Cooker Circuits Diversity, 15kW load, 32A circuit breaker.

Поділитися
Вставка
  • Опубліковано 18 гру 2024

КОМЕНТАРІ • 497

  • @shadow-Sun
    @shadow-Sun 4 роки тому +108

    Your method of teaching is absolutely first class every word you use has value and is not in the least superfluous to your explanation when setting out your examples etc I really do enjoy these mini lectures and the skill with which you impart your subject matter . By far one of the best you tube channels out there bar non on electrical matters . Thankyou for your effort on this channel which is reflected in your number of loyal subscribers .

    • @millomweb
      @millomweb 4 роки тому +2

      "every word you use has value and is not in the least superfluous" - oh yes some are - when he's in dry humour mode - which occurs a few times in his videos.

    • @TheChipmunk2008
      @TheChipmunk2008 4 роки тому +1

      In this video, paraphrasing: "if you're the type of person who puts it in and just uses it for 20 years without cleaning behind it, this does not apply to you" (Which from my experience seems to be most people!)

    • @richardwash6678
      @richardwash6678 4 роки тому +1

      Totally agree with every word!

    • @Mark1024MAK
      @Mark1024MAK 4 роки тому +1

      TheChipmunk2008 - what’s this strange thing you speak of “cleaning”? 😂

    • @jackalek
      @jackalek 4 роки тому +3

      I can only second that! Also very clear English and good pronunciation which really help if someone is not native speaker.

  • @Thruxtonite
    @Thruxtonite 9 місяців тому +4

    Excellent, informative video thanks. We’re about to have our kitchen refitted and are swapping to an induction hob from gas and a number of kitchen suppliers and electricians have told us that we’ll need a dedicated 32Amp supply from the consumer unit even though we have an existing 32Amp cooker circuit with only our single electric oven on it. One suggestion we were given was to put the new Induction hob on the existing oven circuit and then add the 3.2kW oven to the kitchen socket ring main, hardwired. Now I’ve watched this and learnt about Diversity I know that both the new 7.35kW induction hob and 3.2kW oven (20.77Amp total) can be run on the existing 32Amp cooker circuit . Thank you

  • @c4jax
    @c4jax Рік тому +3

    Thankyou for the clear explanation and break down of the explanation into simple steps. The hidden humour of cleaning behind a 20 year cooker made me chuckle too.

  • @GazzJ82
    @GazzJ82 4 роки тому +41

    I have lost count of the times that someone has called me in to install a cooker and the salesman has told them it will need a 50a supply and everything upgrading. Haven't needed a supply greater than 32a yet. :) Great video as always.

    • @musashigundoh
      @musashigundoh 4 роки тому

      The manual for my Gorenje cooker states that it requires a 32A or 40A breaker ("depending on type", so I assume 40B or 32C?) and a 3*4mm2 flex cable. But I have a C40 breaker on this circuit, so I used a 3*6mm2 flex cable.

    • @Dailymailnewz
      @Dailymailnewz 4 роки тому

      When I studied a long time ago it was always 60 amps- things have changed allot since...

    • @gloomyblackfur399
      @gloomyblackfur399 9 днів тому

      I wish we were more sensible in the US. Our code mandates a 50 amp breaker and 6 AWG (16mm2) wiring. And since we have split phase (the electronics on a 240v oven use 120v), that means four 16mm2 wires (line 1, line 2, neutral, ground). Colossal waste of copper.

  • @SJM689
    @SJM689 3 роки тому +8

    My apprentice was talking about you today, said you were better than her college tutor. I do believe she learns far more from you than college....so thought I'd see for myself and I don't think she's wrong.....keep up the good work

  • @bartman58
    @bartman58 4 роки тому +100

    I honestly think they should get you to write the next edition of the wiring regs John👍🏻

    • @mb-electricalservices
      @mb-electricalservices 4 роки тому +1

      Amen to that.....

    • @w415hyz
      @w415hyz 4 роки тому +13

      Agreed. And once the regs are confirmed and finalised, that’s that!!!! I’m fed up of regs changing, you never know wether you’re coming or going.
      The only reason the regs change is for some clown to justify his/her job:
      * walk into building*
      *hmmmmm..........what nonsense can we make up today just to piss everyone off??*
      *ohhhhh, I know,*

    • @cocoino2307
      @cocoino2307 4 роки тому +5

      @@w415hyz if they didnt come up with new ass rules they would be out of job, so why you think they do it

    • @bartman58
      @bartman58 4 роки тому +1

      A couple of points in this video I have had a disagreement with my assessor over the last couple of years......he nearly shat when I showed him this😂😂

    • @Sergey3023
      @Sergey3023 4 роки тому +4

      @@w415hyz You forgot about £ that they earn from sale of these books😁

  • @cathalwright5611
    @cathalwright5611 3 роки тому +11

    As a building control officer with no electrical training I am so impressed with the explanations given in your videos. I very much appreciate your time and effort, you have explained clearly with clear understandable examples. I am not an electrician but feel more confident in my role with regards to understanding electrical work in domestic properties. Thank You .

