- The SACE New Emax family of air circuit-breakers consists of six sizes: X1, E1, E2, E3, E4, E6 up to 6300A.
All the SACE New Emax circuit-breakers have the same height and depth both in the fixed and withdrawable version and allow construction of compact switchgears.
Main benefits
Maximum safety is ensured in many different ways, such as racking-out with the door closed, degree of protection towards the outside up to IP54, various different safety locks and double insulation.
The innovative pole structure guarantees complete insulation between phases, and between the phases and neutral, while ensuring full possibility of inspection of the arcing chamber and the main contacts.
Lively performance. E1 now offers current ratings up to 1600A, whilst E3 is enhanced by the top performance level V.
Main features
Brilliant intelligence. The new generation of protection trip units is fitted with the latest advances in electronics, offering individual bespoke solutions for control and protection.
The new trip units, which are amazingly versatile and simply to use, offer important innovations, such as the brand-new intuitive operator interface allowing a complete control of the system with just a few simply key-strokes.
Furthermore, there are new protections, new alarms and connection to handheld and laptop PCs using Bluetooth technology.
With the new standardize system of accessories, studied and made for new Emax, work becomes easier, convenient, safe and rapid.
new.abb.com/low...
Technical Catalogue:
library.e.abb....
Thank you so much it was very helpful
In=2000? That must be checked from the rating plug (#12 on the instruction photo), NOT from the specs sticker.
Though the frame is a 2000A, the trip unit can actually be downsized to 1600, 1250, 100, 800, 630(?)A by simply exchanging the rating plug.
And that will directly affect the reference In for all settings.
Regards, ABB Tech Support
How to change the Rating plug ?
@@amaan8670 pop out with a screwdriver (or 2, to go straight) and put a smaller one in.
Cannot be replaced with bigger than sold, only smaller.
However, L setting I1 can be as low as 40% of nominal current, so a lower rating plug is not that often needed.
Typically only with smaller currents in high short-circuit or high temperature conditions.
@@ambassadorkees
Thanks for your reply
Very informative video 🙏🙏🙏🙏
Good just the InN was the protection for the neutral in percentage to the protection of the 3 phases
how do you set the S curve to t = k? instead of I2t = k. thank you
Acb on but not closed what is problem
Check closing ckt
L indication alaram blinking what is the problem?
In our CB we have alarm are blinking l would lile why
How to unload spring without pressing push on button
What is problem alarm t1 blink light
Brother what is Icu Ue??
Icu breaking capacity of breaker
sir,I want to know how to tripped Acb reset?& to restart it?
Acb ko off Karke on kare
I also would like to know please. How do you test if it trips and how to reset it
@@technicalkumar3028 sir Earth fault ke near T4 ka bataeye,
Contioling
AC drive parameter setting video
Bhai pehle khud samajh lo