Add a Powerflex 525 drive to a Controllogix Compactlogix over Ethernet

Поділитися
Вставка
  • Опубліковано 23 лис 2024

КОМЕНТАРІ • 179

  • @jerrycarter3963
    @jerrycarter3963 3 роки тому +5

    Thank you for your videos. I have done quite a bit of programming (allen bradley, automation direct, and others) but i always like witching and learning new things. You do a great job of explaining. Thank you for your time and dedication.

  • @palazzolo85
    @palazzolo85 2 роки тому +1

    Subscribed. Your a good man, I’m a fellow controls engineer. Work with AB on a daily basis.

  • @bandapgbr1
    @bandapgbr1 3 роки тому +1

    Tim, Thank you so much for share !!!!
    Im from Brazil

  • @CristianoSantos-yy6dw
    @CristianoSantos-yy6dw Місяць тому +1

    sim como faço ? Outra dúvida estou precisando fazer um controle quando a frequência de pulsos aumentar do encoder quero que diminua a frequência do inversor, nesse caso um controle inversamente proporcional, qual o parâmetro devo alterar pra fazer esse controle inverso no Pf525? Desse já agradeço!

  • @victortarango101
    @victortarango101 Рік тому +1

    Tim excelent video I highly appreciate yours support for showing it😀

  • @jacksonsimon8632
    @jacksonsimon8632 2 місяці тому +1

    I enjoyed this tutorial session. I already learned a lot from you. Can you show me how to program an Allen Bradley 523 VFD with my laptop?

    • @TimWilborne
      @TimWilborne  2 місяці тому +1

      I like using Connected Components Workbench for that. Check out this video.
      ua-cam.com/video/81G0YY5XCS4/v-deo.html

  • @balabala-fw7gi
    @balabala-fw7gi 2 місяці тому +1

    Nice video sir, I learn AB plc and drives for your video reference.

  • @nuragasaric9596
    @nuragasaric9596 3 роки тому +1

    I did same thing and I/O didn't come on at all it whould be nice to get video about it .Thank you

  • @rxplusplates646
    @rxplusplates646 4 місяці тому +1

    Great videos as always! If i am using a momentary foot pedal to control the powerflex can I use the start command in the "Jog" output instead of the start?

    • @TimWilborne
      @TimWilborne  4 місяці тому +1

      Honestly I have never used the Jog feature, I should play with it sometime. The easiest way to do it is XIO Drive.Start OTE Drive.Stop. That way when ever the Start has a 0 in it, it will put a 1 in the Stop, and vice versa.

  • @anthonybuddini2828
    @anthonybuddini2828 Рік тому +1

    Hi Tim, thank you for the information. Very useful video...

  • @VictorValladares-r3r
    @VictorValladares-r3r 2 місяці тому +1

    Tim, how do you get that IP address you used on the VFD? do you just make that IP address up or do you get it from somewhere on studio? I'm assuming you make that number up from the last IP address you added?

    • @TimWilborne
      @TimWilborne  2 місяці тому +1

      Here is a video that lightly explains IP addresses
      ua-cam.com/users/liveW7Q5ZgvEWiw?feature=share

  • @fernandodepaulavicente9027
    @fernandodepaulavicente9027 3 роки тому +2

    PARABENS PROFESSOR SOU BRASILEIRO VENDO TODOS SEUS VIDEOS E DANDO LIKES.

  • @muhammadshehbaz7765
    @muhammadshehbaz7765 10 місяців тому +1

    its very interesting and informative video. thank you for making it

  • @alangutierrez1447
    @alangutierrez1447 Рік тому +2

    Can you do a video explaining a power flex 525 path splicing failed splice path

    • @TimWilborne
      @TimWilborne  Рік тому +1

      Do you have a yellow triangle beside of it?

  • @lalitpandey8023
    @lalitpandey8023 3 роки тому +1

    Thanks sir for this video, please share video on the use of sequence control in plant automation.