  • @NOELTM
    @NOELTM Рік тому +4

    Really helped me with my kitchen hob/oven install and working out the load with diversity applied. Thank you.

  • @a146674
    @a146674 Рік тому +3

    Just about to start a kitchen renovation, your videos have literally put me at ease and I now have a great understanding of the work that will be needed to be done and how it can be done. Fantastic!!

  • @francisexperience
    @francisexperience 2 місяці тому

    Your presentation are the best I have even seen, clear precise and easy to understand, nothing short of excellent Thank you.

  • @keithhowes402
    @keithhowes402 4 роки тому +9

    As an old spark I wished I'd have had you as a lecturer back in the late 1960s when I was at college

  • @mikes6844
    @mikes6844 4 роки тому +7

    This has been a refreshing albeit vindicating video for me, fantastic/straightforward and common sense view on the difference between the use of 4mm and 6mm size cable. Thank you John. 👍🏻👍🏻👍🏻

  • @ipmoroca
    @ipmoroca 4 місяці тому

    I did find your channel in the past with great explanation, but this just reminded me of the effort you go through to break down things! Keep up the great work!

  • @maciejtryka9145
    @maciejtryka9145 3 роки тому +1

    One of the best videos on domestic cooker installation, so many sparkies don't understand it and panic when coming to install electric range cooker- just dividing W/V and coming up with 16mm2 cable, not taking into account thermostats and energy regulators which allow for use of diversity factor.
    The way its presented is so simple that every layman would understand.
    Well done Sir!

  • @SqwarkParrotSpittingFeathers
    @SqwarkParrotSpittingFeathers 4 роки тому +10

    Very informative as usual. I shall be placing on any consumer units installed a notice saying "in compliance with JW regs", as JW regs are more authoritive and clearly explained than the On Site Guide and BS7671:2018, lol.

  • @ThePa1ch
    @ThePa1ch 4 роки тому +5

    I love this video. Thank you. It's so frustrating seeing people on forums advocating 10mm2 cable with 45a MCBs for cooker circuits without any rationale.

    • @spencerwilton5831
      @spencerwilton5831 4 роки тому +2

      P JD You need to come to mine for a full Christmas dinner! Three ovens, eight rings and warming cupboard going full tilt. If the lights don't dim across South London it means I have forgotten one of the veg.

    • @gavkit
      @gavkit 4 роки тому

      @@r.h.8754 22amps

    • @johnburns4017
      @johnburns4017 3 роки тому

      @@spencerwilton5831
      The old Christmas dinner fear. They will not be all on at once as thermostats cut in.

    • @Speedkam
      @Speedkam 8 місяців тому

      @johnburns4017 if they are all on, how long until it trips?

  • @johnburns4017
    @johnburns4017 4 роки тому +5

    Some put sub CU's in kitchens to keep all kitchen appliance isolation switches at one convenient point. Grid switches can do the same with switches available with words like _cooker,_ _fridge,_ etc, on them. A small CU using double pole mcbs is cheap and quicker to install. About 15 years ago MEM made a kitchen specific box and isolation switches with the switches labelled _hob,_ _fridge,_ etc. I have not seen it sold for a long time.
    Where all heavy appliances are in the kitchen (even an immersion in a kitchen cupboard), I have seen a heavy cable from the main CU at the front of a house run to the kitchen at the back of the house in a sub CU for the kitchen. It reduced the volume of cables needed simplifying the installation. Quicker to install and local isolation of the appliances at the sub CU.

  • @TupmaniaTurning
    @TupmaniaTurning 4 роки тому +14

    Love this channel. Always something to learn and I’m not a sparky!

  • @leea1988
    @leea1988 Рік тому +1

    This has answered a question I've long wondered about. You're a champion, thankyou!

  • @ApacheSenzala
    @ApacheSenzala 2 роки тому

    Oh my god I wish I had seen this before so helpful and reassuring love your matter of fact tone and the clear and concise math

  • @4544481
    @4544481 3 роки тому

    For me, this is the best site for electrical know how. I very much appreciate your knowledgeable, helpful posts. First class & very thorough👍

  • @yvonfem
    @yvonfem 4 роки тому +3

    Brilliant John you have a fantastic way of explaining things I'm not a spark but I always find your channel entertaining and I actually understand it thank you

  • @kevinpickett7249
    @kevinpickett7249 4 роки тому +1

    So well explained and as previous comments anybody could learn with your technique of teaching

  • @Oldfellas1
    @Oldfellas1 3 роки тому +2

    John, greatly explained, thank you. Found your channel by chance and now wonder how I ever did without it .

  • @ronalddobson3130
    @ronalddobson3130 3 роки тому

    Thanks again, John. Not the first time you've saved me money and educated me.

  • @samplumbe3288
    @samplumbe3288 3 роки тому

    Love your dry sense of humour. Great tips. Thanks

  • @lukwal3514
    @lukwal3514 3 роки тому +4

    In my opinion you do best tutorials on British you tube about the science and practical things regarding electric work.
    Well done👌

  • @viktorskostiks770
    @viktorskostiks770 4 роки тому +1

    Can find out more from your videos than from the college. Many thanks for your work.

