How to Read 4-20mA from PT100 Sensor to Current Converter with a DVP PLC on ISPSoft, DOPSoft-4

Поділитися
Вставка
  • Опубліковано 8 січ 2024
  • DELTA DVP PLC Analog Read 4-20mA and
    Display Pt00 Sensor Temperature from 4-20 mA ISPSoft
    -----------------------
    4-20mA Analog input Calibration
    -------------------------------
    All are Proportional Data
    Step1= 4-20, 0-100c
    Step2= 0-100 = 4-20mA
    0C = 4mA
    100 = 20mA
    Step3= Current Span 20-4 = 16mA
    Step4= 20mA = Digital RAW data = 1000max
    Step5= 20 ma = 1000max
    1 ma = 1000/20
    4 ma = 1000x4/20 = 200
    1000-200 = 800
    200 = 0C = 4mA
    1000 = 100C = 20mA
    Step6= Digital RAW Data Span = 1000-200 = 800
    Tempera per Digital RAW Val = 100/800 = 0.13, unit temperature
    Digital RAW Val per Temperature = 800/100 = 8, Digital Unit
    Step7= Calculation1 =Actual Temperature= Digital RAW input or Source Val x 0.13
    Calculation2 = Actual Temperature = Digital RAW input or Source Val/8

КОМЕНТАРІ • 5

  • @AmiciFelipe
    @AmiciFelipe Місяць тому

    Very good class, it's a shame I couldn't get your translation, I hope you can do a PID control class with dvp06xa soon, but I have a question, is it possible to make the settings directly in the option above, third icon, on the right, going to auxiliary configuration of the module extension and doing all the configuration there of what you want current or voltage? Thanks