    • @TimWilborne
      @TimWilborne  3 роки тому +1

      Hi Lalit. We have that for RsLogix 500. You can find it at the following link. We have machine sequencing lessons in the works for Studio 5000 and Connected Components Workbench planned, with the notable missing method of sequencer instructions. I don't believe they are a good way of sequencing machine steps.
      twcontrols.com/allen-bradley-rslogix-500-lessons-for-the-micrologix-and-slc-plc

    • @lalitpandey8023
      @lalitpandey8023 3 роки тому +1

      @@TimWilborne Thanks alot for your support .

    • @TimWilborne
      @TimWilborne  3 роки тому

      @@lalitpandey8023 You are welcome.

  • @patrickhopman4350
    @patrickhopman4350 3 роки тому +1

    Have made a sequel video to this? I would like to see an example of programming speed control setting up some of the other parameters. Also, can it be configured to use either ethernet or the push button/potentiometer? Love your videos by the way, they are the best ones I've found at explaining things.

    • @TimWilborne
      @TimWilborne  3 роки тому +1

      Hi Patrick, check out this series, it has several different setups for the Powerflex 525.
      twcontrols.com/ac-drives-and-3-phase-motors

  • @guangyaoli6218
    @guangyaoli6218 11 місяців тому +1

    Thank you very much for your answer boss! One more question is if I use wifi in a plant. How to set ip address to match plc inrslink?Could you make a viedo show?

  • @kinikinrd
    @kinikinrd 3 роки тому +2

    Tim, I love you videos but this one brings up a question.
    The two ways you show to turn on and turn off the drive produce the same result but the first one is instantly recognizable as on-off and the second must be interpreted you might say. To the average person the first is easier to understand. Green button turns it on, red button turns it off. The second example has a latch which is not needed, otherwise they are the same. Both take two rungs. What is the benefit of using the harder to read method?

    • @TimWilborne
      @TimWilborne  3 роки тому

      The second one is what you will more commonly see and allows for much more control flexibility when you go beyond a basic start stop.

  • @funnyshortsdaily515
    @funnyshortsdaily515 6 місяців тому +1

    If my drive fails and I replace it do you have a vid on how to load the old parameters to it along with set up Ethernet connection?

    • @TimWilborne
      @TimWilborne  6 місяців тому +1

      Here is a video of backing up your Powerflex drive.
      ua-cam.com/video/81G0YY5XCS4/v-deo.html

  • @shawnspencer8766
    @shawnspencer8766 3 роки тому +1

    Awesome video
    Id be interested in seeing different speed set points and using the logic to change them (ie one button slow jog, second button fast jog)

    • @TimWilborne
      @TimWilborne  3 роки тому +2

      I just recorded that for one of our Patreon supporters. It should be public soon.

    • @joebilby1007
      @joebilby1007 2 роки тому +1

      @@TimWilborne Hey Tim, is the video still only for your Patreon supporters?

    • @TimWilborne
      @TimWilborne  2 роки тому

      @@joebilby1007 Here you go ua-cam.com/video/lPfHHnsCos0/v-deo.html

  • @joseangelrinconluengo5331
    @joseangelrinconluengo5331 2 роки тому +1

    how do i know which revision i have to put when im adding the drive? Thanks

    • @TimWilborne
      @TimWilborne  2 роки тому +1

      Go Communications, Who Active, right click the drive and select Device Properties.

  • @tgomidwest9399
    @tgomidwest9399 3 роки тому +1

    I think PLC to PLC communication would be a great topic to cover.

    • @TimWilborne
      @TimWilborne  3 роки тому +3

      We've hit Controllogix to Micro800 and Micro800 to Controllogix communications and we have Controllogix to Controllogix communications coming. Anything else come to mind?

    • @shawnspencer8766
      @shawnspencer8766 3 роки тому +1

      @@TimWilborne I see a lot of controllogix to SLC 500 communications at my job. That would be a cool topic to cover as well

    • @TimWilborne
      @TimWilborne  3 роки тому +3

      @@shawnspencer8766 I could cover that. I'll put it on the list Shawn.

  • @juanenriquerivera7808
    @juanenriquerivera7808 5 місяців тому +1

    How can I get one of the trainer boards that you use in your videos and what's the price?