  • @4addevelopments139
    @4addevelopments139 Рік тому

    Yet another fantastic video for a learner like me. I didn’t know there was such a thing as dual outlets for ovens/hobs.

  • @MrPDawes
    @MrPDawes 2 роки тому

    Having just installed an induction hob to replace my gas hob and had to run a new cable for it, am quite happy I used 6mm sqr. Cable is run in trunking between brick wall as this was the only way to get power to it. Very happy it won't be heating the wall up. I do have cavity wall insulation though so needed to uprate the cable.

  • @colinhubbard4826
    @colinhubbard4826 4 роки тому +7

    Often we don’t know what the builders will do after our 1st fix. Some jobs the ceilings/floor joist voids are left empty and some get pack with insulation. We tend to use 6mm to cover ourselves on this basis

    • @MH-sf5ml
      @MH-sf5ml 4 роки тому

      Here here. John is an example of relying on books rather than foresight.
      I still remember his video on why it was pointless to replace rewireable fuses with the push-in resettable style.
      Except for the fact that a lot of pensioners can't afford to get a new dB and a full EICR.

    • @cocoino2307
      @cocoino2307 4 роки тому

      you should always future proof it aswell, we dont know what kind of powerfull cookers we might get in 10 20 years

  • @markburgess2327
    @markburgess2327 Рік тому

    Excellent explanation, thank you. And I enjoy your wry sense of humour.

  • @sidwainhouse
    @sidwainhouse 4 роки тому

    I find it really helpful that a lot of manufacturers are giving the ratings now in kWh rather than kW, very helpful when designing a circuit...

  • @literoadie3502
    @literoadie3502 4 роки тому +1

    Great video John. I recently installed a cooker circuit, but never gave the cable size much thought and just assumed 6mm cable was a good choice, and certainly seemed to be the norm. I now realise 4mm is perfectly adequate on a 32A MCB. Thanks

  • @RJSElectricalCheshire
    @RJSElectricalCheshire 4 роки тому +7

    Great video as always John. I've always installed a cooker circuit on 6mm because that's the way it's always been done. I've always got 4mm that rarely gets used and keep buying rolls of 6mm. Time to start using up the 4mm me thinks 😃😃

  • @Event13
    @Event13 3 роки тому +1

    Exactly what I wanted to know. I'm a time served installation electrician with 40 years in the game and although I don't do much domestic I always thought a cooker switch was supplied with a minimum of 6mm. As John mentions this is a hangover from the old rewirable fuse ratings. Excellent explanation proving you're never too old to learn but I'd probably still run 6mm over any kind of distance just in case of containment or lagging etc or maybe they wanted some sort of unusually high rating oven. Saying that have you seen the price of 6mm T&E recently? LORD. It's very tempting to do in 4mm but it feels so wrong.

  • @grahammchardy9249
    @grahammchardy9249 4 роки тому +1

    I can now think of quite a few small domestic properties with 2 cooker circuits. Seems a pointless waste of copper. Thanks for clearing up the misconceptions.

  • @nervousfrog101
    @nervousfrog101 2 роки тому

    Thank you so much for this video. I was looking to get my dual fuel range cooker replaced with a fully electic one so I wanted to get my head round what was needed before getting an electrician to quote. I started looking at cookers online and they were quoting max powers of 15kw but only needing 32A breaker etc which just did not add up from my basic understanding so thank you very much for explaining.

  • @heiltd1286
    @heiltd1286 3 роки тому

    Eloquently and clearly elucidated as always.

  • @jafarsunny1762
    @jafarsunny1762 4 роки тому

    J W you are the star of the you tube electrical video. Need more from you.

  • @williamstewart1266
    @williamstewart1266 3 роки тому

    top video the whole of the uk needs to protect this man!!

  • @SME_Ste
    @SME_Ste 4 роки тому +24

    Love it John many a time i’ve been doubted when installing 4mm for cooker circuits when installation methods allow.
    I’ve lost count have many times fellow youtubers are pulling in 10mm supplies for hob/oven combos, which is ridiculous.

    • @musashigundoh
      @musashigundoh 4 роки тому +6

      Well, a 10mm2 cable won't hurt anything... Except your wallet and your finders, I guess.

    • @TheChipmunk2008
      @TheChipmunk2008 4 роки тому +6

      10MM is a BEOTCH to deal with in any normal accessory box. I agree with the person elsewhere in this comments section that says it doesn't belong in a domestic environment except as a feed to a specific outbuilding or second fuseboard. In which case you're not going to be terminating into an accessory box.. The number of electric showers that have exposed primary insulation outside the box either in the wall or roofspace because there's no physical way of doing otherwise even with a 47mm box... is countless

    • @und4287
      @und4287 4 роки тому

      10mm is overkill, unless they have multiple cookers

    • @nafizkhan7748
      @nafizkhan7748 4 роки тому +2

      6mm is the correct size if the cables are partially covered in insulation. You got to derate the cables based on installation method.

