Bosch Singular Tankless Condensing Combi No Domestic Hot Water

Поділитися
Вставка
  • Опубліковано 10 лют 2025

КОМЕНТАРІ • 75

  • @Jimbobo162
    @Jimbobo162 Рік тому +9

    Praying for all the plumbers and HVAC workers, the middle of the country will have subzero temperatures down through Texas next week. It’s going to be busy and stressful.

  • @MobtubeClips
    @MobtubeClips Рік тому

    I deleted that. I’m no better. Thanks Mike for all the good work you do and people you help.

  • @SuperComfee
    @SuperComfee Рік тому +4

    looks like the exhaust is getting sucked into the intake,
    that would definitely cause issues as the gases will condense and the low ph may cause things to corrode faster

    • @SuperComfee
      @SuperComfee Рік тому +1

      perhaps the reason this boiler is in such shitty condition already is because of the recirc

    • @iLikeC00kieDough
      @iLikeC00kieDough Рік тому

      @@SuperComfeeI’m surprised Mikey didn’t spend more time explaining that. It’s the first thing I thought of too; you can even see in the video the wind is pushing the exhaust right into the intake 🤦

    • @SuperComfee
      @SuperComfee Рік тому

      @@iLikeC00kieDough snorkel the exhaust up 3 ft

    • @SuperComfee
      @SuperComfee Рік тому

      @@iLikeC00kieDough too late now , boilers Joe Biden

  • @davidlampe4153
    @davidlampe4153 Рік тому +1

    Nice video well done on your analysis of the issues.
    Are you doing a part 2?
    It’s nice to have some closure on problems.

  • @DCHVAC
    @DCHVAC Рік тому +6

    Epic

  • @samuelnason8585
    @samuelnason8585 Рік тому

    oh darn, i wanted to see the end if you replaced it or not.

  • @RudiduPlessis
    @RudiduPlessis 7 місяців тому

    Thanks for the video. Found it very helpful. I recently put in a dewhot system which is total junk. Only been hearing good reports from the bosch systems.
    Out of interest is it possible to buy the blower and venturi assembly as a separate part?

  • @williampagan4489
    @williampagan4489 Рік тому

    Very Familiar I Had a Flashback and I was wondering...#LoveBosch

  • @jdawginc
    @jdawginc 4 місяці тому

    Great video. I am in Astoria NY. how does the availabilty of parts and service compare between Bosch combi and Navien?

  • @umairtariq8708
    @umairtariq8708 Рік тому

    Hello, I have this same exact tank, however my heating does not pass 73 .... Before 73 temperature I can feel my radiator emitting lots of heat but after 73 it isn't the same. I have a nest thermostat that is calling to reach 80 but it gets to 73 and that's it. The boiler keeps running and that's about it. Any helpful information on this would be very appreciated

  • @kevinfoster2308
    @kevinfoster2308 Рік тому

    Had a similar thing happen with a Rheem tankless except the condensate water was from a leaking furnace in the utility room above.

  • @MikeMcGushin
    @MikeMcGushin Рік тому +1

    Nice tour of the unit. What about cause of leak? Cost the customer big $ for service call and repair. Wouldn’t say anything bad about Bosch. 8:32

  • @swaterman08
    @swaterman08 Рік тому +2

    you would think the outer box could be some composite material or even just the bottom plate, that would not rust.

    • @mxslick50
      @mxslick50 Рік тому

      True, but flue gas condensate is highly corrosive, plain water would not cause the rust seen here so soon. Manufacturers warn not to use ANY metal pipe or fittings of any type on condensate drains, and require neutralizers on the condensate discharge.

  • @kens.3729
    @kens.3729 Рік тому +3

    Parts of U.S. Forecasted to Receive Extreme Cold 🥶 Temperatures. Don’t Forget to Open Faucets to Drip, so they Don’t Freeze causing 1000’s in Damages.

  • @zacharywhite8230
    @zacharywhite8230 Рік тому

    Looks like the same garbage heat exchanger we had on our slant fin. Same branding on the tag of the exchanger. Was all aluminum inside and could not take it apart to clean. At least this one looks like it has more serviceability.