    • @TimWilborne
      @TimWilborne  5 місяців тому +1

      Here you go
      twcontrols.com/plc-trainers

  • @benedalati1527
    @benedalati1527 Рік тому +1

    At 4:43, you mention downloading the program. What program? I put the parameters in the powerflex manually following your previous video. Was i supposed to write a simple start stop program and downloaded it to the controller? what should my output be? one more, can i delete the pwerflex drive and create one the way you show here. I wanted to delete it and start fresh but got a mesage"Are you sure you want this module and all og its child to be deleted?" sounds scary? Thanks for all of your informative videos. I am new to this and already have learned a lot by watching them. regards
    Ben E

    • @TimWilborne
      @TimWilborne  Рік тому +2

      Not following your question Ben. The program we made from 0:00 to 4:42 of this very video is what you are downloading.

    • @benedalati1527
      @benedalati1527 Рік тому +1

      Hi Tim, Thanks for the reply. What I am asking is which program you are referring to. i don't see you doing any program but you say let's download ( the program ??). Did you write a program. Do mind posting it along with the wiring for the input and output. I hope my question makes sense. Regards
      Be

    • @TimWilborne
      @TimWilborne  Рік тому

      From 0:00 to 4:42 we created a program and added the drive to the configuration. I'm still not following you.

  • @richardsonmoura593
    @richardsonmoura593 10 місяців тому +1

    Hi, thanks for all of your videos, really useful for me. Please could you tell me, how the plc keep the parameters for those inverters, I meanimg, we have a powerflex 225 burned out and we just set the IP on his HMI and all parameters was set and it works as built. How it happened? Thanks.

    • @TimWilborne
      @TimWilborne  10 місяців тому +2

      Automatic Device Configuration, check out this video.
      ua-cam.com/video/TZhuCUGcp3s/v-deo.html

  • @noname-g8e
    @noname-g8e Рік тому +1

    Could you make a video on how to use the powerflex 525 VFD PID loop control function in studio 5000 using the compactlogix plc?

    • @TimWilborne
      @TimWilborne  Рік тому +1

      That would make a good one.

    • @noname-g8e
      @noname-g8e Рік тому

      ​@@TimWilborne Could you make a video on how to control the powerflex VFD in studio 5000 using modbus?

    • @TimWilborne
      @TimWilborne  Рік тому

      @@noname-g8e You can only do Modbus to the Powerflex 525 over serial, not Ethernet. Here is a video connecting a Micro820 to it over serial.
      ua-cam.com/video/ARg2QHn3IB0/v-deo.html

    • @noname-g8e
      @noname-g8e Рік тому +1

      @@TimWilborne Do you have a 1769-sm2 Compact I/O module or a Prosoft technology MVI69E-MBS module you can use with your compactlogix plc to control a powerflex vfd besides the powerflex 525? I would like see a video on how to setup and use those modules in studio 5000 on the compactlogix plc to control a powerflex 4 vfd so that I can learn how to do it myself. I watched the video on the Micro800 Modbus RTU Serial Configuration and gave me some good information, but I would like to see a video on how to setup and use the 1769-sm2 Compact I/O module or a Prosoft technology MVI69E-MBS module in studio 5000 on the compactlogix plc to control a powerflex vfd .

    • @TimWilborne
      @TimWilborne  Рік тому

      @@noname-g8e No, don't have either of them

  • @mikebradley812
    @mikebradley812 2 роки тому +1

    Thanks for the videos, your doing a great job. When we have to replace a drive that is networked to a Compact Logix via ethernet, we often have problems getting the drive to work with the system. Is there a video that you have that covers troubleshooting these problems? Thanks again

  • @geesonmartinem.r4926
    @geesonmartinem.r4926 6 місяців тому

    Very detailed information.thank you Sir

  • @pablodigamon9360
    @pablodigamon9360 3 роки тому +1

    Thanks Tim. good Video Do you have video tutorial to how to set up IP number of 1794 AENT and 1747 AENTR