    • @thomasbonse
      @thomasbonse 4 роки тому

      Is there not a regulation concerning box fill? I know the US version has a section specially addressing box fill and minimum volumetric dimensions.

  • @tarassu
    @tarassu 4 роки тому

    I wired my cooker with 1.5mm2 cable. 4 tops and one oven with grill.
    Well.. MCB was 3xB13A. Works perfectly.

  • @KINGWD0110
    @KINGWD0110 2 роки тому

    Very informarive video, no need to waste money on larger cables for 2 MCB's =).
    Thanks,

  • @Observer-hl3mm
    @Observer-hl3mm 3 роки тому +4

    Method C means clipped directly, which is unlikely to be found in a modern kitchen. Hidden in a conduit inside the wall (method A) is far more usual. Which corresponds to 6 mm2 at 32A MCB.

  • @electricery
    @electricery 4 роки тому +13

    As usual, an excellent video John, Love the way you say 6mm is installed just because some electricians insist on doing things the way they’ve always been done. I find the same applies to bathroom lights, why do they automatically get installed with pull switches or with plate switches outside the room when you can often install a plate switch in the bathroom as long as its out of zone 1 or 2, also ring circuits get Installed just because they have always done it that way

    • @markgilder9990
      @markgilder9990 4 роки тому +3

      Myhippocampus I tend to do rings for utility and kitchen, radial circuits for remainder of house. 👍🏻Just makes sense.

    • @jaydenplaysguitar3896
      @jaydenplaysguitar3896 3 роки тому

      Rings for utility and kitchens are a must in my opinion. Fair power distribution across a circuit is an important factor to consider when designing.

    • @electricery
      @electricery 3 роки тому +1

      @@jaydenplaysguitar3896 if only people would actually design rings with "fair power distribution across the circuit" trouble is it never happens, rings are always installed in the easiest, shortest route from socket one to the next rather than considering how much load might be on one leg, which is normally the dishwasher, washing machine, kettle, oven, microwave all next to each other on the same leg. SparkyNinja did a good video on balancing rings and loading a year back

  • @sankyeat
    @sankyeat Рік тому

    Great Video! Please keep making videos like this they're amazing.

  • @chrisrhodes1127
    @chrisrhodes1127 6 місяців тому +1

    Diversity Perfectly explained !

  • @Watan-jan
    @Watan-jan 3 роки тому

    Thanks John for producing easy understanding video, I would be lost with out your explanation. Thank again

  • @cambridgemart2075
    @cambridgemart2075 4 роки тому +9

    Unfortunately that's what our electrician did, but he failed to note our split level oven has a cleaning mode that runs all the elements for 90 minutes, bringing the oven up to 470C; without fail, it trips the breaker midway through the cleaning cycle.

    • @jwflame
      @jwflame  4 роки тому +4

      What is the total load of the oven?
      To trip a 32A circuit breaker in 45 minutes would require well over 40 amps continuously, which would be a heating load in the region of 9-10kW, which seems grossly excessive for any oven.

    • @loosecannon5813
      @loosecannon5813 4 роки тому +2

      6mm cable is acceptable for 40A MCB (clipped direct)

    • @cambridgemart2075
      @cambridgemart2075 4 роки тому +1

      @@jwflame I dug through the manual and it states it should be fused at 16A and has a max consumption of 2900W. I'll have to get a clamp meter on the supply cable to see what it is drawing in cleaning mode.

    • @millomweb
      @millomweb 4 роки тому +5

      @@cambridgemart2075 Something fishy there then - if rated 16A and tripping a 32A breaker ! Faulty appliance ?

    • @TheChipmunk2008
      @TheChipmunk2008 4 роки тому +3

      Has he replaced a traditional oven with it? (they often used a 13A plug onto the ring mai...err ring final ;) ) Kitchen companies are AWFUL for that... sell a customer a self cleaning oven without telling them 'you're gonna need an electrician install a dedicated 16 or 20A circuit.
      If it's on the same ring as the rest of the house (often in older properties without a dedicated kitchen ring) a constant 2.9Kw load might be competing with other appliances.

  • @robholding
    @robholding Рік тому +1

    Exactly what I need to know. thank you. Excellent explanation!

  • @johncope6243
    @johncope6243 4 роки тому +1

    Great video with well explained detail. Helped me [DIY] plan my kitchen electrics ready for sparky. On the point of detail: six square millimetres is six times six which equals a surface area of thirty six millimetres. six millimetres squared is a surface area of six millimetres ;) (at least as I understand it?)

    • @tomporter6182
      @tomporter6182 3 роки тому

      That's the wrong way around surely... 6mm squared is 36, (as in 6 squared = 36), 6 square mm is 6 square mm

  • @johnburns4017
    @johnburns4017 3 роки тому +1

    A 4mm cable with a 32A mcb at CU. A hob and oven to be connected.
    A hob can be connected directly to the 4mm cable. Fine. As you said, a 3kW oven will never draw more than about 13A, unless in a fault situation. So, the oven can be plugged into a 15A fuseless round pin plug and socket which is off the 4mm cable, behind the oven. 15A round pin plugs are still legal on radials on directly on a final ring circuit (can be on a radial spur circuit off a final ring). Using a normal square pin 13A plug gives an inaccessible fuse. Fuses ideally should not be inaccessible.

