I configured a motor of 4kw.but the frequency is not stable when you increase the frequency. It starts warning and alarming 7.and trips when the frequency reaches 30.what do I need to do
WARNING/ALARM 7 is DC Over-Voltage: If the intermediate circuit voltage exceeds the limit, the frequency converter trips after a time. Troubleshooting: 1. Connect a brake resistor, 2. Extend the ramp time, 3. Change the ramp type 4. Activate the functions in 2-10 Brake Function Increase 14-26 Trip Delay at Inverter Fault The fault may be caused by mains distortions. Installing Danfoss Line Filter may rectify this problem.
Sir , can you help me to decrease from danfoss VFD. I tried many times , since when I watch your video.but I faild to increase or decrease. Please help me
ALARM 13-Over current 1.Remove power and check if the motor shaft can be turned, 2.Check that the motor size matches the frequency converter, 3.Check parameters 1-20 to 1-25 for correct motor data,
I had a similar problem. I had to change the lower frequency value in the quick menu. Its set to 0.0hz by default but you have to change it to the frequency you want to run the motor on for the motor to start in auto on mode.
Pressing the menu button, ok button, and down arrow button this will unlock the password. This will automatically enter the parameter editing screen in quick menu or main menu.. Please try this method..
@@controlsSystemsofficial Thank You very much for help. I solved problem with password but I have another one question to You. on our pump was problem, (AL11) Motor thermistor over temperature . and after that the Motor with thermistor was broken. we take new Motor without thermistor and make changes on danfoss micro drive fc 51 : manual reset press [Reset], [Auto On] and restart the motor. 1-90 Motor Thermal Protection: [0] *No Protection Disables temperature monitoring. 1-93 Thermistor Resource: [0] * None No thermistor is connected after thet the new pump stil not working. please how can I slove this problem. Thanks
Liked your vedio from 🇮🇳🇮🇳❤❤❤
Thank you
Is there a way to remove the connection to the manual button? Or disable the manual button function?
Hey,,How do I make the micro drive work again in automatic mode now that I'm only using manual hand on and it’s challenging me?
I configured a motor of 4kw.but the frequency is not stable when you increase the frequency. It starts warning and alarming 7.and trips when the frequency reaches 30.what do I need to do
WARNING/ALARM 7 is DC Over-Voltage:
If the intermediate circuit voltage exceeds the limit, the frequency converter trips after a time.
Troubleshooting:
1. Connect a brake resistor,
2. Extend the ramp time,
3. Change the ramp type
4. Activate the functions in 2-10 Brake Function
Increase 14-26 Trip Delay at Inverter Fault
The fault may be caused by mains distortions. Installing
Danfoss Line Filter may rectify this problem.
voz sos muy proo!!!
Is it single to three phase 440v drive
What is 1 A0 WARNING RELATED TO
Nice
HOW CAN I ADD A WARNING LIGHT WHEN MOTOR NOT RUNNING?
How to check alarm or fault log Or
Sir , can you help me to decrease from danfoss VFD.
I tried many times , since when I watch your video.but I faild to increase or decrease.
Please help me
Dear sir please explain how we resolve the AL 13
ALARM 13-Over current
1.Remove power and check if the motor shaft can be turned,
2.Check that the motor size matches the frequency converter,
3.Check parameters 1-20 to 1-25 for correct motor data,
Hi there how do you get into the menu to change the frequency
Thanks
Very good information. Thank you
Thank you for the interesting explanation & but I have an error 37 what should I do
AL 13 WHAT DID IT MEANS
saya mempunyai masalah yaitu start di digital input tidak bisa, apakah ada kontak yang bisa saya hubungi, terimakasih
I had a similar problem. I had to change the lower frequency value in the quick menu. Its set to 0.0hz by default but you have to change it to the frequency you want to run the motor on for the motor to start in auto on mode.
Add more
Ok
After 7
hi. I can't change parameters on my danfoss micro drive fc 51, can You tell me password. thanks
Pressing the menu button, ok button, and down arrow button this will unlock the password. This will automatically enter the parameter editing screen in quick menu or main menu.. Please try this method..
@@controlsSystemsofficial Thank You very much for help. I solved problem with password but I have another one question to You.
on our pump was problem, (AL11) Motor thermistor over temperature . and after that the Motor with thermistor was broken.
we take new Motor without thermistor and make changes on danfoss micro drive fc 51 :
manual reset press [Reset], [Auto On] and restart the motor.
1-90 Motor Thermal Protection:
[0] *No Protection Disables temperature monitoring.
1-93 Thermistor Resource:
[0] * None No thermistor is connected
after thet the new pump stil not working.
please how can I slove this problem. Thanks