    • @TimWilborne
      @TimWilborne  3 роки тому +2

      Here is how I do it.
      plctools.com/how-to-read-and-write-an-ip-address-to-an-allen-bradley-1794-aent-flex-i-o-module/

    • @marcelodigamon4845
      @marcelodigamon4845 3 роки тому

      @@TimWilborne Thank you

  • @nandusuresh2202
    @nandusuresh2202 11 місяців тому +1

    Thankyou soo much for the videos ❤❤

  • @jwarf7864
    @jwarf7864 3 місяці тому +1

    Hello, is there anyway to add the powerflex 525 to a version 13 controller project? I have to AOP downloaded but they won't show up, when I try to add the 525 to the ethernet module in the tree? I found AOP's for ver.16-19 on the Rockwell site.

    • @TimWilborne
      @TimWilborne  3 місяці тому +1

      You would have to use the Generic Ethernet module. It isn't difficult to set up but I don't have a video on that. It's in the manual... if I'm recalling correctly. We did it in a recent class for some reason.

    • @jwarf7864
      @jwarf7864 3 місяці тому +1

      @@TimWilborne Thank you for your response. I think I will try updating the firmware to ver.17. We are limited to nothing above Version 19 due to Zenon HMI's.

  • @spokitive
    @spokitive 4 місяці тому +1

    Hello, So I had power flex 70 but it is now obselete and I replaced it with 525 so I followed same steps but I am getting module not configured after the download how do I fix that ? Also sometimes I can ping my PLC but when I try to connect to it it takes so long and sometimes it works and sometimes not what could be the issues ?Thank you

    • @TimWilborne
      @TimWilborne  4 місяці тому +1

      Wildly guessing one of the data link numbers are wrong

  • @philliptwin326
    @philliptwin326 3 роки тому +1

    I'd like to know if you could show us how to integrate a vision camera on a Controllogix or Micrologix over ethernet, please

    • @TimWilborne
      @TimWilborne  3 роки тому +1

      Hi Philip. I don't have the hardware for that.

  • @ManojYadav-rq8or
    @ManojYadav-rq8or 2 роки тому +1

    Hi tim can you help me how to do configuration of two device ome master plc and other ethernet module via wireless anybus bolt wifi

  • @iamcool8304
    @iamcool8304 Рік тому +1

    Do you have a video on how I can control a VFD on a compact logix PLC that is connected to a different compact logix?

    • @TimWilborne
      @TimWilborne  Рік тому +1

      I'm not following you. Are you saying that they are not on the same Ethernet network?

    • @iamcool8304
      @iamcool8304 Рік тому +1

      @@TimWilborne
      I have a L30-ER that is connected to 3 drives, 1 output and one input card. I want my L24ER-QBFC1B to be able to control a drive, and few inputs and a few out puts of the L30-ER.

    • @TimWilborne
      @TimWilborne  Рік тому

      @@iamcool8304 Sounds like produced and consumed tags between the L30 and the L24 would be the easiest solution if they are both connected over Ethernet. Here is a video on that.
      ua-cam.com/video/ABOAHyLcgSM/v-deo.html

    • @iamcool8304
      @iamcool8304 Рік тому +1

      OK Tim you passed that challenge with flying colors thank you.
      Now for my next question what if I wanted to control the same two PLCs using one HMI?

    • @TimWilborne
      @TimWilborne  Рік тому +1

      @@iamcool8304 Most HMI support more than one controller. You should be fine

  • @guangyaoli6218
    @guangyaoli6218 9 місяців тому +1

    boss .please show us asi gateway control in studio5000.tahnks a lot

    • @TimWilborne
      @TimWilborne  9 місяців тому +2

      Don't have one of those

  • @FaizanKhan-j6q2u
    @FaizanKhan-j6q2u 9 місяців тому +1

    good explaination thank you sir .

  • @brianm17
    @brianm17 3 роки тому +1

    At 8:43 I noticed that you have three options for the start source (#46, 48, and 50). Number 50 is already set to E/IP. Did you have to change source one to E/IP or is there a way to simply select source three as your control method?

