Upgrading Your Main Fuse

Поділитися
Вставка
  • Опубліковано 6 лют 2025

КОМЕНТАРІ • 24

  • @Adam-oy1vp
    @Adam-oy1vp Рік тому +3

    Very informative

  • @essexandy189
    @essexandy189 7 місяців тому +1

    Gotta say you explain it very well makes it a lot easier than some off the others iv’e seen

  • @Perryrburgess
    @Perryrburgess 5 місяців тому

    Great video. Full of useful clear understandable information. Great to have it explained in layman's terms rather than trade-speak. Really good content. Well done. Nice one. Thank you guys

  • @allahdittababu4802
    @allahdittababu4802 Рік тому +2

    Your really good and clear with explaining each step ... Thanks made alot of sense

    • @tonyrobinson362
      @tonyrobinson362 Рік тому

      Thanks not quite straight forward having a charger fitted thanks for info.

  • @elless317
    @elless317 7 місяців тому +1

    Hi, very interesting and well explained.
    About the service cable, is otfen wrapped in that greasy strip; is a way to know its amperage(maybe from external diameter?) . Thank you

    • @VartiaElectrics
      @VartiaElectrics  7 місяців тому

      Good morning Elless317,
      Unfortunately not, however the main fuse often has the amps written on it. Or you can phone your electrical supplier and they can confirm for you.
      Kind regards
      Vartia Electrics

    • @elless317
      @elless317 7 місяців тому

      @@VartiaElectrics thanks👍

  • @Mike_5
    @Mike_5 Рік тому

    Did you upgrade the main fuse yourself or get the DNO to do it?

    • @VartiaElectrics
      @VartiaElectrics  Рік тому +1

      Good Afternoon Mike,
      We got the DNO to upgrade the main fuse to 100amps.
      Kind regards
      Vartia Electrics

    • @Kemalustatv2
      @Kemalustatv2 11 місяців тому +1

      How much average to upgrade to 100?

    • @Mike_5
      @Mike_5 11 місяців тому

      @@VartiaElectrics nice one

    • @VartiaElectrics
      @VartiaElectrics  11 місяців тому +1

      ​@@Kemalustatv2 Hi AtheistProphet,
      In this case the meter tails (main cut out to meter and meter to fusebox) were only 16mm2 and needed to be uprated 25mm2 to support 100 amps.
      The DNO charged the client £170 to do this and fitted an isolation switch.
      If the meter tails are a sufficient size for the relative amps, DNO's don't normally charge to uprate the fuse.
      Please get in contact if you have any more questions

    • @davidwood-c5m
      @davidwood-c5m 11 місяців тому +1

      Spenergyworks want a long and complicated form filled out. I gave up, how is a normal person supposed to fill out that! I already have a pod point fitted so it’s not as if I can ask the fitter. I don’t even know who it was. It’s very silly. Now I just wait for the main fuse to blow then they do t have a choice but to come fit a bigger amp fuse.

  • @Leeroytrucks01
    @Leeroytrucks01 9 місяців тому +2

    Do i need landlord permission to do this ? Also my fuse box and meter are not in the same room. Is this a problem?

    • @VartiaElectrics
      @VartiaElectrics  9 місяців тому +1

      Hi Leeroytrucks01, the landlord would need to grant permission and most likely have to make the call.
      The meter not being in the same room does not cause any issues. Please be aware if the fuse is going to be uprated the meters tails may also need to be uprated.
      Kind regards
      Vartia Electrics