NEC Electrical Exam Prep Question # 157 Pipe Fill Calculations Master Journeyman

Поділитися
Вставка
  • Опубліковано 15 жов 2024
  • We offer the #1 Electrical Exam Prep Program
    FREE VERSION
    electricalcode...
    PRO VERSION
    www.electrical...
    USB OR DVD PROGRAM FREE SHIPPING!!
    electricalcode...
    400x Practice Exam PDF Download for only 14.99 electricalcode...
    2017 Tabs with FREE SHIPPING
    electricalcode...
    2020 NEC TABS with FREE Shipping
    electricalcode...
    2023 NEC TABS with FREE SHIPPING
    electricalcode...

КОМЕНТАРІ • 1

  • @MosesMalone-s8f
    @MosesMalone-s8f 9 місяців тому

    NEC 2023 applicable articles:
    Conduit size: Ch.9, T4, art. 352
    Conductor size: Ch.9, T5
    Equation solution:
    2.5" PVC SCHED 80 (over 2 wires @ 40% column) = 1.647
    #4 THWN = 0.0824
    Equation states that there is already (10) #4 THWN conductors in the conduit: 10 X 0.0824 = 0.824
    Leftover space within the conduit: 1.647 - 0.824 = 0.85
    Out of all the possible answers on the table above, only 10 additional conductors within that conduit would meet the appropriate maximum fill:
    10 X 0.0824 = 0.824 = 0.824 < 0.85
    (✓)
    12 X 0.0824 = 0.9888 = 0.9888 > 0.85 (X)
    Both 8 and 9 conductors would fit inside the conduit, but the conduit would have not been filled to its maximum capacity, while using 12 conductors would overfill the maximum permitted fill. Therefore, 10 #4 THWN would be the appropriate amount of conductors to put in a 2.5" PVC SCHED 80 that has already been filled with 10 additional #4 THWN conductors.