Communication with Micromaster 4 and PLC via Profibus-DP
Вставка
- Опубліковано 7 лют 2025
- On the Micromaster Drive change Parameter: before you change it set P0003 = 3 and P0010 = 1 this will allow you to change anything on the parameters. After changing don't forget to put back P0010 = 0 otherwise your drive will not run.
Allow full Profibus Control
P0700 = 6
P1000 (IN0) = 1
P0918 = Profibus Address
Control word 1 (bits 0-10 as per PROFIdrive Profile, bits 11-15 specific to
MICROMASTER 4)
Control Word 2 will be the reference speed value.
Hex Values:
47F = Start Forward
C7F = Start Reverse
47E = Stop
This is the exact video I was looking for. Thanks for the help.
don't forget to subscribe :) and watch other useful tutorials
Nice
Great automation tutorial, keep it up
Good video
Great sir
Testowałem działa i u mnie
hi, how did the control word 2 for frequency setpoint got the initial("4744") value when u start.
Dear Charlie;
Thanks for the nice example.
I want to ask you for help on something. How can I read the driver active alarm in MM 420 series with profibus.