enter the motors information such as; speed, current, voltage, poles, etc. into Menu 5 of the drive. After that information is entered an autotune will need to be performed.
Menu 0 Parameters can be configured, but by default M00.P35 is the keypad reference. If you are wanting to change the keypad reference then, select the "M" menu button twice and hold down the up arrow. You should see the value increasing which is the keypad speed reference.
First time this devic is parameter no 0.48 cl vector and pr 0.42- 6 pole,0.43-.920, 0.44-380, 0.45-950.Than look open and pr 1.00 write 1253 than reset.now parameter auto setting 0.42-4pole,0.43-0.920, 0.44-400, 0.45-1450.please help me.0.42 -2pole?
You will perform a save by entering a "1000" into M00.P00 and selecting the Red Reset button. If you do this after you change the pole value it will be saved in the drives memory.
If pressing the Red "Stop/Reset" button does not clear a trip or error then you will likely need to check the diagnostic section of the manual to determine the cause of the trip and eliminate the condition causing the trip before the trip/error can be reset.
We have a special surprise today! Another Fun Demo for Wednesday!! Please click the link below to see how easy it is to transfer from Unidrive SP to Unidrive M. #unidriveSP #UnidriveM #Smart #Card #Drives #SkipSpeed #Transfer #FDW
If unidrive SP has SM Application card how to transfer the card program to SI application card. Also for SM application replacement, we have to use SI Application or SI Application plus?
I am facing problem with nidec SP2401. We backed up program from old Emerson SP2401 and uploaded to new nidec sp241. But it is not functioning. Could you provide me solution??
hello there, please is there a means i can format a drive to restore a missing menu/par on the drive.
Dear all I would like to know how can I use the CT-USB-CABLE (USB to RJ45 Programming Cable with USB to RS485 Converter, used with: SK, SX, SP, DST, EP & MP) to download the program, please ?
Hello, If you would like to send an email to Techsupport@carolinamotioncontrols.com we have a tech note for connecting via a CT-US-CABLE, but no video at this time.
Thanks I'll go to get in touch.
Hello sir Emerson How to run uni drive in slot2
Motor is 75KW but drive is 90Kw ,This time drive in side parameter setting usable?
where drive in side KW parameter option and setting system?
Please help me.
I am slightly unclear of the question, but the motor KW is not entered into the drive. You will need to enter the motors information such as; speed, current, voltage, poles, etc. into Menu 5 of the drive. After that information is entered an autotune will need to be performed.
parameter no 0.35 display showing 0.0. How can edit it. please give me some help.
Menu 0 Parameters can be configured, but by default M00.P35 is the keypad reference. If you are wanting to change the keypad reference then, select the "M" menu button twice and hold down the up arrow. You should see the value increasing which is the keypad speed reference.
First time this devic is parameter no 0.48 cl vector and pr 0.42- 6
pole,0.43-.920, 0.44-380, 0.45-950.Than look open and pr 1.00 write 1253
than reset.now parameter auto setting 0.42-4pole,0.43-0.920, 0.44-400,
0.45-1450.please help me.0.42 -2pole?
You will perform a save by entering a "1000" into M00.P00 and selecting the Red Reset button. If you do this after you change the pole value it will be saved in the drives memory.
Can anyone share me modbus mapping parameters of M200 drive
Could you please send an email to our techsupport@carolinamotioncontrols.com and we can better assist you.
k
How reset error please
If pressing the Red "Stop/Reset" button does not clear a trip or error then you will likely need to check the diagnostic section of the manual to determine the cause of the trip and eliminate the condition causing the trip before the trip/error can be reset.
Please answer