GUIDED WAVE RADAR (CONTACT TYPE) - DESIGN CONSIDERATIONS
Вставка
- Опубліковано 10 лют 2025
- Dear Friends
This video features on Guide Wave Radar ( Contact Type) design considerations, installation and design requirement for chamber, stilling well, verification pin, reflector kit and applications.
Thanks
Ram Bala
very good Bala sahab
Thank you for watching
Really Great effort... Giving clearn understanding of Practial aspects instead of reading LIPTAK books@@B-SPICE
Thanks for the support @@sundaramnarayanan1375
Thank you
Thank you for the support
thank sir
thank you for watching and support
IN 6.25,,,,, WHAT IS THE PURPOSE OF LIGHT GOING BEYOND LIQUID SURFACE TILL BOTTOM OF PROBE? ONCE the light wave is returned after touching the level back to sensor... then why wave should travel till bottom and retunr back.... Purpose and use.. Please
Thanks again for writing and support.. As you aware, when radar pulses reaches the media with different di-electric, part of energy is reflected to transmitter by which the level is calculated. What i meant the statement "remaining passes down" means due to different di-electric or less dielectric the reflection will be poor and no use . that's why we need to focus on the di-electric material of the process while choosing radar probe..thanks again for the support.. keep watching..
understand the dielectric constant . once the reflected after touching surface of material, level is calculated, But remaining passed down, will reflect back from the bottom vessel bottom, will create another peak as zero level.... Am i correct?
My question is,, remaining passes down, will not create false level Echos...?? @@B-SPICE
Echo will not occur if the tank is dish or cone bottom where the slope is more than 20 deg and other tanks we use reflector kit to avoid echoes.. thanks again ..@@sundaramnarayanan1375