Sir ye batao neutral & phes joint hone se rccb trip kyu nah ihoti hai to rccb lagane se wiring ki kya sefty sirf urthing aur phes se hi joint hone se hi kyu hoti hai kya Folt aur current urthing aur phes se hi hota hai please reply
jamshed shab nutrul our pase brne se short breker trip ho gi jinab earthing hone par arth examal agr ap ki koi fan ki wending short ho to earth breker trip ho g i
RCCB only works if both the lines are taken from its output. If not the RCCB trips itself. It is a way of indicating that the connections are not done properly.
Achha video tha, lekin RCCB ke standards ke hisaab se 15 mA pe bhi trip hona allowed hai. Alag alag current level pe alag alag time limit hota hai milliseconds mein. 100 mA me ~30 milliseconds allowed hoga, 15 mA pe 500 msec. 15 mA se kam pe trip nahin hona chahiye as per standards.
RCCB kee jaanch ke lie yeh karen: In coming connect karne ke baadh out going ke "Line" se aek dhoosraa wire connect karne ke baadh is ke dhoosre sare ko geelee zameen ko ch'hooyen tho RCCB trip hojanaa chaahie, yeh behadh surakshith aur b'harosamand thareeqa he.
i've watched your video very caefully red and blue wires are connected to source input and the 2 black wires to load the RCD function to load and does not trip and when you bypass the load it trips something that is puzzling me where it should trip it doesn't and where nothing is connected it trips
Bhai sahb is bulb men pcb card hota hy jis pe bht sary electronics components lgy hoty hn jis ki wja se start men zyada current ki jerk jati hy jo definitely 100mA se zyda hoti hy is liay breaker trip hota hy. Agr ap bulb ki jga koi variable resistance lga k current ko 100mA se km pass krwaen to ye ni hoga trip
Sir, i have a modification in RCCB. If we will done this modification in rccb then rccb work in main line with inverter single wire. If main line shut down then work rccb with inverter current.
I have the same make 4 pole rccb and installed it. How to be sure that it will trip in case of accident. I connected a wire from phase of my 3 pin socket and touched it with wall. Rccb did not trip. Why
Rccb aur elcb alag hota hai sir. Elcb mein earthing wire k extra terminal hote hai and elcb uska current sence karta hai. Rccb live and neutral k difference current ko sense karta hai.
Sir MERA pass 10kva ka gernitor Hai kya me gernetor ki safe ki liye gen set ki out put me kitna ampire ka mcb lagna hai our kun se mcb lagana hai plz reply
Sir 2kv aur 3 kv kay load pay rccb kitnay amp ka hona chahiye Agar 3kv kay hisab shay rccb lgaya jaye toh ghar par kisi member ko current lga toh kya rccb trip hogi kya btaye pls chahiye jyada shay jyada amp ka rccb ghar par install hay Toh rccb trip hogi agar ghar mein kisi member ko current ata hay jayshay fridge mein kabhi kabhi current lagtha hay toh kya rccb trip hogi btaye pls
bhai 100mA ka mtlb h if koi particular load agr 2 amp le rha h and continueous 2 amp ja rahe h rccb se and kisi ke touch krne se wo 2000 mili amp agr 2100 milli amp jane lg gye to wo trip hogi. ye experiment to useless tha bhai meko to smjh hi ni aya iska motive 😅 rccb sirf trip krke dikha rahe ho app isse kya proof hua ?
Sir aik 100 ml amp ka rccb 2 pol ka hai but o trip kr ja rha hai bar bar, aior jb rccb ko jb Bay pas karke mcb ko on karte hai to bilkul sahi chal rha hai, please btaiye n kya karu SIR
Sir Bohot Hi Achhi Information Di, Aur RCCB Ko Energy Meter Ke Baad Ghar Me Lgane Ka Sahi Sequienc Aur Kitne Load Ki Lagegi ispar Bhi Detail Video Banaye
Dosto ye video aap ko kesa laga jarur bataie !!
4 pole ka rccb me to sabi phase alag amp leti hai..to trip kiu nehi hoti???aap galat bata rahi hai....
Firoj9352426925
Sir ye batao neutral & phes joint hone se rccb trip kyu nah ihoti hai to rccb lagane se wiring ki kya sefty sirf urthing aur phes se hi joint hone se hi kyu hoti hai kya Folt aur current urthing aur phes se hi hota hai please reply
jamshed shab nutrul our pase brne se short breker trip ho gi jinab earthing hone par arth examal agr ap ki koi fan ki wending short ho to earth breker trip ho g i
Nice
RCCB only works if both the lines are taken from its output. If not the RCCB trips itself. It is a way of indicating that the connections are not done properly.
Added load of meter too
Kabhi bhi nutal by pass nahi hota hai bhai. Erth likege se hota hai trip
Brother RCCB and ELCB both have different working principles just like key ped phone and Android phone...
Yes, but now days only current based available
बहुत अच्छा वीडियो
Bhai aap mcb dubal pool ke Rccb ka praise ky h 32 ampeyr frij me kitne ampr ka hona Chai ye
Wonderful. Great information! Soon I will post a video on this item.