    • @TimWilborne
      @TimWilborne  3 роки тому +2

      Hi Brian, you can configure digital inputs to switch between start sources and speed references. I have done this once, it would make for a good exercise. It had a 3 position Hand Off Auto selector switch. When in Auto, it's start source and speed reference was over Ethernet, but when in hand, its start source and Ethernet were from the drive I/O terminals.

  • @rahulrpatil3005
    @rahulrpatil3005 3 роки тому +1

    Brilliantly done 🙏👍🏼

  • @balakumaranrajavelu3218
    @balakumaranrajavelu3218 2 роки тому +1

    Hi Tim, Thank you for knowledge you share. I have to replace on same 525vfd but different version ( old is version 1.6 and new one is version 4.0). After copying vfd program and connected to plc but Ethernet not connecting. But same vfd working with same Ethernet IP if i control from my PC

    • @TimWilborne
      @TimWilborne  2 роки тому +1

      Chances are you have an electronic key and mismatch. The firmwares must match.

  • @SlavaGC8
    @SlavaGC8 21 день тому +1

    does IP have to match PLC? as in the first 3 numbers. BTW I followed the steps and it didnt work, I connected drive to workbench and double checked everything (realized my drive was 1.003 and was set up as 7.001). Long story short, nothing seemed to work until I cycled drive power and than boom.... magic.

    • @TimWilborne
      @TimWilborne  21 день тому +1

      Yes, the have to be in the same network

  • @keithhoffman-q8q
    @keithhoffman-q8q 4 місяці тому +1

    good video
    i have a question
    i need to know how to get a micro 800 plc to set the powerflex drive parameters on power-up via ethernet/ip or dsi and if any additional hardware is required other than ethernet cables

    • @TimWilborne
      @TimWilborne  4 місяці тому +1

      I don't believe the Micro800s support ADC (Automatic Device Configuration) so it would take quite a bit of work to set the drive parameters. If you need that feature, you probably need to look at a Compactlogix. Here is a video showing that feature. Curious, why do you need to set them on powerup? Is it just in case you need to replace a drive?
      ua-cam.com/video/C249NnJ4EmM/v-deo.html

    • @keithhoffman-q8q
      @keithhoffman-q8q 4 місяці тому +1

      @@TimWilborne correct,
      in the event of drive failure during production hours the maintenance crew will replace it and when they power up the panel it takes an additional 5 min to program the drive even if they have the "cheat sheet" for that machine
      as far as looking at CompactLogix the company cant afford swap out all the plc's to those at the moment
      the old automation tech was able to do it with a micrologix 1400 and an adaptor (i assume it was for Modbus) to set parameters on a power flex 4
      now just a guess on my part but can you send a write string or word to the powerflex something like a program variable?
      variable "p36" with a value of "5"

    • @TimWilborne
      @TimWilborne  4 місяці тому +1

      We long as the parameters are limited, it would be possible

    • @keithhoffman-q8q
      @keithhoffman-q8q 4 місяці тому +1

      @@TimWilborne outstanding, i think i would not need more than 5 parameters such as a preset speed, start source, and basic motor parameters like FLA etc.

  • @smartpaco8360
    @smartpaco8360 2 роки тому +2

    If the 525 is not on the list, how is it possible to add it?

    • @TimWilborne
      @TimWilborne  2 роки тому +1

      Are you right clicking "Ethernet" then selecting new module? This brings up a different list than adding standard I/O.

    • @smartpaco8360
      @smartpaco8360 2 роки тому

      Yes, I have other powerflex devices but not 525 unfortunately

  • @shapoorkosarimehr9404
    @shapoorkosarimehr9404 3 роки тому +1

    Hi TIM
    I am starting a new project with a 1769-L24ER controller. I connected up to the USB port and did a firmware flash to V21.011. Everything seemed to go normal. At the end the controller would not communicate back to the ControlFlash program that it had the new version.
    Now I get the solid red OK light and when I power it up it wont do the diagnostic test where it will runs through and lights all the lights. The USB port wont work either.
    Any ideas

    • @TimWilborne
      @TimWilborne  3 роки тому +1

      The firmware upgrade failed. Time to call Rockwell, it will need to be sent back.