  • @tcpnetworks
    @tcpnetworks 4 роки тому

    Methods in Australia - 4mm required, 32A RCBO mandated, isolation switch installed within 1.5M of device, maximum distance run of 20M, no de-rating. However, we've just done a run of houses with 3-phase domestic units. They are using a 4mm by three phases to get the induction ranges working properly.

  • @StewSims
    @StewSims Рік тому

    Brilliant video thanks. We are putting in a new cooker (induction hob and double oven rated at 10.7kW) and have been advised by an electrician that the existing 32A MCB needs upgrading to 40A and existing 6mm cable from CU swapped with 10mm! Doesn't seem right to me based on the diversity calculations and would involve significant works. The wiring is fairly old but all tested recently and I don't see why we should have to 'upgrade' it. Might seek a second opinion from another sparky.

    • @jwflame
      @jwflame  Рік тому +1

      32A will be fine for that. 6mm² cable can be rated to well over 40A depending on how it's installed so probably wouldn't have needed upgrading even if the MCB was changed to 40A.
      An induction hob will use less energy overall compared to a conventional electric. Some do have higher power boost settings, but those are only used for short periods so won't be a problem.

  • @richardwash6678
    @richardwash6678 4 роки тому +2

    Brilliant video John, as always. Love the way you explain things. 👍

  • @simonhowle6576
    @simonhowle6576 5 місяців тому

    very very clear explanation. Thank you John.

  • @wizard3z868
    @wizard3z868 2 роки тому +1

    I being from the states run 50amps 240 volts 12,000watts (6awg/4mm) and use 1inch conduit for future upgrades

  • @manchestercity01
    @manchestercity01 3 роки тому

    Top job well explained and nice and calm while showing each example. This has to be my go to site cheers

  • @seandempsey9396
    @seandempsey9396 3 роки тому

    Fantastic.
    Very well explained
    Clear and easy to understand. Thank you John.

  • @TheChipmunk2008
    @TheChipmunk2008 4 роки тому +1

    One case in the US I remember where the oven element DID transform to something that randomly demands more power... 240v oven element shorted to ground somewhere near the middle (which being a centre tapped 120-0-120 system didn't have much effect). No GFCI (rcd).. eventually water got in during cleaning, and began to saturate the mineral insulation... long story short, it still worked but the customer said it was sparking and kept getting brighter and brighter in the bottom of the oven. It''d burned down to about 1/3 of its length on one leg (the other was open circuit)... and was pulling about 30 amps on its own from 120 to ground. Quite scary as back then stoves used a 3 prong plug and grounded via the neutral, so any volt drop in the neutral was being reflected back onto the frame!

    • @johnburns4017
      @johnburns4017 4 роки тому

      So are you saying there should be overcurrent protection on ovens, which John says there is no need for?

    • @TheEulerID
      @TheEulerID 4 роки тому +2

      One of those infamous NEMA 10 connectors with the chassis connected to neutral. What could possibly go wrong? At least it's only 120V to ground...

    • @TheChipmunk2008
      @TheChipmunk2008 4 роки тому +1

      @@johnburns4017 in the UK absolutely not. In the USA at the current time absolutely not. It was an anecdote vaguely related to the topic.

    • @TheChipmunk2008
      @TheChipmunk2008 4 роки тому

      If your element goes that thermonuclear these days in either country something is going to trip before it gets to that point

    • @TheChipmunk2008
      @TheChipmunk2008 4 роки тому

      @@TheEulerID indeed the very concept horrified me when I first made the move to the US

  • @jazbell7
    @jazbell7 4 роки тому +7

    Interesting, in the USA we call those combined units "electric ranges" or "electric stoves". Typically supplied with 240v @40A over 8 gauge (approx 8 square mm) wire.

    • @kpanic23
      @kpanic23 4 роки тому +5

      Here in Germany you're not allowed to pull more than 20A from a single phase (Schieflastverordnung, "asymmetric load act").
      So our Cookers or hobs are usually supplied by 3x16A three-phase in Y configuration, so 3x230V. Cable is 5x2.5mm². We don't have isolator switches, just a cooker outlet (Herdanschlussdose) with screw terminals, from which a flex cable runs to the cooker. To isolate the appliance, you just flip the breakers. If you have an oven separately from the hob, it usually gets its own 16A breaker.
      Single phase installations get more and more rare, three-phase has pretty much been standard for the last 50 years. Even the smallest flats and apartments usually have three phase power. You can usually bridge the cooker's input to supply it with a single phase, but you're then limited to 20A. Although they're still some really old installations, where the cooker has a 25A or even 35A D-System fuse (slow-blow).

