Daikin inverter Split AC Wiring connection | Daikin split AC Outdoor to Indoor wiring

Поділитися
Вставка
  • Опубліковано 23 гру 2024

КОМЕНТАРІ • 58

  • @ahsanprima6141
    @ahsanprima6141 2 роки тому +2

    great...very helpful😀

  • @amidismalek8502
    @amidismalek8502 6 місяців тому +1

    Thank you very much…. Very helpful 👍🏼👍🏼👍🏼

  • @marciosantos4202
    @marciosantos4202 2 роки тому +2

    Amazing!!!

  • @eddiecovel6478
    @eddiecovel6478 11 місяців тому

    Thankyou…. we fought for hours looking at the colours on the top of the indoor unit where number one was black and were afraid to connect an active to this location

  • @satyanarayanatiruveedhi5215
    @satyanarayanatiruveedhi5215 Рік тому +1

    Very good explanation in connection.
    But please explain what happens to company suggested over load protection in type 2?

  • @Jordan.108
    @Jordan.108 6 місяців тому +1

    Thanks a lot

  • @mohammadaftabsiddiqui9053
    @mohammadaftabsiddiqui9053 Рік тому +1

    Thaks bro

  • @ShrihariPandula
    @ShrihariPandula Рік тому +1

    Thank you MrEngineers! Is this applicable in the same exact way for both INVERTER and FIXED-SPEED air conditioner units? Are there any exceptions where only Option 1 (Outdoor to Indoor) is applicable?

    • @MrEngineerss
      @MrEngineerss  Рік тому

      Same for inverter and and fixed speed also connection way is same for both

  • @Kr1_2h20brag
    @Kr1_2h20brag Рік тому +1

    Thanks bro

  • @briangallardo3246
    @briangallardo3246 Рік тому

    Thanks, it’s asking for 208V but I just put 12 on a 30A breaker

  • @ahmadmdnoh6585
    @ahmadmdnoh6585 Рік тому +1

    Will type 2 wiring work for midea inverter AC? Manufacturer suggests wiring type 1, power supply connected to outdoor and then 4 wires go to indoor

    • @MrEngineerss
      @MrEngineerss  Рік тому

      In meadia compny i have no idea but these both are wiring types is good for split ac so don't worry

  • @JoginderSingh-tc9rs
    @JoginderSingh-tc9rs Рік тому +1

    Can we use 1.5 mm four core wire for type 2 installation in daikin 1.5 ton inverter ac

    • @MrEngineerss
      @MrEngineerss  Рік тому

      Yes but how much length of wire and ton of ac...?

    • @JoginderSingh-tc9rs
      @JoginderSingh-tc9rs Рік тому

      @@MrEngineerss 1.5 ton AC and wire length is approximately 25 feet

  • @saurabhgupta9644
    @saurabhgupta9644 2 роки тому +4

    My ac is installed by local technician by giving indoor to outdoor connection . But company says that wiring should be outdoor to indoor .
    There may be any problem in the working of ac or compressor by giving indoor to outdoor connection?

    • @MrEngineerss
      @MrEngineerss  2 роки тому

      There is no problem in working so don't worry 🙂

    • @saurabhgupta9644
      @saurabhgupta9644 2 роки тому +1

      @@MrEngineerss then why company recommend for outdoor to indoor connection?

    • @MrEngineerss
      @MrEngineerss  2 роки тому

      Company recommend outdoor to indoor because there is overload safety features available for indoor unit
      And for other company that is in indoor juction so

    • @VinodVinod-xy7wy
      @VinodVinod-xy7wy 2 роки тому +1

      @@saurabhgupta9644 company sujjecstion outdoor wiring

    • @MrEngineerss
      @MrEngineerss  2 роки тому

      Right

  • @somnathdey1411
    @somnathdey1411 7 місяців тому +1

    In daikin 1.5 ton ATKL50UV16VA model technical told that 3 core and 4 core both wire require. But 2 of my friends install same AC but only with one type of wire. I am confused. Can u suggest what is the best part.

