I can get my setup (using the same OPC UA Client as the video) all the way to about 4:40 in the video. In the OPC UA Client I can connect to the server and I see the M241-M251 Data folder but when open the folder the tags are not there, the folder is empty. Any suggestions?
Hi I faced the same problem. Everything was solved after I found I forgot to add the POU (PRG) to Task configuration so nothing was running inside PLC...
For those who have problems with licensing; from V4.3 Patch 2 onwards a license for the OPC UA server is no longer required.