  • The WT controller maintains residual dissolved ozone in the contact tank and measures well water use to control ozone dosing into untreated water. A timer controls two 120v outlets - one for the injection pump and one for the ozone generator. The factory setting for this timer turns the pump and ozone on for 1 minute every hour to maintain a residual level of dissolved ozone in the ozone contact tank. Timing on/off cycle is fully adjustable to accommodate water conditions and ozone generator size. The Hall effect water flow sensor will also turn on the pump and ozone for one minute after the factory setting of 10 gallons of water is used. Flow sensor calibration and water flow quantity is adjusted on the controller display.