    We have problem with ge/AF650 or danfous speed controller. when it starts up to 40hz speed. It stops and displays an alarm (WARNING/ALARM 7, DC over voltage) and 2nd time alarm (WARNING/ALARM 8, DC under voltage)
    Please how is the solution?
    Thanks

    • @controlsSystemsofficial
      @controlsSystemsofficial  Рік тому

      1. Symptom: Motor is not reaching maximum speed,
      Possible cause: Frequency limits set wrong.
      Test: Check output limits in parameter 4-13 Motor Speed High Limit [RPM], parameter 4-14 Motor Speed High Limit [Hz], and parameter 4-19 Max Output Frequency.
      Solution:Program correct limits.
      Possible cause: Reference input signal not scaled correctly.
      Test: Check reference input signal scaling in parameter group 6-0* Analog I/O mode and parameter group 3-1* References.
      Solution:Program correct settings
      2. Symptom: Motor speed unstable
      Possible cause: Possible incorrect parameter settings.
      Test: Check the settings of all motor parameters, including all motor compensation settings. For closed-loop operation, check PID settings.
      Solution: Check settings in parameter group 1-6* Load Depen. Setting. For closed-loop operation, check settings in parameter group 20-0* Feedback.

  • @mightypavan5917
    @mightypavan5917 2 роки тому

    Can you explain about option detection alarm

  • @Pakistanzindabad-jg7mw
    @Pakistanzindabad-jg7mw Рік тому

    how i adjust quick stop time on parameter 3-81 i

  • @hajasherifhaja407
    @hajasherifhaja407 Рік тому

    Hi’ Auto on indication on and off automatically what does its mean?

  • @sajid4upn
    @sajid4upn 2 роки тому

    Hi Iam facing error in VLT Danfoss FC102. 250Kw DC over Voltage A7 I have increased the Ramp Down time from 8sec/15sec but still the problem same as per your informative video their in no any option in the hardware for Brake Resistor could you pls help me

    • @controlsSystemsofficial
      @controlsSystemsofficial  2 роки тому +1

      If the alarm/warning occurs during a power sag,
      use kinetic back-up (parameter 14-10 Mains
      Failure).

    • @sajid4upn
      @sajid4upn 2 роки тому

      @@controlsSystemsofficial could you pls guide me

    • @sajid4upn
      @sajid4upn 2 роки тому

      @@controlsSystemsofficial thank you for your prompt support

  • @SK-uo2wo
    @SK-uo2wo Рік тому

    Alarm led glows vfd stops with text message 1A0. What does 1A0 means

  • @raoulboumi4043
    @raoulboumi4043 2 роки тому

    I have an alarm on my danfoss vlt internal MCO error[A199]
    Please how can i solve it ?

    • @controlsSystemsofficial
      @controlsSystemsofficial  2 роки тому +1

      Error 199
      Internal MCO fault:
      If such an error should occur, please contact your dealer and report the error number displayed to the technical service department.