Siemens Logo PLC analog input scaling and bar graph

Поділитися
Вставка
  • Опубліковано 21 жов 2024
  • In this video , we will scale on board AI for (1) 4-20 ma and then for (2) 0-10VDC input.
    Also demonstrating bar graph functionality.
    on board analogue input of logo plc supports 0-10V DC input only.
    so for sensor with 4-20 ma output , we require to connect 500 ohm resistor.
    #Siemens #LogoPLC #beginner #Logo
    #AI #Analog #Input #Scale #Scaling
    Check out other training videos:
    Siemens Software License - Online software Delivery / OSD
    • Siemens OSD - Online S...
    S7 200 PLC data over OPC DA - PC Access SMART
    • S7 200 PLC data over O...
    Siemens LOGO PLC as Modbus TCP Client
    • Siemens LOGO PLC as Mo...
    Synchronize Siemens HMI time with S7 PLC using Area Pointer
    • Synchronize Siemens HM...
    S7 200 SMART Analog Input scaling (Applicable for SMAI04 / AI08 / AM03 / AM06)
    • Synchronize Siemens HM...

КОМЕНТАРІ • 17

  • @ranjiththekkepara3871
    @ranjiththekkepara3871 2 роки тому +1

    sensor input is 4-20ma, but logo input is only adopt 0-10v. so used 500ohm resistor to convert 4-20ma to 0-10vdc. but why did you configure the logo AI 4-20ma? should configure 0-10v right?

    • @StableAutomation
      @StableAutomation  2 роки тому +1

      becase at 4ma you will get 2V. so 0-10V wont work.

  • @rajeshc6292
    @rajeshc6292 6 місяців тому

    Sir, I am facing scaling issue 4to 20 mA into 0-100 %convertion in logo analog input module.I wanted to discuss.

  • @joeltshiela4605
    @joeltshiela4605 Рік тому

    how to make a siemens logo program to drive the AM2 AQ analog outputs without using an input (no sensor). THANKS

  • @flex01223
    @flex01223 4 роки тому +1

    Very nice video!

  • @Kejtoo
    @Kejtoo 2 роки тому

    is it possible to change pulse frequency by the analog input?

  • @rajeshc6292
    @rajeshc6292 Рік тому

    Is it possible to connect the 3 wire transmitter in logo PLC ???

    • @StableAutomation
      @StableAutomation  Рік тому

      It's possible.
      But wiring depends on where you are connecting - either on on board PLC input (0-10V) or external module (4-20 ma)

  • @rabiburrahmanrabbi8307
    @rabiburrahmanrabbi8307 3 роки тому

    Thank you

  • @moindalvs
    @moindalvs 3 роки тому

    PLEASE SHOW WIRING FOR ANALOG INPUT ASSIGNED? DID YOU USE I7 AND I8 AS 0V AND 10V OR M LOGO PLC POWER SUPPLY 0V ?

    • @StableAutomation
      @StableAutomation  3 роки тому +1

      M as 0V and I7 , I8 as 10V +(input)
      Plz refer wiring diagram in manual.

    • @moindalvs
      @moindalvs 3 роки тому

      @@StableAutomation thanks alot sir

    • @moindalvs
      @moindalvs 3 роки тому

      Dear Sir,
      So can i consider I7 as AI1 and I8 as different Analog input ie AI2?

    • @StableAutomation
      @StableAutomation  3 роки тому +1

      @@moindalvs Yes..

  • @ericdenja2122
    @ericdenja2122 3 роки тому

    Asuuming I want to have I7 as 50% and I8 as 100% can I use one pressure transducer (4-20mA) for the same?