    • @millomweb
      @millomweb 4 роки тому +8

      "Stove" is used in England for said item but is an old-fashioned term for such things - and tended to be more used with gas - hence 'gas stove'. The enamelled finish on such appliances being commonly referred to as 'stove enamel'. Here, a 'range' is a similar thing but on a significantly larger scale - 3,4 or more ovens and plenty of places for heating pans or boiling water. These were developed around a solid fuel fire (wood burning, coal or coke) and were likely known in America in its 'early' modern days - and not surprisingly, the name is still used for the smaller 4-burner 'cookers' that are common in England.
      One thing to bear in mind, if you compare photos of equivalent cooking devices between US & England, ours are always much more compact due to our more compact style of 'average' homes. While a US 4 hot plate cooker may well have space for pans between the hot plates, you will not find this on typical appliances in England - where in fact lage pans placed on adjacent hot plates may well have to be touching each other to centre them on the hot plates !

    • @Zenmelin
      @Zenmelin 4 роки тому

      @@millomweb Similarly in Wales and probably Scotland and Northern Ireland too! 😉

    • @millomweb
      @millomweb 4 роки тому +1

      @@Zenmelin I'm now using 'England' instead of Disunited Kingdom.

    • @tonyjones9442
      @tonyjones9442 4 роки тому +2

      @@Zenmelin In North wales the word for cooker is 'Popty'.

  • @chrisswift1834
    @chrisswift1834 3 роки тому

    It's also been ingrained in my head to use 1.5mm T&E lighting cable....1.0mm is fine with all the LED lamps now available.

  • @mikeZL3XD7029
    @mikeZL3XD7029 4 роки тому

    Bugger!!,
    That is very sage advice John, I've been un-necessarily installing 6mm² cable to free-standing ovens over here in New Zealand, on a 32A breaker.
    Oddly enough, we have a 4 pin socket-outlet here, that I've never seen used anywhere else in the world, it may be possible it is used in Australia.
    Thanks for the great video.

  • @gibbodive140
    @gibbodive140 3 роки тому +6

    I have the utmost respect for you and have watched many of your presentations. They are clear, concise and informative, far more so than most training courses I have attended. However on this one I (and some others by the reading below) would like a little further clarification :-
    Agreed regarding mutating ovens/appliances. However if the wiring were rated at less than 32 A within the the appliance, would it be adequately protected by a 32A overcurrent protective device ?
    If there were a short circuit within that wiring, would it be adequately protected by such a device ?
    Non compliance in any respect from manufacturers requirements/specifications sounds rather foolish to me, potentially resulting in a tricky situation if there were a significant incident ?
    Why expose oneself by non compliance with all relevant standards, however small.
    I am not being critical, but would appreciate a greater understanding.
    Thank you

    • @jamesdevlin3892
      @jamesdevlin3892 2 роки тому

      I'd be interested too. Some manufacturers specify a 16A breaker. On a recent job I has two 3kW ovens that specified a 16A breaker. I ended up putting them on a 32A breaker, to a cooker isolator, to two 13A fused connection units to try to comply. Easier to whack them both in a cooker plate. If there was an accident like a fire that started on the cooker circuit, I wonder what the verdict would be.

  • @ap06smart
    @ap06smart 4 роки тому

    Thank you John for the comfirmation on Cooker Circuits, just what I thought.

  • @kevvywevvywoo
    @kevvywevvywoo 4 роки тому

    Around here in the old MEB region we were taught 45A rewireable and 6mm. Most houses built before the 1990's in this area were done this way

    • @jwflame
      @jwflame  4 роки тому +1

      45A rewirable fuse with 6mm² cable doesn't comply, and never did. It's the same problem as 4mm and 30A rewireable - not permitted due to the 0.725 correction factor for rewirable fuses.
      45A with a cartridge fuse or circuit breaker could comply, depending on cable installation method.

    • @kevvywevvywoo
      @kevvywevvywoo 4 роки тому

      @@jwflame probably 7/044 TRS as I'm talking the early 1950's

  • @charletonzimmerman4205
    @charletonzimmerman4205 4 роки тому

    In USA we gage wire by CM, circular mills, & under 100 amps. terminal & wire Insulation is , set @ 60 C degrees .

  • @LakeNipissing
    @LakeNipissing 4 роки тому

    Here in Canada for most cookers with four element stove top and broil/bake oven, the circuit would be 240 V, 40 A with cable size 8/3 which works out to just 3.25 mm... Looks like the British Standard is strict for heavier cable, at 4mm with only 32 A.
    Electric clothes dryer circuits here are 240 V, 30 A with 10/3 (2.59 mm) cable.

    • @jwflame
      @jwflame  4 роки тому

      Uk cables are sized on cross sectional area, not diameter.
      8AWG is equivalent to about 8mm2
      4mm2 as in the video is approximately 11AWG.

    • @LakeNipissing
      @LakeNipissing 4 роки тому

      @@jwflame Thanks for the reply!! As if it is not confusing we use AWG, they also use diameter in mm , instead of mm2.
      Keep up the great, great work, JW !

  • @orestismiaris4928
    @orestismiaris4928 Рік тому

    In Cyprus we follow the british regulations but we put everything in conduits buried inside the walls and fllors. Seeing the installation methods table on the on-site guide, I guess that would correspond with installation method A, which demands a 6mm2 cable for this job.