  • @2012jordanat
    @2012jordanat 2 роки тому

    These videos are absolutely phenomenal! It's tutorials and explanations like these that have helped me teach myself these automation systems, so thank you so much for your time and effort here!
    I don't suppose you have plans to pull together a video similar to this one, expect using a Micro800 series with the PF525? I'm looking to control one using an 850, a PanelView, and a PF525...

    • @2012jordanat
      @2012jordanat 2 роки тому +2

      And as soon as I finished this comment, I saw your "Program a Micro820 to Control a Powerflex 525 with a UDFB" video in my upcoming videos list...so thank you!

    • @TimWilborne
      @TimWilborne  2 роки тому +2

      You are welcome!

  • @eliekhananya1551
    @eliekhananya1551 3 роки тому +1

    Do you know generally how old the revision on the vfd can be until it stops communicating? Bc I think we had a power flex 525 with a revision 3 that went bad, replaced it with a 6 and didn’t communicate bc in the plc it was a 3.

    • @TimWilborne
      @TimWilborne  3 роки тому +1

      You must change your major revision in Studio 5000. I should have thought to cover this. I'll put it on the list Elie.

  • @pratik9057
    @pratik9057 3 роки тому +1

    Thank you so much for the video, I have to make some changes to my data type the default data type doesn't have the actual current. what should I do to get actual current in the Input which are read from the VFD

    • @pratik9057
      @pratik9057 3 роки тому +1

      Ok i found it, its in the drive properties/Device Definition/Connection format. thank you very much

    • @TimWilborne
      @TimWilborne  3 роки тому +1

      Glad you found it.

  • @Victor_Sj
    @Victor_Sj 3 роки тому +1

    Hi, i would like to change a powerflex 525 installed for other new one, but after It's configured, the ethernet led port only flashing and not connect to the net to recive and manage the vfd via ethernet?
    thancks

    • @TimWilborne
      @TimWilborne  3 роки тому +1

      Sounds like you need to double check the IP address configuration.

    • @Victor_Sj
      @Victor_Sj 3 роки тому

      @@TimWilborne But the parameters ip and mask net are correct

  • @guangyaoli6218
    @guangyaoli6218 11 місяців тому +1

    Boss. When i meet two enthernet cards in plc with different ip address. Which ip address i should set up in my pc for matching? Thank you ceru much!

    • @TimWilborne
      @TimWilborne  11 місяців тому +1

      The one that is on the network that you are plugging into.

    • @guangyaoli6218
      @guangyaoli6218 11 місяців тому +1

      @@TimWilborne thank you boss

    • @TimWilborne
      @TimWilborne  11 місяців тому

      You are welcome

  • @douglaslinton8292
    @douglaslinton8292 3 роки тому +1

    HI Tim Your videos are great my question to you how do you connect and disconnect the 525 from within the studio 5000

    • @TimWilborne
      @TimWilborne  3 роки тому +1

      Hi Douglas. Do you mean the inhibit function?

    • @douglaslinton8292
      @douglaslinton8292 3 роки тому +1

      no i was just setting up for the first time and saw a means to connect to the via project or physical i chose physical so was just wondering how to disconnect since i was able to connect

    • @TimWilborne
      @TimWilborne  3 роки тому

      @@douglaslinton8292 Still not sure I'm following your lingo. Do you mean viewing the module properties of the Powerflex drive and Studio 5000? If so the connect is more of make sure the parameters match what's in the offline and you'll get used physical, which is what's in the drive, or use project, which is what's in Studio 5000 after that. Not looking at Studio 5000 right now but I don't believe there's actually a disconnect or a need to disconnect afterwards. Just close the module properties.

    • @douglaslinton8292
      @douglaslinton8292 3 роки тому +1

      for example just like how you can go offline and online with the plc i was wondering if that was possible to do that to the vfd from within the studio 5000 software after you would have establish connection to the drive from the software

    • @TimWilborne
      @TimWilborne  3 роки тому

      @@douglaslinton8292 No. It's more like my previous reply.