  • @everettstevenson2111
    @everettstevenson2111 Рік тому +1

    Hey Mikey, of Mikey Pipes Plumbing not easy being cheesy. I like your podcast/social media, looking thru some comments/reply. Hmm? tankless hot water boiler, that rubber drain hose can not take all that thermal shock, i have found. Thank God you are not working for Alaskan Airline ? lol. It's murphy's law again. Love you buddy, you be safe out there.

    • @PipeDoctor
      @PipeDoctor  Рік тому +1

      I only fly Delta

    • @mxslick50
      @mxslick50 Рік тому +1

      @@PipeDoctor Alaska Air's open door policy reaches new heights, 16,000 feet to be precise.

  • @192347001
    @192347001 Рік тому +1

    I think the oem is Vesta

    • @mxslick50
      @mxslick50 Рік тому

      I currently have a Takagi, which is also branded as AO Smith here in the US. Supposedly made in Japan and rebadged. I haven't looked too much at the internals (other than initial setup dip switch settings) to see where the heat exchanger comes from.

  • @chatrkat
    @chatrkat Рік тому

    Honestly, those look nicely constructed, in spite of that leak. Didn’t help it was dripping highly corrosive water on that connector.

  • @MatthewLarsen-t6q
    @MatthewLarsen-t6q Рік тому +1

    So it's a navien?

    • @mxslick50
      @mxslick50 Рік тому

      Nope. Bosch.

    • @SuperComfee
      @SuperComfee Рік тому +2

      navien is better than bosch for Tankless

    • @mxslick50
      @mxslick50 Рік тому +1

      @@SuperComfee You are obviously new to this channel..lol. Prepare to get flamed in the comments. 🤣

    • @SuperComfee
      @SuperComfee Рік тому +1

      @@mxslick50 T9800SE Greentherm models have issues all the time

    • @SuperComfee
      @SuperComfee Рік тому +1

      @@mxslick50 they look nice but the best is viessmann

  • @DavidButler-b9g
    @DavidButler-b9g Рік тому +1

    No site glass to see the flame or ignition!

    • @SuperComfee
      @SuperComfee Рік тому

      theres a small one, often gets dirty and doesn't work, some companies include a replacement screen

  • @nosaya3
    @nosaya3 Рік тому +2

    Why would anyone choose to install these types of units in their homes over more time tested options?

    • @mxslick50
      @mxslick50 Рік тому

      Space limitations, efficiency. Endless hot water. Lower operating costs over the unit life. IF properly maintained (which is not that difficult or expensive) a unit like this will last as long or longer than 2 or 3 conventional tank types. (Takagi warranties their heat exchanger for 15 years.)

    • @SuperComfee
      @SuperComfee Рік тому +1

      storage tanks require to be maintained at a certain temperature, which passively uses energy..
      some of these boilers are capable of heating your house like a boiler and also providing potable water as well ( combi ), they save space.
      overpriced, storage tank heaters are fine, just put a timer on them and only have them heat your tank at night rates

    • @SuperComfee
      @SuperComfee Рік тому

      Also these require maintenance, it’s not uncommon to go 15 years no service on storage tanks whereas these will hit you in maintenance and more water usage, destroying your dreams of ever saving any money

    • @SuperComfee
      @SuperComfee Рік тому

      As a tech I’m not complaining gives me job but does not save money

    • @scotts4125
      @scotts4125 Рік тому +1

      @@SuperComfee I flush my Rinnai once a year. Just did mine this weekend. It's 4 years old. I took the flame rods out to inspect them. I have brand new ones on hand as well. They were completely intact. I hit them with Scotch Brite and put them back in. I know none of my neighbors are doing any kind of maintenance on theirs so time will tell. I have almost every spare part on hand just in case.