Good information,keep it up
Thanks
आरसीसीबी को फसल वाली झटका मशीन की तरह प्रयोग कर सकते हैं क्या
*बल्ब को ON कंडीशन में रख कर दूसरे वायर से ऊपर नीचे के दोनों पॉइंट शॉर्ट करो।*
*क्यों कि कोई भी इलेक्ट्रॉनिक डिवाइस स्टार्टिंग करंट ज्यादा लेती है।*
Achha video tha, lekin RCCB ke standards ke hisaab se 15 mA pe bhi trip hona allowed hai. Alag alag current level pe alag alag time limit hota hai milliseconds mein. 100 mA me ~30 milliseconds allowed hoga, 15 mA pe 500 msec. 15 mA se kam pe trip nahin hona chahiye as per standards.
Aap ek aur low power bulb (around 1 W) se try kijiye same experiment.
Very good teaching welldown
Thank you
RCCB kee jaanch ke lie yeh karen:
In coming connect karne ke baadh out going ke "Line" se aek dhoosraa wire connect karne ke baadh is ke dhoosre sare ko geelee zameen ko ch'hooyen tho RCCB trip hojanaa chaahie, yeh behadh surakshith aur b'harosamand thareeqa he.
rccb stand for?
Sir,,,jmd brand ka rccb ghar ke liye a66a rahega??????please sir reply
i've watched your video very caefully red and blue wires are connected to source input and the 2 black wires to load
the RCD function to load and does not trip and when you bypass the load it trips something that is puzzling me where it should trip it doesn't and where nothing is connected it trips
Bhai sahb is bulb men pcb card hota hy jis pe bht sary electronics components lgy hoty hn jis ki wja se start men zyada current ki jerk jati hy jo definitely 100mA se zyda hoti hy is liay breaker trip hota hy. Agr ap bulb ki jga koi variable resistance lga k current ko 100mA se km pass krwaen to ye ni hoga trip
Rccb actual work leakage current me karta hai, apka experiment sahi nahi hai
Sure
Clear concept gained. Thanks
Sir, i have a modification in RCCB. If we will done this modification in rccb then rccb work in main line with inverter single wire. If main line shut down then work rccb with inverter current.
Agar ghr mai inverter laga ho to, kya main mcb kaam nhi krta hai kya?
Bro what is the name of this digital meter
And purchase link
Agr ghr pr inverter h to RCCB ko kha connect krna h plz btaye
Please make video on change over MCB.
Rcn ko input niche ya upar se hoga hai...
Good job bro. Next video ka lntzar karunga
Use electrical hand gloves also
I have the same make 4 pole rccb and installed it. How to be sure that it will trip in case of accident. I connected a wire from phase of my 3 pin socket and touched it with wall. Rccb did not trip. Why
RCCB not trip because there is no enough amount of current leaks through dry wall
What about 3 phase 4 pole
What is the display meter used. Would u let me know. Waiting for reply.
This is a Power monitor. link in description for more information.
@@LetsSeeInside thank you bro
Kya yeh powar monitor
votege power aur amr batata hai sir
What is the difference between 100 and 300 mA
Sir Bohot achi bata ye hai MCB avr RccB ka kitna ka fark hai
Bhai, ye red colour me Flipkart ki JMD rccb order kri hai, iske button dusri side h.. kya bta sakte ho orginal h ya nhi
Rccb aur elcb alag hota hai sir.
Elcb mein earthing wire k extra terminal hote hai and elcb uska current sence karta hai.
Rccb live and neutral k difference current ko sense karta hai.
Bhai kon company ka rccb best hota hai aur kiya hum 63amp aur 30milliamp ka rccb use kar sakte hai bhai reply de please bhai reply me
Nice video
Apna mitar hata kar test karo bhai
Rccb line me connect karne bad MCB ki jarurat he?
Ha bilkul, mcb or rccb alag alag h.
A company ki rccb achhi ati Hain?
RCCB kis company ka sabse best aata hai
RCCB और ELCB दोनो एक जैसे नहीं होते !
Bhai sabdhani se kaam karma next part me,(lagta h shock khayenge aap)
Aur bataiye yeh RCCB ki offline market price kitna hai?
2000
Market me kitna kitna Amp ka RCCB milta hai? Or price kitna se start hota hai?
Arre bhai sahab RCCB Shock se bachne ke liye hota hai.
घर में कितने Amp की आरसीसीबी लगाए , सिंगल फेज पावर में ?
30mA rccb best hai ghar k liye
Right because 30mA se jada current human body ke liye dangerous hota hai
Sir rccb ghar me two lagani padege one inverter one for main???
Bhai kya jeebh lagaa kar test Karna tha kya..........
क्या प्राराइस है....☺
Nice sir
will harmonic current affect rccb function since some harmonics produce zero sequence current ...