  • @benedalati1527
    @benedalati1527 Рік тому +1

    Hi Tim, Thanks for the video. I have done all of the steps in it. I can ping my controller from my PC and when I check the ip address of the drive it is 192.168.1.12 in the same subnet as the controller 192.168.1.10 and my PC. But I am getting communication error when I click on the connection tab of the drive. Don't know why? Thanks again

    • @TimWilborne
      @TimWilborne  Рік тому +1

      What is the error? Also, can you ping both of them from your PC?

    • @benedalati1527
      @benedalati1527 Рік тому +2

      @@TimWilborne the error message is communication error, no number. No i can't ping the PF. Thanks

    • @TimWilborne
      @TimWilborne  Рік тому

      @@benedalati1527 If you can't ping the Powerflex then you need to hit the basics. Here is a video to help.
      ua-cam.com/users/liveW7Q5ZgvEWiw

  • @souravsain4178
    @souravsain4178 Рік тому +1

    How to change IP address in Power flex video-18?

  • @LearningInVR
    @LearningInVR 3 роки тому +1

    Only have version 20 of studio 5000 /
    . Will trainer work with this version(20)
    If not I gotta go ccw 12 / micrologix 800 / logic theme but I rather compactlogix .... which is ideal but I cannot get the proper version new at work .... only service version its 789 so I don't think it's the right one to program and train with but I have a full version 20 pro

    • @TimWilborne
      @TimWilborne  3 роки тому +1

      Yes, version 20 is the minimum version that will work with our trainers.

  • @nelsonpantaleon7751
    @nelsonpantaleon7751 2 роки тому +1

    How about siemens like s7 1200 controlling thevspeed of vfd same like this video i hope you have video for s7 1200 siemens

    • @TimWilborne
      @TimWilborne  2 роки тому +1

      No Siemens videos as of yet but we're exploring ideas.

  • @tarekmohsen7572
    @tarekmohsen7572 Рік тому +1

    Thank you very much

  • @justinpuzak2558
    @justinpuzak2558 3 роки тому +1

    can i program a compact logix l32e with studio 5000 lite, (the 950$ version you were talking about)
    im going buy that version but i only have a compact logix l32e to practice on and dont know if they're compatible...
    also. i told my boss at hershey about your classes and hes very interested. we are waiting till they hire 2 more guys to set up classes for everyone. do you have a buisness email i can give to my boss incase he has any questions.

    • @TimWilborne
      @TimWilborne  3 роки тому +1

      You could also use Mini if you are only programming in ladder. You can find more about our PLC training at twcontrols.com/plc-lab

  • @CristianoSantos-yy6dw
    @CristianoSantos-yy6dw Місяць тому +1

    Como usar uma entrada digital pra desativar a função PID ?

    • @TimWilborne
      @TimWilborne  Місяць тому +2

      You probably want to look at using it to switch to speed reference 2.

    • @CristianoSantos-yy6dw
      @CristianoSantos-yy6dw Місяць тому +1

      @@TimWilborne sim como faço ? Outra dúvida estou precisando fazer um controle quando a frequência de pulsos aumentar do encoder quero que diminua a frequência do inversor, nesse caso um controle inversamente proporcional, qual o parâmetro devo alterar pra fazer esse controle inverso no Pf525? Desse já agradeço!

  • @oanthientam9189
    @oanthientam9189 Рік тому +1

    thansk you , please help me , i can't find 525 inveter and adding into app rslogix5000, how to find that. best regarsd

    • @TimWilborne
      @TimWilborne  Рік тому +1

      Make sure you're right clicking Ethernet then selecting new module. Otherwise it won't show up, then enter Powerflex 525 into the filter box

  • @automotivate.vamshi1549
    @automotivate.vamshi1549 2 роки тому +1

    Nice video.