  • @consolidatedplumbingandhea4390

    Why I gave up on wall hung junk. Almost all the brands that were the latest and greatest become junk. I got sick off off hour calls for broken systems with no technical or parts support. Homeowners with 20 to 30 thousand dollar installs under 10 and especially 5 years old. They would look at me and ask why the are paying so much repairs and the old cast iron boiler they could forget about for years. May be saving gas usage but flushing money down the drain. Most technicians I know are tired of constantly tossing parts into the same machine. Orver 5 years old its broken, it gets replaced.

  • @scottmaz4063
    @scottmaz4063 Рік тому +4

    #2

  • @scottvolage1752
    @scottvolage1752 Рік тому +1

    Making the trades great again. #LoveBosch Keep up the good work Mikey Pipes. Smash the like button please.

  • @Wolfhound.
    @Wolfhound. Рік тому

    im not going to say it cause you know what it looks like lol good gosh

  • @tonybochiano
    @tonybochiano 10 місяців тому

    If Bosch is so good why is it leaking

  • @tmacgee1234
    @tmacgee1234 Рік тому +1

    looked like a navien at first.

  • @tphvac87
    @tphvac87 Рік тому

    Looks exactly like a lochinvar primary loop HX only branded as Bosch…yet it looks like a Navien HX wahwahwahhhhh

  • @fernandoprieto2865
    @fernandoprieto2865 24 дні тому

    I think Rinai machine is better

  • @stevelammers2536
    @stevelammers2536 3 місяці тому

    That unit is only a year old should b under warranty

  • @scotts24d
    @scotts24d Рік тому +1

    All these Tankless videos tech never solves the problem 👎

  • @donaldfournier9059
    @donaldfournier9059 Рік тому +1

    Why does this look soooo much like a NAVIEN ?

    • @mnhvacguy9788
      @mnhvacguy9788 Рік тому

      Because Bosch/Buderus contracted with Navien to make the heat exchangers. It even says Navien on the metal plate

    • @mxslick50
      @mxslick50 Рік тому

      The heat exchanger is made in Korea but a different plant. (At least that's what it looks like from the nameplate.)

    • @Shadi2
      @Shadi2 Рік тому +1

      @@mxslick50 probably the same plant, they just put a different nameplate during 2nd shift.

    • @mxslick50
      @mxslick50 Рік тому

      @@Shadi2 Yep. Mine ( A Takagi, also branded AO Smith over here) has the labels rather crooked, must have been done on the Friday 5pm hour. 😁

  • @everettstevenson2111
    @everettstevenson2111 Рік тому

    Hey Jack Daniel, of Mikey Pipes Plumbing not easy being cheesy. The news was about the gospel according to Mikey ? you talk about your jewish jesus again, unquote. But again, like it said, on the back of the US one dollar bill, I'm going to have my eye on you too. Love you buddy, I'm don't know about Mikey and this broke back mountain thing again. I have install a like of cast iron bath tubs too.

  • @mikebaranHVACGOD
    @mikebaranHVACGOD 3 місяці тому +1

    Now That Trump Is Back More Folks Will Be Able To Afford Bosch Products

  • @jimmyjamesl2318
    @jimmyjamesl2318 Рік тому

    They didn't paint the plywood blue...automatically FAIL!

  • @rickydudderidge9404
    @rickydudderidge9404 Рік тому

    Just as crappy as a Navien! No good boilers made nowadays

  • @MustPassTruck
    @MustPassTruck 10 місяців тому

    These things look way too cheaply built to cost so much.

    • @PipeDoctor
      @PipeDoctor  10 місяців тому

      Why do you think so?

    • @MustPassTruck
      @MustPassTruck 10 місяців тому

      @@PipeDoctor I have completely disassembled mine and put it back together. The parts are similar in quality to a cheap gas grill. Had to patch the condenser section with bondo it was so badly corroded. Quietside boiler. Maybe a higher end one like Lockinvar would be different, but they cost 3 times more.
      By the way.. Thanks for the videos.

  • @kat2641
    @kat2641 Рік тому

    😂😂 at first I thought it was our nemesis (“[]”) that would of not shocked me … But a Bosch ??😮 no no no they don’t do that !!!