Definitely Harmonic affect in RCCB working but some company make special RCCB for that kind of application
मजा नही आया
जब phase बॉडी को touch होता हैं तो ट्रिप होता हैं या नही ये दिखाना चाहिये था
ताकी हम इसे खरीदी कर सके
Is video me sahi btaya gya hai kyo aap test button ki madad se be check kr skte hai
Sir Agar ghar may 3 led tube light 3 9volt led bulb 1 iron led tv aur refrigerator iske lia kitne ampier ka RCCB lena hoga
16 amp ka mcb me gharka kitna load or kya kya chala sakte hai
Ye digital meter kon sa he
Ye meter mujhe Lana he
Vii 25A mcb ka sat kitna amp ka rccb lagana ha
House warning main ketna amper ke elcb hona chiya?
Search protection device main ek video banai
आपके पास जो मीटर हैं उसका नांम ?
Price?
thanks bro
Hello dear, your rccb is totally defective as per leakage current ratting.
Rccb Kitna ka liye ho bhai market se
Sir kya ye double phase agricultural monoblock pump pe work karega kya?
Yes you should use three phase version of this.
Appne jo mitar use Kiya hai uska Keya name h
Sir series canicsan kysa huta hai
Kya rccb ka electric water rod me use KR sakti h Kya , protection k leya
Bilkul or karna bhi chahiye
Good video 👍👍
Rccb trep kregee 75 mm wayar sot hone se bhi trep ho jate h
sir i have one doubt short circuit and over load time rccb will trip or not?
Sure. It is a circuit breaker with extra feature.
@@engineerkohat ... I differ u. Not all RCCBs have Overload tripping.
इस प्रक्टिकल के लिये elcb teste लेना चाहिए उस पर मिली एम्पियर मैं रेटिंग होती हैं
Sir which resistence its inside sir?
Sir MERA pass 10kva ka gernitor Hai kya me gernetor ki safe ki liye gen set ki out put me kitna ampire ka mcb lagna hai our kun se mcb lagana hai plz reply
Shoket ke upar Jo lagaye hai usake name
Rccb ko inverter output me kaise connect kare usme sirf line out hota hai neutral to hotta nahi?
RCCB ko agr solar k bd inertor sa jo out nikalti h us ma lgay r neutral na lien to ya kam kray ga ya ni ,,,,
100ma matlaba kya he sir , kucha pata he kya
100mA means = 0.1A
Basically ish sensitive rating ki RCCB commercial or offices me use karte hai
Video to Jhakass hai
ek bat samajh me nahi aa rahi hai RCCB se MCB me कनेक्शन diya to erth lagne par pahle MCB trip karega ya RCCB
Rccb karega because current differences two phase or neutral me aya he wo sif 100ma he while Mcb to short circuit me treap hogi
@@hiteshvariya9827 thank you so much
Thank You sir 💐❤️
Sir 2kv aur 3 kv kay load pay rccb kitnay amp ka hona chahiye
Agar 3kv kay hisab shay rccb lgaya jaye toh ghar par kisi member ko current lga toh kya rccb trip hogi kya btaye pls
chahiye jyada shay jyada amp ka rccb ghar par install hay
Toh rccb trip hogi agar ghar mein kisi member ko current ata hay jayshay fridge mein kabhi kabhi current lagtha hay toh kya rccb trip hogi btaye pls
Bhai yah sab experiment Mila hai UA-cam channel per
Hello sir this one using the battery charging process reverse polarity
Dost e jo rccb ke baad board lagaya hai or uske baad jo device lagaya hai oo keya hai
Nice
What's is different RCCB & RCBO.
How to check practical Trip function
RCCB only for Leakage current protection
But RCBO gives Overload, Shortcircuit and Leakage current protection
Nice,
This is a RCD (residual current device) not RCCB (residual-current circuit breaker )
Sir matlab
Thanks
bhai 100mA ka mtlb h if koi particular load agr 2 amp le rha h and continueous 2 amp ja rahe h rccb se and kisi ke touch krne se wo 2000 mili amp agr 2100 milli amp jane lg gye to wo trip hogi. ye experiment to useless tha bhai meko to smjh hi ni aya iska motive 😅 rccb sirf trip krke dikha rahe ho app isse kya proof hua ?
Rccb through a/c chala skate hain
Sir kithna k ohm ka resistene iska ander he?
Wo meter kaunsa hai
Nice guidance ELCB
घर के कितने RCCV कितने एम्पीयर कि लगवायें
Please change your bypass connection test onese phase bypass please
Sir aik 100 ml amp ka rccb 2 pol ka hai but o trip kr ja rha hai bar bar, aior jb rccb ko jb Bay pas karke mcb ko on karte hai to bilkul sahi chal rha hai, please btaiye n kya karu SIR
Rccb input output বুঝবো কি রকম বলো দাদা
Sar inwarter ki wyring kisye kary Rccb me csnfuz hu
Sar mera rccb jmd kampani Ka hai 40 mp hai par tip nahi karte par tipar kam karte hai
Sir Bohot Hi Achhi Information Di,
Aur RCCB Ko Energy Meter Ke Baad Ghar Me Lgane Ka Sahi Sequienc Aur Kitne Load Ki Lagegi ispar Bhi Detail Video Banaye
👌boss