4 WAY VALVE | REVERSING VALVE | HEAT PUMPS

Поділитися
Вставка
  • Опубліковано 30 січ 2025

КОМЕНТАРІ • 17

  • @sdsd4284
    @sdsd4284 Рік тому +1

    Thanks for that knowledge .

    • @D2DNYAC
      @D2DNYAC  Рік тому

      Thanks for watching

  • @thesilentonevictor
    @thesilentonevictor Рік тому +1

    Great tip tech

  • @manschool4992
    @manschool4992 Рік тому +1

    Thank you! Great vid. I've removed reversing valves in package units but never residential style like this with coil directly behind it. I'm assuming you use a heat shield to prevent damaging the coil?

    • @D2DNYAC
      @D2DNYAC  Рік тому +1

      Yes! however ONLY when installing the new valve i use wet rag or wet rag paste,,... for the removal process this isn't needed!

  • @johnnyb8629
    @johnnyb8629 Рік тому

    That's a good tip, because the tuning fork torch tip is hard to use. So I do something similar when replacing the liquid headers on the Carrier RTU with the individual metering devices on each coil tube that always plug up. You cant heat 4 or 5 tubes up all at the same time so I snip them off and then un sweat them individually. Typically in Chicago on commercial units when the reversing valve starts to stick people opt to just remove them pipe them straight and make it a conventional unit at that point and use the electric heater. Mostly see them by the lake, further in land they use retention ponds instead of air to air.

    • @D2DNYAC
      @D2DNYAC  Рік тому

      Sweet thanks for watching

  • @saleht9472
    @saleht9472 8 місяців тому

    Great video! I just wanted to ask, how can I check if a 4-way valve is healthy or not using a multimeter? I would really appreciate an explanation.

    • @D2DNYAC
      @D2DNYAC  7 місяців тому +1

      You can only check the coil for short to ground or to see if coil open, a good test is to energize and de energize the coil while the compressor is running to check valve switching

  • @ahmedb186
    @ahmedb186 Рік тому +1

    Why is the blue wire off the spade connector on the valve? Was that an accident and came off? I’m in Chicago Always wanted to work on them but not much here. If possibly do a video on thermostat wire connection.

    • @D2DNYAC
      @D2DNYAC  Рік тому

      Thanks for watching my brother,,

    • @D2DNYAC
      @D2DNYAC  Рік тому +1

      the connector was off because this heat pump is designed to fail safe in heat mode hence if the valve isn't powered it's in heat mode, and because the outdoor fan fan cycling switch or low ambient control isn't functioning when the system goes into defrost mode this causes head pressures to be extremely low, so low there isn't enough differential pressure so the valve can switch back to heat. This was a temporary fix to keep the heat going

  • @anthonysherrisefigueroa
    @anthonysherrisefigueroa Рік тому

    What wireless gauges are those?

    • @D2DNYAC
      @D2DNYAC  Рік тому

      Parker smart service tool kit

  • @realSamAndrew
    @realSamAndrew Рік тому

    Another UA-camr says he uses bolt cutters, but I don't know all the details.

    • @D2DNYAC
      @D2DNYAC  Рік тому

      if you can fit them into the gaps between pipes 🤷‍♂️