Communication with Micromaster 4 and PLC via Profibus-DP

Поділитися
Вставка
  • Опубліковано 7 лют 2025
  • On the Micromaster Drive change Parameter: before you change it set P0003 = 3 and P0010 = 1 this will allow you to change anything on the parameters. After changing don't forget to put back P0010 = 0 otherwise your drive will not run.
    Allow full Profibus Control
    P0700 = 6
    P1000 (IN0) = 1
    P0918 = Profibus Address
    Control word 1 (bits 0-10 as per PROFIdrive Profile, bits 11-15 specific to
    MICROMASTER 4)
    Control Word 2 will be the reference speed value.
    Hex Values:
    47F = Start Forward
    C7F = Start Reverse
    47E = Stop

КОМЕНТАРІ • 10

  • @kgauravb
    @kgauravb 4 роки тому +2

    This is the exact video I was looking for. Thanks for the help.

    • @charliecabreros8158
      @charliecabreros8158  4 роки тому +2

      don't forget to subscribe :) and watch other useful tutorials

  • @IqramAli-be9ui
    @IqramAli-be9ui Місяць тому

    Nice

  • @SuperMoha86
    @SuperMoha86 4 роки тому

    Great automation tutorial, keep it up

  • @pzebzda
    @pzebzda 2 роки тому

    Good video

  • @satendrachaturvedi5739
    @satendrachaturvedi5739 3 роки тому

    Great sir

  • @CNC_MRC
    @CNC_MRC 2 роки тому

    Testowałem działa i u mnie

  • @rishinathreghu579
    @rishinathreghu579 Рік тому

    hi, how did the control word 2 for frequency setpoint got the initial("4744") value when u start.

  • @mehmetkayali5183
    @mehmetkayali5183 4 роки тому

    Dear Charlie;
    Thanks for the nice example.
    I want to ask you for help on something. How can I read the driver active alarm in MM 420 series with profibus.

  • @dhurgis9522
    @dhurgis9522 3 роки тому

    suprb