  • @winstoningram7713
    @winstoningram7713 4 роки тому +1

    Awesome video as always great teaching methods very easy to listen to , Thanks JW 👍

  • @xxwookey
    @xxwookey 2 роки тому

    So all those installs with 6mm2 fitted with method C can just put a 40A MCB on. Which isn't all that useful but does allow for a very fat induction hob+oven setup to be installed. That does mean that you can turn on absolutely everything with no danger of tripping the breaker (in theory this could happen with hob+oven on ful blast, although clearly in practice this just about never happens otherwise there would be a lot more grumbling about 32A MCBs.
    It will also save something like 1.2kWh/yr in reduced losses for a 10m cable run (assuming half an hour a day of cooking at 5kW on average), where upgrading from 4mm2 to 6mm2 causes losses to go down from ~21W to ~14W. So that would take a while to pay for the extra copper.
    This calculation is more significant for EV chargers which typically run at 7kW continuous for an hours a day on average, and can often be a quite a long run. In my case (25m run) the difference in cost between 10mm2 and 6mm2 is paid for in improved efficiency after 6 years. That's a sensible option IMHO.

  • @michaeltb1358
    @michaeltb1358 3 роки тому +1

    Cooker switches used to include a 15/13 amp socket which would have increased possible load dramatically.

  • @AntonyoKnight
    @AntonyoKnight 3 роки тому

    16:30 Can you please help me? I have been searching in the 18the Ed and On-Site about the flexible cable but all I can find is the " 521.9 (Selection and Erection of Wiring Systems) Equipment that is intended to be moved in use shall be connected by flexible cables." And of cource in Definitions but that's a bit useless.
    Should I use Table 4E2A 3 core 4mm2?
    Thanks

  • @hpt08
    @hpt08 3 роки тому +1

    If you're looking for the JW dry humour max moment, it's at 16:00 mins in and refers to your propensity to clean over 20 years 😆😅😆

  • @supersparks9466
    @supersparks9466 4 роки тому +4

    Nice vid JW , one issue is 4mm can cost as much and sometimes more than 6mm given it’s unpopular size.

  • @Ralphs-House
    @Ralphs-House 4 роки тому +1

    Thank you John. Wonderfully informative. As always.

  • @adamdavis2274
    @adamdavis2274 2 роки тому

    When choosing the flex cable for the appliance from a outlet plate for a hob or built in oven would you use the same diversity , the first 10amp then 30% of remaining load .

  • @andrewforsyth4799
    @andrewforsyth4799 5 місяців тому

    Hi j, really like your channel its very informative, just come across this older vidio of yours which i do remember, could you explain how the newer iet brown book now reference's this same model regarding the 3036 fuse . They've changed the book because of your teaching ,,brill!!

  • @ginandtreats8556
    @ginandtreats8556 Рік тому

    Thank you for a very informative explanation.

  • @Wilkkid1
    @Wilkkid1 4 роки тому +1

    Great video as always John 👌

  • @justifiedfreelybyhisgrace1779
    @justifiedfreelybyhisgrace1779 2 роки тому

    My inlaws are getting a new large range style cooker thats induction and is about 15.5 kw potentially.
    I believe this is on a 6mm cable and a 32a mcb (although) im yet to check so this video has eased my fears for them somewhat

  • @speeka9850
    @speeka9850 3 роки тому

    Heating up water & what not, its called cooking JW.😄😄😄

  • @darrenbanton8929
    @darrenbanton8929 Рік тому

    Respect John👊🏾 thank you very much

  • @crashk6
    @crashk6 4 роки тому

    John, If you think 6mm2 is bad. Once you import that same freestanding cooker to North America and get the appropriate shinny CSA-us or, cULus stickers slapped on, then you have to install either 8.36mm2 (8awg) or 13.30mm2 (6awg) to serve that same cooker at the same 240v. I take very little issues with 6mm2 serving the cooker by comparison to the equivalent madness in the North American methodology.

  • @markluke7528
    @markluke7528 3 роки тому +1

    Hi John please explain 2x 4 ring induction hobs side by side and 2x ovens side by side as I have big family want to install in my new kitchen

  • @malcolmkenward2663
    @malcolmkenward2663 4 місяці тому

    Excellent video thank you. I have an historic 6mm connection to a double oven (mcb’s now) and a gas hob. The oven is being replaced by a single 15kW and the hob by a 7.5 kW induction. They will be on opposite sides of the kitchen, about 3 metres apart. Your video suggests to me that I could fit a junction box to the 6mm cable (access is easy) and then add an extra 4mm outlet (spur) for the hob, both going to required connections and switches, instead of installing a whole new radial circuit.
    Both cables will run in the void under the floorboards in a Xictorian house.
    Would this comply with the regs?

    • @malcolmkenward2663
      @malcolmkenward2663 4 місяці тому

      Can’t edit. 3kW oven!

    • @jwflame
      @jwflame  4 місяці тому +1

      Yes, doesn't matter whether they are in different locations or not.

