  • @Matt92766
    @Matt92766 2 роки тому

    Is there a way to remove the connection to the manual button? Or disable the manual button function?

  • @mirlomill5233
    @mirlomill5233 2 роки тому

    Hey,,How do I make the micro drive work again in automatic mode now that I'm only using manual hand on and it’s challenging me?

  • @jonahagwau6681
    @jonahagwau6681 Місяць тому

    I configured a motor of 4kw.but the frequency is not stable when you increase the frequency. It starts warning and alarming 7.and trips when the frequency reaches 30.what do I need to do

    • @controlsSystemsofficial
      @controlsSystemsofficial  Місяць тому

      WARNING/ALARM 7 is DC Over-Voltage:
      If the intermediate circuit voltage exceeds the limit, the frequency converter trips after a time.
      Troubleshooting:
      1. Connect a brake resistor,
      2. Extend the ramp time,
      3. Change the ramp type
      4. Activate the functions in 2-10 Brake Function
      Increase 14-26 Trip Delay at Inverter Fault
      The fault may be caused by mains distortions. Installing
      Danfoss Line Filter may rectify this problem.

  • @leninpastrana2713
    @leninpastrana2713 9 місяців тому

    voz sos muy proo!!!

  • @SanjivMaheshwari
    @SanjivMaheshwari 2 роки тому

    Is it single to three phase 440v drive

  • @SK-uo2wo
    @SK-uo2wo 2 роки тому

    What is 1 A0 WARNING RELATED TO

  • @muhammadnaeem4834
    @muhammadnaeem4834 Рік тому

    Nice

  • @ErnestMazurekIII
    @ErnestMazurekIII 4 місяці тому

    HOW CAN I ADD A WARNING LIGHT WHEN MOTOR NOT RUNNING?

  • @SK-uo2wo
    @SK-uo2wo 2 роки тому

    How to check alarm or fault log Or

  • @rajeshkumar-fp6vs
    @rajeshkumar-fp6vs 2 роки тому

    Sir , can you help me to decrease from danfoss VFD.
    I tried many times , since when I watch your video.but I faild to increase or decrease.
    Please help me

  • @ravimathur9487
    @ravimathur9487 2 роки тому

    Dear sir please explain how we resolve the AL 13

    • @controlsSystemsofficial
      @controlsSystemsofficial  2 роки тому

      ALARM 13-Over current
      1.Remove power and check if the motor shaft can be turned,
      2.Check that the motor size matches the frequency converter,
      3.Check parameters 1-20 to 1-25 for correct motor data,

    • @ronandrons
      @ronandrons 2 роки тому

      Hi there how do you get into the menu to change the frequency
      Thanks

  • @rajeshkumar-fp6vs
    @rajeshkumar-fp6vs 2 роки тому

    Very good information. Thank you

  • @khaledulker437
    @khaledulker437 2 роки тому

    Thank you for the interesting explanation & but I have an error 37 what should I do

  • @GertPhyffer-n2z
    @GertPhyffer-n2z 5 місяців тому

    AL 13 WHAT DID IT MEANS

  • @ramanuzhagunawan5561
    @ramanuzhagunawan5561 2 роки тому

    saya mempunyai masalah yaitu start di digital input tidak bisa, apakah ada kontak yang bisa saya hubungi, terimakasih

    • @henrikandersson8132
      @henrikandersson8132 2 роки тому

      I had a similar problem. I had to change the lower frequency value in the quick menu. Its set to 0.0hz by default but you have to change it to the frequency you want to run the motor on for the motor to start in auto on mode.

  • @mwanawahakaemmanuel7232
    @mwanawahakaemmanuel7232 Місяць тому

    Add more

  • @franklinpaulson2933
    @franklinpaulson2933 Місяць тому

    After 7

  • @batumibrewery1628
    @batumibrewery1628 2 роки тому

    hi. I can't change parameters on my danfoss micro drive fc 51, can You tell me password. thanks

    • @controlsSystemsofficial
      @controlsSystemsofficial  2 роки тому

      Pressing the menu button, ok button, and down arrow button this will unlock the password. This will automatically enter the parameter editing screen in quick menu or main menu.. Please try this method..

    • @batumibrewery1628
      @batumibrewery1628 2 роки тому

      @@controlsSystemsofficial Thank You very much for help. I solved problem with password but I have another one question to You.
      on our pump was problem, (AL11) Motor thermistor over temperature . and after that the Motor with thermistor was broken.
      we take new Motor without thermistor and make changes on danfoss micro drive fc 51 :
      manual reset press [Reset], [Auto On] and restart the motor.
      1-90 Motor Thermal Protection:
      [0] *No Protection Disables temperature monitoring.
      1-93 Thermistor Resource:
      [0] * None No thermistor is connected
      after thet the new pump stil not working.
      please how can I slove this problem. Thanks