For 33kV 26MW load, load current will be 454 Amp for pf=1. For pf=0.8, it would be 568Amp. So you can use a CT having ratio of 600/1. If 600/1 is not available, use 800/1.
Great information, thank you bro
Tanks sir for more information given through your video
Recommended Videos:
1) Power Transformer Nameplate Details Explained in Hindi: ua-cam.com/video/6HrTgIOZC5k/v-deo.html
2) Tan Delta testing of Current Tranformer (CT) : ua-cam.com/video/iFWFyM3rhuo/v-deo.html
Please tell How to calculate (Ith) Rated thermal short circuit current?
Sir if rayed dyanamic current is 65.5KAP
Then why short time current is only 26.2 which flow only 1 minute
Short time current means what..u said that RMS value of rated primary current that we did not get
1400(1-1-1) what is full form ct
Tell me sir
bhai esa kyu lag raha koi gunpoint pe aapke pass ye video shoot karva raha hai ?
what is the ratio of weight of copper and core used?
How parimary current and short time current related by using one example..
How to understanding example: 1250/1+1+1+1A 1600/1A like this ratio
Hi There, u gave me a gud information.
Could you please let me know steps for selection of a CT for 33KV feeders 26MW of load.
For 33kV 26MW load, load current will be 454 Amp for pf=1.
For pf=0.8, it would be 568Amp.
So you can use a CT having ratio of 600/1.
If 600/1 is not available, use 800/1.
May i know the formula please
I = P/( sqrt(3) * V * pf)