  • @tonymontero4752
    @tonymontero4752 3 роки тому +1

    hi TIM i am wonder can we program VFD BY RSL 500 software i looked at controller i didnt see
    thank you

    • @TimWilborne
      @TimWilborne  3 роки тому +1

      Program as in set the parameters? Possible but very difficult. Run? Yes, you can use messaging instructions.

    • @tonymontero4752
      @tonymontero4752 3 роки тому +1

      @@TimWilborne thank you but I was looking for controler at software but I couldn’t find
      Also one more question pleas if we have any other typ VFD like Siemens can we program it by RSL5000 or should be just Allen Bradley
      Thank you

    • @TimWilborne
      @TimWilborne  3 роки тому +2

      @@tonymontero4752 The Powerflex 525 can be programmed with Connected Component Workbench. Siemens has its own software as far as programming.

    • @tonymontero4752
      @tonymontero4752 3 роки тому

      @@TimWilborne thank you

    • @tonymontero4752
      @tonymontero4752 3 роки тому +1

      Do u have video shows how to program power flex by connected work bench
      Thank you

  • @phucrau007
    @phucrau007 6 місяців тому +1

    Thank you Sir🤝🤝🤝🤝

  • @davem5392
    @davem5392 3 роки тому +1

    I had many problems following this video i wanted to list some things for others who have the trainer and their Studio 5000 may have locked up and sent many errors to AB. I changed many things not 100% sure what did what.
    Program would not download deleted ethernet connection, only left ethernet IP active and changed to windows default driver. Took HMI out of run on config screen. The program seems to have problems with blank spaces on PLC and Drive descriptions.
    When downloaded I tried to double click on drive it stopped like yours but my powerflex connection was grayed out in use physical so i had to use project. Then I got error writing port 0 Parameter 122 value out of range. I clicked ok and then double clicked drive and all loaded properly.
    Also for others with trainer steps in video may not work for instance buttons on drive because this is already changed in drive to ethernet IP.
    Really not 100% sure how i got myself in so many problems but maybe some of these steps will help others

    • @TimWilborne
      @TimWilborne  3 роки тому +1

      Hi Dave. Yours should have already been set up for this but I know we had some issues with IP addresses. Try doing a factory reset as shown in the following video and see if that smooths out the steps.

  • @Sakthi_R
    @Sakthi_R Місяць тому +1

    Okay...but, How to program for reverse operation...😢

    • @TimWilborne
      @TimWilborne  Місяць тому +1

      Use the direction tag to reverse the start

  • @christopherdean2893
    @christopherdean2893 3 роки тому +1

    This is what I see more and more in the field. Most drives are controlled over ethernet

  • @flaviomartins48
    @flaviomartins48 3 роки тому +1

    otimo ja me ajudou.

  • @alxdufour
    @alxdufour Рік тому +1

    awesome

  • @जीवनदर्शन-ध2छ

    Failed to splice the path errror PF525??

    • @TimWilborne
      @TimWilborne  Рік тому +2

      It usually means no connection or firmware mismatch. Can you ping the drive? What is your IO Light doing?

    • @जीवनदर्शन-ध2छ
      @जीवनदर्शन-ध2छ Рік тому +1

      @@TimWilborne Actually my drive is healthy ,but ot didnot accept command from ethernet ip communication,so i reset it to default.I tried your communication video step by step but no response ,but when i change ip it doesn't ping and didn't showing in RS links.I tried to set ip at automatic in my pc,but its not communicate.

    • @TimWilborne
      @TimWilborne  Рік тому +1

      If you can't ping it then you need to check your network configuration.

    • @जीवनदर्शन-ध2छ
      @जीवनदर्शन-ध2छ Рік тому +1

      Thanks for your kind attention and Support 😊🙏.Error solve.Vfd run over ethernet.

    • @TimWilborne
      @TimWilborne  Рік тому +1

      Outstanding! What did you find?

  • @Time-Trvlr
    @Time-Trvlr 3 роки тому +1

    It gets fun when altering the mask ie 255.255.0.0

    • @TimWilborne
      @TimWilborne  3 роки тому +2

      I'm thinking I might to a video on subnets Joel.