    • @MrEngineerss
      @MrEngineerss  7 місяців тому

      4 core wire is required but in the same thing types 2 wiring there is both required

  • @dilipkukreja2705
    @dilipkukreja2705 9 місяців тому +1

    Hi, I am relocating my diakin AC. The wiring from indoor to outdoor is done. The AC will be shifted after interor. As per wireman the main supply can be given from indoor unit. The wiring will be covered by wooden pelmet, my concern is power supply can be given from indoor unit.

    • @MrEngineerss
      @MrEngineerss  9 місяців тому

      Yes you can be given from indoor to outdoor but in Daikin company advisor from outdoor to indoor

    • @dilipkukreja2705
      @dilipkukreja2705 9 місяців тому

      Thanks, will it affect cooling or life of machine, at present it's from outdoor unit.

    • @MrEngineerss
      @MrEngineerss  9 місяців тому +1

      @dilipkukreja2705 no there is no any issue

  • @zah7417
    @zah7417 Рік тому +1

    Thnk you

  • @美人-w8x
    @美人-w8x 2 роки тому +1

    Hi may I ask normally 3 core wiring got connect to outdoor compressor ?

    • @MrEngineerss
      @MrEngineerss  2 роки тому +1

      Not possible because without earthing wire compressor not working very well

    • @美人-w8x
      @美人-w8x 2 роки тому +1

      @@MrEngineerss TQ for reply. I means the 3 core wiring connect to indoor and from indoor direct connect to outdoor, because the installer charged me wiring fee very long, he said wiring need very long. I wish to know is that true that the wiring need for outdoor also ?

    • @MrEngineerss
      @MrEngineerss  2 роки тому

      Yes wire is need to connect from indoor to outdoor that is necessary in connection so no any other way to save money please do that

    • @美人-w8x
      @美人-w8x 2 роки тому +1

      @@MrEngineerss I see. Is that wire to outdoor is came from wall ?

    • @MrEngineerss
      @MrEngineerss  2 роки тому

      Yes that is possible

  • @Harsh-yc6ho
    @Harsh-yc6ho 2 роки тому +2

    Hi I live in a flat where indoor piping is already done. But they have given 3 core wire between indoor and outdoor unit. I want to buy Daikin inverter AC. Is it possible to run inverter AC on 3 core wire.

  • @Jzz5156
    @Jzz5156 6 місяців тому

    My daikin inverter compressor is the same like on your video but i having problem with the indoor unit which has connection ( 1/2/3 N/L/E) thats 6 quite confuse right now

  • @nbctcp3450
    @nbctcp3450 5 місяців тому

    Daikin Service Center told me if anyone using Option2 in Daikin Inverter. That will void warranty
    Someone said in comment. We need to choose Option1 because Overload protection for Inverter is in OUTDOOR.
    Is Overload protection in Inverter in PCB Outdoor or after Compressor?

  • @saurabhgupta9644
    @saurabhgupta9644 2 роки тому +1

    Pls tell

    • @MrEngineerss
      @MrEngineerss  2 роки тому +1

      I think your ac is Daikin brand ...?

    • @saurabhgupta9644
      @saurabhgupta9644 2 роки тому +1

      @@MrEngineerss yes Daikin non inverter split 1.5 ton

    • @MrEngineerss
      @MrEngineerss  2 роки тому

      In my house also connection from indoor to outdoor so there is no problem don't worry
      And you want to change connection than you can see my video and follow type 1 of wiring

  • @aa19500
    @aa19500 7 місяців тому

    I have daikin non inverter 1.5 ton using type 2 wiring, in which the technician has given neutral in 1 & Line in 2 for indoor unit and Line in 2 & neutral in 3 for outdoor unit. Earthing is as last option in both. The issue is that the PCB is not working.
    Please suggest what to do, provide your contact/email address to contact you.

    • @nbctcp3450
      @nbctcp3450 5 місяців тому

      pin1 in Daikin always Live
      pin2 Neutral
      I believe for Daikin Non Inverter using Option2 wiring