  • @mwbg
    @mwbg Рік тому

    Thank you. You've answered everything.

  • @anthonyloftus1236
    @anthonyloftus1236 2 роки тому

    Brilliant. I know the theory of electricity but am no electrician. Built in oven is kaput, wife would like the gas hob replaced as well. Does this mean ripping up the kitchen to provide all the extra power? This video answered all my questions. Nice wee bit of humour too.

  • @MrPantss
    @MrPantss 4 роки тому

    Love the Hammond in the background..... 👍🙂

  • @GeorgeHenderson-iv5vs
    @GeorgeHenderson-iv5vs 11 місяців тому

    John is diversity applied to Induction Hobs,

    • @jwflame
      @jwflame  11 місяців тому +1

      Yes. Like any other, they won't all be on 100% power 100% of the time.

    • @GeorgeHenderson-iv5vs
      @GeorgeHenderson-iv5vs 11 місяців тому

      Thanks John

  • @robsparks1993
    @robsparks1993 4 роки тому +2

    Great work JW!!

  • @jdickson242
    @jdickson242 3 роки тому

    I feel i should donate you some beer port or wine for Christmas. I have learnt so much from you for free. I would happily donate to the J Ward Christmas beverage fund

  • @damonbtc9701
    @damonbtc9701 4 роки тому

    Almost totally agree although how many times do we see a wee single oven melting the plugtop its hanging off personally alway bring fcu out the elephants nose...
    Again great content JW,keep it up

  • @justcruisin109
    @justcruisin109 4 роки тому

    I thought an advantage of having the old 6mm2 cable (back from when it used wire fuse) was that you could have a higher powered modern cooktop (like 11kW induction) without having to rewire. This is a theory I’m about to test so I’ll find out one way or the other (located in Australia). Thanks for an informative video. Cheers

  • @tonylynessable
    @tonylynessable 2 місяці тому

    Hi John. Great content as always.
    Can this rule of diversity be applied if trying to figure how many amps a house would generally draw?
    Taking into account all appliances etc etc..

  • @gapster77
    @gapster77 4 роки тому +1

    I have a question regarding 4mm radials in T&E;
    In a Warehouse I was going to pull a 20A Radial in 4mm T&E, through Metal Trunking & then dropping down a wall in Plastic conduit, the load being a Twin Socket outlet. I did this in 4mm as I was sure a 2nd or 3rd outlet would be requested by the client at a later date. The total length of the Radial was currently 15m, out of interest I checked the onsite guide to see how far this circuit could be extended if I wanted to add another socket at a later date. I could not find an answer, it lists 2.5mm and 6mm ran in such a way for Radial and Ring circuits but 4mm isn’t covered?
    It puzzled me, and I started to consider the size of the CPC in comparison to the Live conductor, in 4mm the CPC is 1.5mm, which is relatively small in comparison (incidentally I believe this is the same size ratio for 16mm cable?). Is this why this cable size isn’t considered in the tables?
    What are your thoughts on this cable selection, and how far could it be ran as a 20A radial for socket outlets? (PME supply)
    Whenever I’m party to a conversation about domestic installations, with Radials Vs Rings being used I consider the 4mm T&E with its 1.5mm CPC and think maybe they should have a 2nd Variant of 4mm with a 2.5mm CPC specifically for Domestic Radials? ...I’m very likely overthinking this though :)

    • @jwflame
      @jwflame  4 роки тому

      20A 4mm radial is on page 70, maximum length with terminal load is 69m. More if the load is distributed.

    • @gapster77
      @gapster77 4 роки тому

      John Ward Thanks! I did call the NIC, and they couldn’t help me?

  • @millomweb
    @millomweb 4 роки тому

    On our 1ph cooker circuit, we have:
    Cooker
    4 13A sockets, one of which feeds a kettle
    Commercial dishwasher with a 20A option (not used), and, last but not least, the
    GARAGE including a few fluorescent lamps, electric welder AND 3ph lathe and 3ph milling machine.
    30A fuse.
    And guess what ! Yeah, we don't use everything at the same time !

  • @neilanderson394
    @neilanderson394 4 роки тому +1

    The problem is when you carry out a EICR , you have no idea how the cable has been ran in , I’ve always aired on the side of caution, reference method C mentions capping but I’ve seen conduits being used as mechanical protection. Plus you would have to gauge the required depth. If I seen 4mm on a 32Amp MCB I would pick that up unless I was totally sure of the reference methods used. If you’ve installed it then great no problems.

  • @Adywebb123
    @Adywebb123 4 роки тому +1

    Brilliant video as always well explained.
    I have recently been asked to work out an electrical load for a new build property. Not something I normally do .
    It’s has 3 floors 3 separate flats, each flat consists of a cooker circuit, 10 kw shower, 2 small rings mains and single lighting circuit.
    It’s has a three phase supply coming in, how do I work out each flat and total for all flats. Hope you can help. Thanks

    • @jwflame
      @jwflame  4 роки тому +2

      Covered in this older video: ua-cam.com/video/Wq0uODypaGI/v-deo.html and also see Appendix A in the on site guide.